9
|
Electrical installation
Installer reference guide
95
EPRA14~18D + ET23E
Daikin Altherma 3 H HT F
4P644739-1A – 2022.03
Wires: 1N+GND
Maximum running current: Refer to name plate on unit.
—
L N PE
b
a
L
N
Q1DI
1N~,
50 Hz,
230 V AC
F1B
1
3
2
4
I
I
BRN
BLU
YLW/GRN
b
a
L
N
a
Power supply cable (field supply)
b
Field wiring
F1B
Overcurrent fuse (field supply). Recommended fuse: 2 pole, 32 A fuse, C curve.
Q1DI
Earth leakage circuit breaker (30 mA)(field supply)
2
Interconnection cable
(indoor↔outdoor):
▪
Route the cable through the frame.
▪
Connect the wires to the terminal block (make sure the numbers match with
the numbers on the indoor unit) and the earth screw.
▪
Fix the cable with a cable tie.
Wires: (3+GND)×1.5 mm²
—
Summary of Contents for ETVZ16E6V7
Page 281: ......
Page 282: ......
Page 283: ......
Page 284: ...4P644739 1A 2022 03 Copyright 2021 Daikin Verantwortung f r Energie und Umwelt...