i
nstallation
C
onsiderations
IM 1059-12 LARGE VERTICAL WSHP
6
www.DaikinApplied.com
Vibration isolators
For minimum sound and vibration transmission, it is
recommended that the unit be mounted on vibration
isolators.
Holes are provided in the bottom panel to facilitate
connection of isolators (see
Figure 4
& 5 for hole locations).
Isolators supplied by the manufacturer are the type
shown in
Figure 3
. Four white isolators are used for single
compressor units and six green isolators are used for
dual compressor units. The holes in the bottom of the unit
allow for a 3⁄8" (10 mm) bolt to be secured to the isolator.
Figure 3: Vibration isolator dimensions
4½" (114 mm)
5½" (140 mm)
2½" (64 mm)
2⅝" (61 mm)
7/16" (11 mm)
3/8" (10 mm) TAP
Figure 4: Vibration isolators locations - single compressor unit
3" (76 mm)
3"
(76 mm)
3" (76 mm)
3" (76 mm)
Section A-A
2"
(51 mm)
A
A
28
5
/
32
"
(715 mm)
(4)
7
/
16
" (11 mm) holes
7
/
16
"
(11 mm)
1
/
4
"
(6 mm)
54
23
/
32
"
(1390 mm)
Figure 5: Vibration isolators locations - dual compressor unit
2"
(51 mm)
2" (51 mm)
30
1
/
8
"
(765 mm)
3
1
/
4
" (83 mm)
3
1
/
4
" (83 mm)
(6)
3
/
8
" (19 mm) holes
80
3
/
8
"
(2042 mm)
40
3
/
16
"
(1021 mm)