6
|
Application guidelines
Installer reference guide
63
EPRA14~18D + ETSH/X(B)16P30+50E
Daikin Altherma 3 H HT ECH₂O
4P679467-1C – 2023.07
P
i
t
DI4
DI3
DI1
a
b
P
i
Power input
t
Time
DI
Digital inputs (power limitation levels)
a
Power limitation active
b
Actual power input
Setup
▪
Demand PCB (option EKRP1AHTA) needed.
▪
Maximum four digital inputs are used to activate the corresponding power
limitation level:
-
DI1 = strongest limitation (lowest energy consumption)
-
DI4 = weakest limitation (highest energy consumption)
▪
Specification of the digital inputs:
-
DI1: S9S (limit 1)
-
DI2: S8S (limit 2)
-
DI3: S7S (limit 3)
-
DI4: S6S (limit 4)
▪
Refer to the wiring diagram for more information.
Configuration
▪
Set the power consumption control settings in [9.9] via the user interface (for the
description of all settings, see
215]):
-
Select limitation by digital inputs.
-
Select the type of limitation (power in kW or current in A).
-
Set the desired power limitation level corresponding to each digital input.
INFORMATION
In case more than 1 digital input is closed (at the same time), the digital input priority
is fixed: DI4 priority>…>DI1.
6.6.3 Power limitation process
The outdoor unit has better efficiency than the electrical heater. Therefore, the
electrical heater is limited and turned OFF first. The system limits power
consumption in the following order:
1
Turns OFF the backup heater.
2
Limits the outdoor unit.
3
Turns OFF the outdoor unit.
Example
If the configuration is as follows: Power limitation level does NOT allow operation
of backup heater (step 1).
Then power consumption is limited as follows:
Summary of Contents for ETSXB16E
Page 313: ......
Page 314: ......
Page 315: ......
Page 316: ...4P679467 1C 2023 07 Copyright 2022 Daikin Verantwortung f r Energie und Umwelt...