EHBH/X16
Daikin Altherma - Low Temperature Split
4P313776-1 – 2012.05
Installer reference guide
38
8 Configuration
Leaving water temperature: Additional zone
Only applicable if 2 leaving water temperature zones are present.
#
Code
Description
[A.3.1.2.1]
N/A
LWT setpoint mode:
Q
Absolute (default)
The desired leaving water
temperature is:
Q
NOT weather-dependent (i.e.
does not depend on the
outdoor ambient temperature)
Q
fixed in time (i.e., not
scheduled)
Q
Weather dep.: The desired leaving
water temperature is:
Q
weather-dependent (i.e.
depends on the outdoor
ambient temperature)
Q
fixed in time (i.e., not
scheduled)
Q
Abs + scheduled: The desired
leaving water temperature is:
Q
NOT weather-dependent (i.e.,
does NOT depend on the
outdoor ambient temperature)
Q
according a schedule. The
scheduled actions are On or
OFF.
Remark: This value can only
be set in leaving water
temperature control.
Q
WD + scheduled: The desired
leaving water temperature is:
Q
weather-dependent (i.e., does
depend on the outdoor
ambient temperature)
Q
according a schedule. The
scheduled actions are On or
OFF
Remark: This value can only
be set in leaving water
temperature control.
[A.3.1.2.3]
[0-03]
[0-02]
[0-01]
[0-00]
Set weather-dependent heating:
Q
T
t
: Target leaving water
temperature (main)
Q
T
a
: Outdoor temperature
Q
[0-03]: Low outdoor ambient
temperature. –20°C~5°C (default:
–10°C)
Q
[0-02]: High outdoor ambient
temperature. 10°C~20°C (default:
15°C)
Q
[0-01]: Desired leaving water
temperature when the outdoor
temperature equals or drops below
the low ambient temperature.
Between minimum and maximum
leaving water temperature (default:
40°C).
Note: This value should be higher
than [0-00] as for low outdoor
temperatures warmer water is
required.
Q
[0-00]: Desired leaving water
temperature when the outdoor
temperature equals or rises above
the high ambient temperature.
Between minimum and maximum
leaving water temperature (default:
25°C).
Note: This value should be lower
than [0-01] as for high outdoor
temperatures less warm water is
required.
#
Code
Description
[0-00]
[0-01]
Ta
Tt
[0-03]
[0-02]