ER3~10DA
Air-cooled condensing units
4PW00410-1C
Installation manual
5
Connection of the condensing unit power supply
1.
Using the appropriate cable (see table before), connect the
power circuit to the (N), L1, L2 and L3 terminals of the
condensing unit as shown on the wiring diagrams (see
figure 6
,
figure 7
and
figure 8
).
2.
Connect the earth conductor (yellow/green) to the earthing
terminal.
Interconnection cable
In addition to the power supply cable, a cable must be provided for
the interconnection between the condensing unit and the switch box
of the air conditioning unit.
The cable must be of the type H05VV-U5X1.5 and must be
connected to terminals 1, 3, 4, 5 and 6 of the condensing unit as
shown on the wiring diagrams (see
figure 6
,
figure 7
and
figure 8
).
Refer to the manual supplied with the air conditioning unit for the
connections at the switch box side.
H
OW
TO
CONTINUE
After installation and connection of both the condensing unit and the
air conditioner, the complete system should be checked and tested
as described in “Checks before initial start-up” in the operation
manual supplied with the condensing unit.
Fill out the brief operation instructions form and fix it visibly near the
operating site of the refrigeration system.
N
OTES