Installer reference guide
37
EHBH/X16
Daikin Altherma - Low Temperature Split
4P313776-1 – 2012.05
8 Configuration
[A.3.1.1.3]
[1-00]
[1-01]
[1-02]
[1-03]
Set weather-dependent heating:
Q
T
t
: Target leaving water
temperature (main)
Q
T
a
: Outdoor temperature
Q
[1-00]: Low outdoor ambient
temperature. –20°C~5°C (default:
–10°C)
Q
[1-01]: High outdoor ambient
temperature. 10°C~20°C (default:
15°C)
Q
[1-02]: Desired leaving water
temperature when the outdoor
temperature equals or drops below
the low ambient temperature.
Between minimum and maximum
leaving water temperature (default:
40°C).
Note: This value should be higher
than [1-03] as for low outdoor
temperatures warmer water is
required.
Q
[1-03]: Desired leaving water
temperature when the outdoor
temperature equals or rises above
the high ambient temperature.
Between minimum and maximum
leaving water temperature (default:
25°C).
Note: This value should be lower
than [1-02] as for high outdoor
temperatures less warm water is
required.
#
Code
Description
[1-03]
[1-02]
Ta
Tt
[1-00]
[1-01]
[A.3.1.1.4]
[1-06]
[1-07]
[1-08]
[1-09]
Set weather-dependent cooling:
Q
T
t
: Target leaving water
temperature (main)
Q
T
a
: Outdoor temperature
Q
[1-06]: Low outdoor ambient
temperature. 10°C~25°C (default:
20°C)
Q
[1-07]: High outdoor ambient
temperature. 25°C~43°C (default:
35°C)
Q
[1-08]: Desired leaving water
temperature when the outdoor
temperature equals or drops below
the low ambient temperature.
Between minimum and maximum
leaving water temperature (default:
22°C).
Note: This value should be higher
than [1-09] as for low outdoor
temperatures less cold water
suffices.
Q
[1-09]: Desired leaving water
temperature when the outdoor
temperature equals or rises above
the high ambient temperature.
Between minimum and maximum
leaving water temperature (default:
18°C).
Note: This value should be lower
than [1-08] as for high outdoor
temperatures colder water is
required.
#
Code
Description
[1-09]
[1-08]
Ta
Tt
[1-06]
[1-07]