3. The charge can be added at any load condition.
Charging the refrigerant
1. Connect the refrigerant bottle with a filling pipe to the filling valve on the evaporator head. Before firmly
tightening the refrigerant bottle valve, open it and force the air out from the filling pipe. Tighten the charging
valve connection and fill the refrigerant.
2. When the refrigerant stops to enter the system, start the compressor and complete the refrigerant charge.
3. If you do not know how much refrigerant has to be added, shut off the bottle valve every 5 minutes and continue
to charge the refrigerant until the sight glass is clear and free from bubbles.
Note: Do not discharge the refrigerant into the atmosphere. To recover it, use empty, clean and dry bottles. The
liquid refrigerant recovery can be made through the valve provided on the condenser coil sub-cooler outlet. To
facilitate the recovery of refrigerant, put the bottle inside a container full of ice; avoid excessive filling of the bottle
(70÷80% max).