11
|
Commissioning
Installer reference guide
219
EPRA14~18D + ET23E
Daikin Altherma 3 H HT F
4P644739-1A – 2022.03
Typical workflow
Purging the air from the system should consist of:
1
Performing a manual air purge for both zones
2
Performing an automatic air purge for both zones
INFORMATION
Start by performing a manual air purge. When almost all the air is removed, perform
an automatic air purge. If necessary, repeat performing the automatic air purge until
you are sure that all air is removed from the system. During air purge function, pump
speed limitation [9‑0D] is NOT applicable.
The air purge function automatically stops after 30 minutes.
INFORMATION
For best results, air purge each loop separately.
Status of valve and pumps during air purge
Status
Air purge on zone …
Main zone (mixed)
Additional zone
(direct)
Tank (domestic hot
water)
Mixing valve
Fully open
Bypassed
Bypassed
Pump main zone
ON
OFF
OFF
Pump additional
zone
OFF
ON
ON
Example:
Air purge on main zone:
a
b
d
c
M3S
M1S
35°C
45°C
45°C
Example:
Air purge on additional zone:
a
b
d
c
M3S
M1S
35°C
45°C
45°C