15/19
Breadcrumb
Setting name
Range, step
Default value
Field settings table
9.I
[6-01]
R/W
0~10°C, step: 1°C
0°C
9.I
[6-02]
R/W
0~10kW, step: 0,2kW
0kW
9.I
[6-03]
R/O
0~10kW, step: 0,2kW
0kW
2kW (*5)
3kW (*4, *6, *7)
9.I
[6-04]
R/W (*5,
*6)
R/O (*4,
*7)
0~10kW, step: 0,2kW
0kW (*4)
3kW (*7)
4kW (*5)
6kW (*6)
9.I
[6-07]
0
9.I
[6-08]
R/W
2~20°C, step: 1°C
10°C
9.I
[6-09]
0
9.I
[6-0A]
R/W
30~[6-0E]°C, step: 1°C
60°C
9.I
[6-0B]
R/W
30~min(50, [6-0E])°C, step: 1°C
45°C
9.I
[6-0C]
R/W
30~min(50, [6-0E])°C, step: 1°C
45°C
9.I
[6-0D]
R/W
0: Reheat only
3 scheduled reheat
9.I
[6-0E]
R/W
E-07 = 4
40~ 75°C, step: 1°C
65°C
9.I
[7-00]
R/W
0~4°C, step: 1°C
0°C
9.I
[7-01]
R/W
2~40°C, step: 1°C
2°C
9.I
[7-02]
R/W
0: Single zone
1: Dual zone
9.I
[7-03]
2,5
9.I
[7-04]
0
9.I
[7-05]
R/W
0: Very high
1: High
2: Medium
3: Low
4: Very low
9.I
[7-06]
R/W
0: Disabled
1: Enabled
9.I
[7-07]
R/W
0: No
1: Yes
9.I
[7-09]
R/W
20%
9.I
[7-0A]
R/W
20~95%, step 5%
95%
9.I
[7-0B]
R/W
20~95%, step 5%
95%
9.I
[7-0C]
R/W
20~300 seconds, step 5 sec
125 seconds
9.I
[7-0D]
R/W
2~20, step 0,5 °C
4 °C
9.I
[7-0E]
R/W
2~22, step 0,5 °C
7 °C
9.I
[8-00]
R/W
0~20 min, step 1 min
1 min
9.I
[8-01]
R/W
5~95 min, step: 5 min
30 min
9.I
[8-02]
R/W
0~10 hour, step: 0,5 hour
0,5 hour
Anti-recycling time.
Maximum running time for domestic hot water operation.
What is the desired eco storage temperature?
What is the desired reheat temperature?
BBR16 activation*
*BBR16 settings are only visible when the language of the user
interface is set to Swedish.
Minimum running time for domestic hot water operation.
How much is the minimum pump PWM value.
Additional zone fixed pump PWM, in case a bizone kit is installed.
Main zone fixed pump PWM, in case a bizone kit is installed.
Time needed by the mixing valve to turn from one side to the
other, in case a bizone kit is installed.
Offset on the setpoint to determine when the tank is high enough
to go the excess state
What is the desired DHW production type?
What is the maximum temperature setpoint?
Domestic hot water booster heater overshoot temperature.
Domestic hot water booster heater hysteresis.
How many leaving water temperature zones are there?
--
--
Boiler efficiency
HP forced OFF
Hysteresis value used to control the tank bivalent in case it’s
supporting space heating operation
The temperature difference determining the heat pump OFF
temperature.
What is the capacity of the booster heater?
What is the capacity of the backup heater step 1?
What is the capacity of the backup heater step 2?
--
What is the desired comfort storage temperature?
What is the hysteresis to be used in reheat mode?
--
(*1) *X*_(*2) *H*_(*3) *B*_(*4) *EKECBUA*3V_
(*5) *EKECBUA*6V_(*6) *EKECBUA*9W_(*7) BUH less_
(*8) 300L tank_(*9) E_(*10) E7
4P681797-1C - 2023.07