t
roubleshooting
Table 22: Compressor low suction temp
Description
Type
Yellow
Green
Red
Compressor Low Suction Temp
Fault
Flash
OFF
OFF
• Check water flow (heating operation)
• Check airflow (cooling operation)
• Entering water and air temperatures should be within the operating limits.
Table 23: Freeze fault detect
Description
Type
Yellow
Green
Red
Freeze Fault Detect
Fault
Flash
OFF
Flash
• Low entering water temperature (below 35
°
F standard range or 13.5
°
F extended range)
Table 24: Condensate overflow
Description
Type
Yellow
Green
Red
Condensate Overflow
Fault
ON
OFF
OFF
• Poor condensate drain
• Check the resistance to ground on condensate wire. This should be open if there is no water in the pan.
Table 25: Serial EEPROM corrupted
Description
Type
Yellow
Green
Red
Serial EEPROM Corrupted
Fault
ON
ON
ON
• Replace main board
Table 26: Waterside economizer low temp cutout (WSE control & call for cooling)
Description
Type
Yellow
Green
Red
Waterside Economizer Low Temp
Cutout (WSE Control & Call for
Cooling)
Mode
Flash
ON
Flash
• Water temperature is below 35
°
F.
Table 27: Service test mode enabled
Description
Type
Yellow
Green
Red
Service Test Mode Enabled
Mode
Flash
Flash
Flash
• Jumper JP1 is shorted for test mode operation.
Table 28: Unoccupied mode
Description
Type
Yellow
Green
Red
Unoccupied Mode
Mode
ON
ON
OFF
• Terminal U on main control board is connected to common from external source.
Table 29: Occupied, bypass, standby, or tenant override modes
Description
Type
Yellow
Green
Red
Occupied, Bypass, Standby, or Ten-
ant Override Modes
Mode
OFF
ON
OFF
• Unit is operating normal. It may currently have a control signal or ready to operate when a control signal is active.
IM 1059-12 LARGE VERTICAL WSHP
44 www.DaikinApplied.com