LARGE VERTICAL WSHP IM 1059-12
Note:
The settings of the hardware configuration jumpers are read when the controller is powered. Any changes to
the jumper settings require cycling power to the controller or sending a controller a reboot command through
the network communications.
Table 10: MicroTech III controller configuration jumper settings
Baseboard Description
Jumper(s)
Jumper Setting
Function
Normal / Test Mode
JP1
Open
Normal Operation
Shorted
Service / Test Mode
Fan Operation
JP2
Open
Continuous Fan Operation (On), when not operating in the unoccupied mode.
Shorted
Cycling Fan Operation (Auto)
Loop Fluid
JP3
(see warning)
Open
Water Loop Fluid - Water freeze protection (factory default setting)
Shorted
Glycol Loop Fluid - Systems with anti-freeze protection
Freeze Fault Protection
JP4
Open
None
Shorted
Freeze fault protection enabled
Room Sensor Setpoint
Potentiometer Range
JP5
Open
Short Range: -5 to +5 ºF (-2.78 to +2.78 ºC)
Shorted
Long Range: 55 to 95ºF (12.78 to 35ºC)
Thermostat / Room Sensor
JP6
Open
Thermostat Control
Shorted
Room Sensor Control
Compressor Availability
JP7 & JP8
JP7 Open
Both Compressors Available (default)
JP8 Open
JP7 Shorted
One Compressor Available
JP8 Open
JP7 Open
No Compressors Available
JP8 Shorted
WARNING
Jumper JP3 is factory provided in the open position. Extended range units require freeze protection down to 15 degrees. Jumper JP3 must
be field configured.
Figure 16: Location of configuration jumpers on the MicroTech III unit controller
Start-up
1 .
Open all valves to full open position and turn on
power to the conditioner.
2 .
Jumpers must be configured prior to connecting
supply power. See
Table 10
and
Table 11 on page
25
.