10
|
Configuration
Installer reference guide
189
EPRA08~W1 + ETSH/X(B)12P30+50EF
Daikin Altherma 3 H MT ECH₂O
4P663478-1B – 2022.07
[9-0D]=4/8
a (kPa)
b (l/min)
a
External static pressure
b
Water flow rate
Pump outside range
When the pump operation function is disabled the pump will stop if the outdoor
temperature is higher than the value set by the
Space heating off
temperature
[4‑02] or if the outdoor temperature drops below the value set by
the
Space cooling off temperature
[F‑01]. When the pump operation is
enabled, the pump operation is possible at all outdoor temperatures.
#
Code
Description
[4.9]
[F-00]
Pump operation:
▪
0: Disabled if outdoor temperature is higher
than [4‑02] or lower than [F‑01] depending on
heating/cooling operation mode.
▪
1: Possible at all outdoor temperatures.
Increase around 0°C
Use this setting to compensate for possible heat losses of the building due to the
evaporation of melted ice or snow. (e.g. in cold region countries).
In heating operation, the desired leaving water temperature is locally increased
around an outdoor temperature of 0°C.This compensation can be selected when
using an absolute or a weather dependent desired temperature (see illustration
below).
T
t
T
A
R
L
0°C
T
t
T
A
R
L
0°C
a
b
a
Absolute desired LWT
b
Weather dependent desired LWT
#
Code
Description
[4.A]
[D-03]
Increase around 0°C
:
▪
0:
No
▪
1:
increase 2°C, span 4°C
▪
2:
increase 4°C, span 4°C
▪
3:
increase 2°C, span 8°C
▪
4:
increase 4°C, span 8°C
Summary of Contents for EPRA10EAV3
Page 302: ......
Page 303: ......
Page 304: ...4P663478 1B 2022 07 Copyright 2021 Daikin Verantwortung f r Energie und Umwelt...