Daikin EKHVH008BB6V3 Installation Manual Download Page 5

EKHVH/X00 EKHVH/9WN

Daikin Altherma indoor unit

4PW64329-1 – 07.2010

Installation manual

3

3.

I

NTRODUCTION

3.1.

General information

Thank you for purchasing this indoor unit.

The unit is the indoor part of the air to water ERHQ or ERLQ heat
pumps. These units are designed for floor mounted indoor
installation. See 

"6.1. Selecting an installation location" on page 11

.

The units can be combined with Daikin fan coil units, floor heating
applications, low temperature radiators, Daikin domestic water
heating applications and solar kit for domestic hot water applications.

Heating/cooling units and heating only units

The unit range consists of two main versions: a heating/cooling
(EKHVX) version and a heating only (EKHVH) version.

Both versions are delivered with an integrated backup heater for
additional heating capacity during cold outdoor temperatures. The
backup heater also serves as a backup in case of malfunctioning of
the outdoor unit. The backup heater models are available for a
heating capacity of 6 and 9 kW, and – depending on the heating
capacity – for three different power supply specifications.

1

Heat pump capacity

2

Required heating capacity (site dependent)

3

Additional heating capacity provided by the backup heater

4

Equilibriumtemperature (can be set through the user 
interface, refer to 

"8.8. Field settings" on page 26

)

T

A

Ambient (outdoor) temperature

P

H

Heating capacity

3.2.

Combination and options

Domestic hot water tank (option)

An optional EKHTS* domestic hot water tank can be connected to
the indoor unit. The EKHTS* domestic hot water tank is available in
two different water capacities: 200 and 260 litre.

Refer to the domestic hot water tank installation manual for further
details.

Solar kit for domestic hot water tank (option)

For information concerning the EKSOLHT solar kit, refer to the
installation manual of that kit.

Digital I/O PCB kit (option)

An optional EKRP1HB digital I/O PCB can be connected to the
indoor unit and allows:

remote alarm output,

heating/cooling ON/OFF output,

bivalent operation (permission signal for the auxiliary boiler).

Refer to the operation manual of the indoor unit and to the installation
manual of the digital I/O PCB for more information.

Refer to the wiring diagram or connection diagram for connecting this
PCB to the unit.

Remote thermostat kit (option)

An optional room thermostat EKRTW or EKRTR can be connected to
the indoor unit. Refer to the installation manual of the room
thermostat for more information.

Connection to a benefit kWh rate power supply

This equipment allows for connection to benefit kWh rate power
supply delivery systems. Refer to 

"Connection to a benefit kWh rate

power supply" on page 22

 for more details.

3.3.

Scope of the manual

This manual does NOT include the selection procedure and the water
system design procedure. Only some precautions and tips and tricks
about the design of the water circuit are given in a separate chapter
of this manual.

Once the selection is done and the water system is designed, this
manual describes the procedures for handling, installing and
connecting the EKHV(H/X) units. This manual has been prepared to
ensure adequate maintenance of the unit, and it will provide help if
problems occur.

Indoor unit model

Backup heater capacity

Backup heater 

nominal voltage

EKHVX008BB6V3

6 kW

1x 230 V

EKHVX008BB6WN

6 kW

3x 400 V

EKHVX008BB9WN

9 kW

3x 400 V

T

A

4

3

1

2

P

H

Refer to the installation manual of the outdoor unit for items
not described in this manual.

The operation of the indoor unit is described in the indoor
unit operation manual.

Summary of Contents for EKHVH008BB6V3

Page 1: ...INSTALLATION MANUAL EKHVH008BB6V3 EKHVX008BB6V3 EKHVH008BB6WN EKHVX008BB6WN EKHVH008BB9WN EKHVX008BB9WN Daikin Altherma indoor unit...

Page 2: ...van 05 siguiendo las disposiciones de 06 secondo le prescrizioni per 07 v v v 08 de acordo com o previsto em 09 10 under iagttagelse af bestemmelserne i 11 enligt villkoren i 12 gitt i henhold til bes...

Page 3: ...view 24 8 2 Room thermostat installation con guration 24 8 3 Pump operation con guration 24 8 4 Domestic hot water tank installation con guration 25 8 5 Pre operation checks 25 8 6 Powering up the ind...

Page 4: ...power supply before removing the switchbox service panel or before making any connections or touching electrical parts Do not touch any switch with wet ngers Touching a switch with wet ngers can caus...

Page 5: ...tion manual for further details Solar kit for domestic hot water tank option For information concerning the EKSOLHT solar kit refer to the installation manual of that kit Digital I O PCB kit option An...

Page 6: ...pply 11 Domestic hot water tank optional 12 Heat exchanger coil FHL1 3 Floor heating loop T1 3 Individual room thermostat optional M1 3 Individual motorised valve to control loop FHL1 3 eld supply Pum...

Page 7: ...cooling mode The outdoor unit 1 will start operating to achieve the target leaving hot cold water temperature In case of cooling mode the 2 way valve 13 will close as to prevent cold water running thr...

Page 8: ...iliary boiler must be integrated in the piping work and in the eld wiring according to the illustrations below 1 Outdoor unit 2 Indoor unit 3 Heat exchanger 4 Backup heater 5 Pump 6 Shut off valve 7 S...

Page 9: ...water temperature is determined automatically depending on the outdoor temperature During heating operation of the boiler the boiler will operate so as to achieve the target leaving water temperature...

Page 10: ...of both zones is above the thermostat set point the outdoor unit and pump will stop operating The advantage of the dual set point control is that the heat pump will can operate at the lowest required...

Page 11: ...ned 5 2 Main components in the unit 1 Air purge valve Remaining air in the water circuit will be automatically removed via the air purge valve 2 Temperature sensors thermistors Temperature sensors det...

Page 12: ...t water tank The motorized 3 way valve controls whether the water outlet is used for space heating or the domestic hot water tank 20 T piece option delivered with the EKHTS domestic hot water tank 21...

Page 13: ...entioned in 12 Unit speci cations on page 44 due to environmental noise and sound re ections Choose the installation location carefully and do not install in a sound sensitive environment e g living r...

Page 14: ...Space required for refrigerant piping in case of left installation and electrical wiring D Space required for switch box removal 6 3 Inspecting handling and unpacking the unit At delivery the unit mu...

Page 15: ...and electrical wiring For each of these a dedicated knock out hole is foreseen at the backside of the unit 1 Knock out hole for refrigerant piping 2 Knock out hole for electrical wiring 3 Knock out h...

Page 16: ...with the unit should be installed so that normal servicing can be accomplished without draining the system Drain taps must be provided at all low points of the system to permit complete drainage of th...

Page 17: ...e is higher than 30 C and the humidity is higher than RH 80 then the thickness of the insulation materials should be at least 20 mm in order to avoid condensation on the surface of the insulation WARN...

Page 18: ...7 Shut off valve 8 Collector eld supply 10 By pass valve eld supply FHL1 3 Floor heating loop eld supply T1 3 Individual room thermostat optional M1 3 Individual motorised valve to control loop FHL1 3...

Page 19: ...the pre pressure of the expansion vessel When it is required to change the default pre pressure of the expansion vessel 1 bar keep in mind the following guidelines Use only dry nitrogen to set the exp...

Page 20: ...V for PCB V1S V2S Spark suppression 1 2 X1M X9M Terminal strip L Live N Neutral Field wiring Terminal strip Connector Terminal Protective earth BLK Black BLU Blue BRN Brown GRN Green GRY Grey ORG Oran...

Page 21: ...installation use normal kWh rate power supply for indoor unit Indoor power supply from outdoor standard Indoor power supply from outdoor standard User interface User interface Outside unit Outside uni...

Page 22: ...ion cable Power circuit and cable requirements Power supply for the indoor unit is to be provided through the outdoor unit Data communication with the outdoor unit is provided through the same cable F...

Page 23: ...et point contact is enabled See also 3 5 Typical application examples on page 4 and 7 Dual set point control on page 30 Contact requirements The contact shall be a voltage free contact that ensure 230...

Page 24: ...se rates seasonal rates W rmepumpentarif in Germany and Austria This equipment allows for connection to such bene t rate power supply delivery systems Consult with the electricity company acting as pr...

Page 25: ...ote controller and the terminals inside the unit P1 to X2M 16 P2 to X2M 16a 4 Reattach the upper part of the remote controller First begin tting from the clips at the bottom 1 When the signal is relea...

Page 26: ...opening the switch box service panel and making any changes to the DIP switch settings DIP switch SS2 Description ON OFF 1 Not applicable for installer Default 2 Domestic hot water tank installation...

Page 27: ...n page 44 Make sure that neither a fuse nor a protection device has been bypassed 7 Internal wiring Visually check the switch box on loose connections or damaged electrical components 8 Pipe size and...

Page 28: ...oor unit Each eld setting is assigned a 3 digit number or code for example 1 03 which is indicated on the user interface display The rst digit 1 indicates the rst code or eld setting group The second...

Page 29: ...f ces Field settings for cooling operation 1 05 Weather dependent for cooling function enable 1 disable 0 1 06 Low ambient temperature Lo2_A low outdoor temperature 1 07 High ambient temperature Hi2_A...

Page 30: ...n of the 3 way valve and the backup heater during domestic hot water operation When the space heating priority function is enabled it is assured that the full capacity of the heat pump is used as much...

Page 31: ...shing Powerful domestic water heating is deactivated automatically when the set point for the domestic hot water is reached Scheduled continuous domestic hot water reheat 6 05 Reheat de nes whether th...

Page 32: ...t setting If it seems that the domestic hot water night storage operation is not suf cient for your needs an additional scheduled reheat during daytime can be set A B C 6 08 B T t 2 03 6 07 Tdhw 6 04...

Page 33: ...0 Heating set point upper limit maximum leaving water temperature for heating operation 9 01 Heating set point lower limit minimum leaving water temperature for heating operation 9 02 Cooling set poin...

Page 34: ...iler When the bivalent operation function is enabled the indoor unit will stop automatically in space heating operation when the outdoor temperature drops below bivalent ON temperature and the permiss...

Page 35: ...ontact will close and the unit will go in forced off mode 2 When backup heater is forced off at bene t kWh rate power supply it is possible to de ne if pump operation is forced off or permited Refer t...

Page 36: ...ature below which space cooling is turned off Bottom plate heater control Applies only to installation with an outdoor unit ERLQ or in case the option bottom plate heater kit is installed F 02 Bottom...

Page 37: ...with domestic hot water tank without built in booster heater 4 05 5 60 xed 5 C 04 Interval for combination with domestic hot water tank without built in booster heater 4 05 5 60 40 60 5 min 3 Auto re...

Page 38: ...me 30 5 95 5 min 02 Anti recycling time 0 5 0 10 0 5 hour 03 Not applicable Do not change the default value 04 Additional running time at 4 02 F 01 95 0 95 5 min 9 Heating and cooling set point ranges...

Page 39: ...Depending on model 03 Liquid refrigerant temperature Read only 1 C 04 Inlet water temperature Read only 1 C F Option setup 00 Pump operation stop 0 0 1 01 Space cooling permission temperature 20 10 3...

Page 40: ...ng screed dry out program The program is used to dry out the screed of an under oor heating during the construction of a house Disclaimer 1 Even though the program will be executed automatically the d...

Page 41: ...times so the t icon will be displayed 2 To start the Under oor heating dry out program press the y button 3 The Under oor heating dry out program will start and display the action and temperature sett...

Page 42: ...supply is turned off because of high voltage risk The heater of the compressor may operate even in stop mode Please note that some sections of the electric component box are hot Make sure you do not t...

Page 43: ...l installer 11 1 General guidelines Before starting the troubleshooting procedure carry out a thorough visual inspection of the unit and look for obvious defects such as loose connections or defective...

Page 44: ...o return POSSIBLE CAUSES CORRECTIVE ACTION There is air in the system Purge air Water pressure at pump inlet is too low Check on the manometer that there is suf cient water pressure The water pressure...

Page 45: ...n Reset the thermal protector by pressing the reset button refer to 5 2 Main components in the unit on page 9 for location of the reset button Check the reset button of the thermal protector If both t...

Page 46: ...use Corrective action EKHVH008BB6V3 EKHVH008BB6WN EKHVH008BB9WN EKHVX008BB6V3 EKHVX008BB6WN EKHVX008BB9WN Casing material Pre coated sheet metal Pre coated sheet metal Dimensions HxWxD mm 705x600x695...

Page 47: ...NOTES NOTES...

Page 48: ...4PW64329 1 07 2010 Copyright 2010 Daikin...

Reviews: