D-EIMW C00508-16EN - 6/48
Two Compressors Unit
1
– Unit nameplate data
6
– Non flammable gas symbol
2
– Lifting instructions
7
– Manufacturer’s logo
3
– Hazardous Voltage warning
8
– Gas type
4
– Cable tightening warning
9
– Electrical hazard symbol
5
– Water circuit filling warning
10
– Emergency stop
Operating limits
Storing
The units of the series can be stored under the following environmental conditions:
Minimum ambient temperature
:
-20°C
Maximum ambient temperature
:
41°C
Max. R.H.
:
95% not condensing
ATTENTION
Storing below the minimum temperature mentioned above may cause damage to components such as the electronic
controller and its LCD display.
WARNING
Storing above the maximum temperature may cause opening of the safety valves on the compressor’s suction li ne.
ATTENTION
Storing in condensing atmosphere may damage the electronic components.
Operation
Operation is allowed within the limits mentioned in the following diagrams.
ATTENTION
Operation outside the mentioned limits may damage the unit.
In case of doubt contact the manufacturer.