EHBH/X16
Daikin Altherma - Low Temperature Split
4P313776-1 – 2012.05
Installer reference guide
36
8 Configuration
Energy metering
When energy metering is performed by the use of external power
meters, configure the settings as described below. Select the pulse
frequency output of each power meter in accordance with the power
meter specifications. It is possible to connect (up to 2) power meters
with different pulse frequencies. When only 1 or no power meter is
used, select No to indicate the corresponding pulse input is NOT
used.
8.2.4 Quick wizard: Capacities (energy metering)
The capacities of all electrical heaters must be set for the energy
metering and/or power consumption control feature to work properly.
When measuring the resistance value of each heater, you can set the
exact heater capacity and this will lead to more accurate energy data.
8.2.5 Space heating/cooling control
The basic required settings in order to configure the space
heating/cooling of your system are described in this chapter. The
weather-dependent installer settings define the parameters for the
weather-dependent operation of the unit. When weather-dependent
operation is active, the water temperature is determined
automatically depending on the outdoor temperature. Low outdoor
temperatures will result in warmer water and vice versa. During
weather-dependent operation, the user has the possibility to shift up
or down the target water temperature by a maximum of 5°C.
See the user reference guide and/or operation manual for more
details about this function.
Leaving water temperature: Main zone
#
Code
Description
[A.2.2.8]
[D-08]
Optional external kWh meter 1:
Q
0 (No): NOT installed
Q
1: Installed (0.1 pulse/kWh)
Q
2: Installed (1 pulse/kWh)
Q
3: Installed (10 pulse/kWh)
Q
4: Installed (100 pulse/kWh)
Q
5: Installed (1000 pulse/kWh)
[A.2.2.9]
[D-09]
Optional external kWh meter 2:
Q
0 (No): NOT installed
Q
1: Installed (0.1 pulse/kWh)
Q
2: Installed (1 pulse/kWh)
Q
3: Installed (10 pulse/kWh)
Q
4: Installed (100 pulse/kWh)
Q
5: Installed (1000 pulse/kWh)
#
Code
Description
[A.2.3.1]
[6-02]
Booster heater: Only applies to domestic
hot water tanks with an internal booster
heater (EKHW*) The capacity of the
booster heater at nominal voltage.
Nominal value is 3 kW. Default: 0.
0~10 kW (in steps of 0.2 kW)
[A.2.3.2]
[6-03]
BUH: step 1: The capacity of the first
step of the backup heater at nominal
voltage. Nominal value 3 kW. Default:
3 kW.
0~10 kW (in steps of 0.2 kW)
[A.2.3.3]
[6-04]
BUH: step 2: Only applies to a two-step
backup heater (*9W). The capacity
difference between the second and first
step of the backup heater at nominal
voltage. Nominal value depends on the
backup heater configuration:
Q
3 kW, 1N~ 230 V: 0 kW
Q
6 kW, 1N~ 230 V: 3 kW (6 kW-3 kW)
Q
6 kW, 3~ 230 V: 3 kW (6 kW-3 kW)
Q
6 kW, 3N~ 400 V: 3 kW (6 kW-3 kW)
Q
9 kW, 3N~ 400 V: 6 kW (9 kW-3 kW)
0~10 kW (in steps of 0.2 kW):
Q
*3V: default 0 kW
Q
*9V: default 6 kW
[A.2.3.6]
[6-07]
Bottom plate heater: Only applies to an
optional bottom plate heater
(EKBPHTH16A). The capacity of the
optional bottom plate heater at nominal
voltage. Default: 0 W.
0~200 W (in steps of 10 W)
#
Code
Description
[A.3.1.1.1]
N/A
LWT setpoint mode:
Q
Absolute (default)
The desired leaving water
temperature is:
Q
NOT weather-dependent (i.e.
does not depend on the
outdoor ambient temperature)
Q
fixed in time (i.e., not
scheduled)
Q
Weather dep.: The desired leaving
water temperature is:
Q
weather-dependent (i.e.
depends on the outdoor
ambient temperature)
Q
fixed in time (i.e., not
scheduled)
Q
Abs + scheduled: The desired
leaving water temperature is:
Q
NOT weather-dependent (i.e.,
does NOT depend on the
outdoor ambient temperature)
Q
according a schedule. The
scheduled actions consists of
desired leaving water
temperatures either preset or
custom
Remark: This value can only
be set in leaving water
temperature control.
Q
WD + scheduled: The desired
leaving water temperature is:
Q
weather-dependent (i.e., does
depend on the outdoor
ambient temperature)
Q
according a schedule. The
scheduled actions consists of
desired leaving water
temperatures either preset or
custom
Remark: This value can only
be set in leaving water
temperature control.
Summary of Contents for ERLQ011CA
Page 83: ......