10
|
Configuration
Installer reference guide
229
EPRA08~W1 + ETSH/X(B)12P30+50EF
Daikin Altherma 3 H MT ECH₂O
4P663478-1B – 2022.07
#
Code
Description
[9.P.3]
[7-0A]
Add zone pump fixed PWM
: Fixed pump
speed for additional (direct) zone.
▪
20~95% (default: 95)
Main zone pump fixed PWM
The speed of the main zone pump can be fixed with this setting.
#
Code
Description
[9.P.4]
[7-0B]
Main zone pump fixed PWM
: Fixed pump
speed for main (mixed) zone.
▪
20~95% (default: 95)
Mixing valve turning time
If a third party mixing valve is installed in combination with controller EKMIKPOA,
the valve turning time must be set accordingly.
For this setting, space heating/cooling and tank operation MUST be off:
[C.2]
Space
heating/cooling
=0 (
Off
) and [C.3]
Tank
=0 (
Off
). See
#
Code
Description
[9.P.5]
[7-0C]
Mixing valve turning time
: Time in
seconds for the mixing valve to turn from one
side to the other.
▪
20~300 sec (default: 125)
10.5.10 Commissioning
Overview
The following items are listed in the submenu:
A
Commissioning
User profile
Installer settings
Information
Operation
[A]
Commissioning
[A.1]
Operation test run
[A.2]
Actuator test run
[A.3]
Air purge
[A.4]
UFH screed dryout
About commissioning
See:
10.5.11 User profile
[B]
User profile
: See
"To change the user permission level"
143].
B
User profile
Operation
Commissioning
Installer settings
Malfunctioning
[B]
User profile