background image

Oasis 

 

INSTALLATION 

 MANUAL

©2015 Innovair Corporation.  All Rights Reserved.

www.innovair.com

WOE10C2DB1 / HOE10C2MR83

WOE13C2DB1 / HOE13C2MR83

WOE18C2DB1 / HOE18C2MR83

WOE24C2DB1 / HOE24C2MR83

WOE36C2DB1 / HOE10C2MR1

MINI SPLIT SYSTEM

 

Summary of Contents for Oasis WOE10C2DB1 / HOE10C2MR83

Page 1: ...TALLATION MANUAL 2015 Innovair Corporation All Rights Reserved www innovair com WOE10C2DB1 HOE10C2MR83 WOE13C2DB1 HOE13C2MR83 WOE18C2DB1 HOE18C2MR83 WOE24C2DB1 HOE24C2MR83 WOE36C2DB1 HOE10C2MR1 MINI SPLIT SYSTEM ...

Page 2: ...s unit This appliance is not intended for use by persons including children with reduced physical sensory or mental capabilities or lack of experience and knowledge unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety Young children should be supervised to ensure that they do not play with the air conditioner If the power c...

Page 3: ...utlet must be used If electrical circuit capacity is not enough or defect found in electrical work it will cause electrical shock fire 6 Use the specified cable and connect tightly and clamp the cable so that no external force will be acted on the terminal If connection or fixing is not perfect it will cause heat up or fire at the connection 7 Wiring routing must be properly arranged so that contr...

Page 4: ...ld have more than 200cm 78 74in of clearance and the connection side right side should have more than 60cm 23 62in of clearance Do not place animals and plants in the path of the air inlet or outlet Take the air conditioner weight into account and select a place where noise and vibration will not be an issue Select a place so that the warm air and noise from the air conditioner do not disturb neig...

Page 5: ...ilter used to install on Air filter 1 depending on models 11 Sound deadening pads used to wrap up the 2 quick connectors Note Except the above parts provided the other parts needed during installation you must purchase Fig 3 c CAUTION Use a stud finder to locate studs to prevent unnecessary damage to the wall Two of the A Band C directions should be free from obstructions This illustration is for ...

Page 6: ...ar side refrigerantpipe hole I 90 3 54in 9000Btu h models A 680 26 77 B 255 10 04 C 170 6 69 D 92 3 62 12000Btu h models A 770 30 31 B 255 10 04 C 170 6 69 D 95 3 74 Indoor unit outline 150mm 5 91in or more to ceilin b c 20mm 4 72in Dimensions are in mm in unless otherwise stated 120mm 4 72in I I or more to wall 1 I I or more to wall I 120mm 4 72in I or more to wall I Left rear side refrigerant Pi...

Page 7: ...stalled correctly as described in the instructions Do not remove the sealing caps and stoppers until immedi ately before you install the lines To prevent leaks ensure that the quick release screw connections are absolutely free of dirt Moisture or foreign bodies will adversely affect the function of the quick release connectors leading to a risk of refrigerant loss not covered by the warranty Only...

Page 8: ...m 2 Align the refrigerant pipes correctly make sure the dimensions of the connecting refrigerant pipe are the same Place the screw connector on the refrigerant pipes just on to the thread on the indoor equipment and tighten the first few threads by hand See Fig 9 IMPORTANT Before you continue it is essential that you read the following instructions carefully 3 Hold the points marked A using a 22mm...

Page 9: ... the indoor unit Be careful not to let the drain hose slack Heat insulate both of the auxiliary piping Be sure that the drain hose is located at the lowest side of the bundle Locating at the upper side can cause drain pan to overflow inside the unit Never intercross nor intertwist the power wire with any other wiring Run the drain hose sloped downward to drain out the condensed water smoothly 5 In...

Page 10: ... unit with a bolt and nut l 10 or l 8 tightly and horizontally on a concrete or rigid mount Outdoor unit dimension Mounting dimensions mm in WxHxD A mm in B mm in 760 29 92 x590 23 23 x285 11 22 530 20 87 290 11 42 820 32 28 x595 23 43 x330 12 99 523 20 59 340 13 39 780 30 71 x540 21 26 x250 9 84 549 21 61 276 10 87 660 25 98 x242 9 52 x540 21 26 458 18 03 276 10 87 840 33 07 x700 27 56 x320 12 6 ...

Page 11: ...w connector on the refrigerant line just on to the thread on the outdoor unit and tighten the first few threads by hand Fig 22 NOTE The refrigerant pipes must be connected to the valves on the outdoor unit with as little stress as possible IMPORTANT Before you continue it is essential I that you read the following instructions carefully 4 Now tighten the bottom screw connector first and then the t...

Page 12: ...o using a 5 mm Allen key The valve is now open If the valve is not opened fully the system may malfunction and suffer damage Screw the cover back on to the bottom valve and tighten it well to ensure that it is properly sealed See Fig 25 Important The conical ring on the valve has an Newton meter N m Kilogram force meter kgf m 24 4 27 1 2 4 2 7 40 6 47 4 4 1 4 8 61 0 67 7 6 2 6 9 81 3 88 1 8 2 8 9 ...

Page 13: ...Connection at the condesnser slides over the spade Air Handler Connection Air handler preconnected at factory no connection needed Grounding Wire Use screw to connect to ground 2015 Innovair Corporation All Rights Reserved www innovair com ...

Page 14: ...ote controller is disabled or maintenance is necessary Hold the panel sides and lift the panel up to an angle until it remains fixed with a clicking sound Press the Manual control button to select the AUTO or COOL the unit will operate under Forced AUTO or COOL mode see User Manual for details 4 The test operation should last 30 minutes Manual control button AUTO COOL TEST RUNNING Fig 27 Fig 28 14...

Page 15: ...ir gap contact separationof at Ieast 3mm ineach active phase conductors Electricalwork Electric safety regulations for the initial Installation 1 If there is serious safety problem about the power supply the technicians should refuse to install the air conditioner and explain to the client until the problem is solved 2 Power voltage should be in the range of 90 11 0 of ratedvoltage 3 The creepage ...

Page 16: ...trical components Secure the cable onto the control board with the cord clamp Connect the cable to the outdoor unit 1 Remove the electricalcontrolboardcover from the outdoorunitby loosening the screw 2 Connect the connective cables to the terminals as identifiedwith their respective matched numbers on the terminalblock of indoor and outdoorunits 3 Secure the cable onto the controlboardwiththe cord...

Page 17: ...Innovair Corporation 11490 NW 39th Street Miami FL 33178 www innovair com 2015 Innovair Corporation All Rights Reserved www innovair com ...

Reviews: