10
|
Configuration
Installer reference guide
164
EPRA08~W1 + ETSH/X(B)12P30+50EF
Daikin Altherma 3 H MT ECH₂O
4P663478-1B – 2022.07
NOTICE
Room frost protection.
Even if you turn OFF space heating/cooling operation ([C.2]:
Operation
>
Space heating/cooling
), room frost protection operation –if
enabled– can still activate. However, for leaving water temperature control and
external room thermostat control, the protection is NOT guaranteed.
For more detailed information about room frost protection in relation to the
applicable unit control method, see the sections below.
Leaving water temperature control ([C‑07]=0)
Under leaving water temperature control, room frost protection is NOT
guaranteed. However, if room antifrost [2‑06] is activated, limited frost protection
by the unit is possible:
If...
Then...
▪
Space
heating/cooling
=
Off
,
and
▪
Outdoor ambient temperature drops
below 6°C
▪
The unit will supply leaving water to
the heat emitters to heat up the room
again, and
▪
the temperature setpoint of the
leaving water will be lowered.
▪
Space heating/cooling
=
On
, and
▪
Operation mode
=
Heating
The unit will supply leaving water to the
heat emitters to heat up the room
according to normal logic.
▪
Space heating/cooling
=
On
, and
▪
Operation mode
=
Cooling
There is no room frost protection.
External room thermostat control
([C‑07]=1)
Under external room thermostat control, room frost protection is guaranteed by
the external room thermostat, provided that:
▪
[C.2]
Space heating/cooling
=
On
, and
▪
[9.5.1]
Emergency
=
Automatic
or
auto SH normal/DHW off
.
However, if [1.4.1]
Antifrost
is activated, limited frost protection by the unit is
possible.
In case of 1 leaving water temperature zone:
If...
Then...
▪
Space
heating/cooling
=
Off
,
and
▪
Outdoor ambient temperature drops
below 6°C
▪
The unit will supply leaving water to
the heat emitters to heat up the room
again, and
▪
the temperature setpoint of the
leaving water will be lowered.
▪
Space heating/cooling
=
On
, and
▪
The external room thermostat is
"Thermo OFF", and
▪
Outdoor temperature drops below
6°C
▪
The unit will supply leaving water to
the heat emitters to heat up the room
again, and
▪
the temperature setpoint of the
leaving water will be lowered.
▪
Space heating/cooling
=
On
, and
▪
The external room thermostat is
"Thermo ON"
Room frost protection is guaranteed by
the normal logic.
In case of 2 leaving water temperature zones: