Daikin EKHVH008BB6V3 Installation Manual Download Page 35

EKHVH/X00 EKHVH/9WN

Daikin Altherma indoor unit

4PW64329-1 – 07.2010

Installation manual

33

Additional external backup heater operation [C-02]=2

This function give the possibility to drive an additional external
backup heater.
The additional external backup heater can be used to assist space
heating (not domestic hot water heating) during low ambient
conditions.

The signal for additional external heater will be activated when the
second step of the internal backup heater is closed and when the
outdoor temperature goes below [C-03] setting with [C-04] hysteresis.

[C-02]=2 Additional external backup heater operation is
enabled (2)

[C-03] external backup heater ON temperature: defines the
outdoor temperature below which the permission signal for
the external backup heater will be active (closed, KCR on
EKRP1HB).

[C-04] external backup heater hysteresis

External backup heater signal X1–X2 (EKRP1HB)

[D] Benefit kWh rate power supply/Local shift value weather
dependent

Benefit kWh rate power supply

[D-00] Switching off heaters: Defines which heaters are
switched off when the benefit kWh rate signal of the
electricity company is received.
If [D-01]=1 or 2 and the benefit kWh rate signal of the
electricity company is received, following devices will be
switched off:

[D-01] Unit connection to benefit kWh rate power supply:
Defines whether or not the outdoor unit is connected to a
benefit kWh rate power supply.
If [D-01]=0, the unit is connected to a normal power supply
(default value).
If [D-01]=1 or 2, the unit is connected to a benefit kWh rate
power supply. In this case the wiring requires specific
installation like explained in 

"Connection to a benefit kWh

rate power supply" on page 22

When parameter [D-01]=1 at the moment that the benefit
kWh rate signal is sent by the electricity company, that
contact will open and the unit will go in forced off mode

(1)

.

When parameter [D-01]=2 at the moment that the benefit
kWh rate signal is sent by the electricity company, that
contact will close and the unit will go in forced off mode

(2)

.

When backup heater is forced off at "benefit kWh rate power
supply" it is possible to define if pump operation is forced off
or permited. (Refer to 

"[D-05]" on page 34

.)

Local shift value weather dependent

The local shift value weather dependent field setting is only relevant
in case weather dependent set point (see field setting 

"[1] Weather

dependent set point" on page 27

) is selected. 

[D-03] Local shift value weather dependent: determines the
shift value of the weather dependent set point around
outdoor temperature of 0°C.

CAUTION

The combination of setting [4-03]=0/2 with
bivalent operation at low outdoor temperature
can result in domestic hot water shortage.

The bivalent operation function has no impact on
the domestic water heating mode. The domestic
hot water is still and only heated by the indoor
unit.

The permission signal for the auxiliary boiler is
located on the EKRP1HB (digital I/O PCB). When
it is activated, the contact X1, X2 is closed and
open when it is disactivated. See figure for the
schematic location of this contact.

When [4-07] "Backup heater second step" is disabled, then
additional external backup heater signal will never be
activated.

T

A

Outdoor temperature

YC Y1 Y2 Y3 Y4

X1

X2

X3

X4

OFF ON

X2M

SS1

X1M

T

A

[C-03]

[C-04]

closed

open

[D-00]

Compressor

Backup heater

0 (default)

Forced off

Forced off

2

Forced off

Permitted

Do not select 1 or 3 value.

[D-00] settings 2 is only meaningful if the benefit
kWh rate power supply is of the type that power
supply is not interrupted.

(1) When the signal is released again, the voltage free contact will close and 

the unit will restart operation. It is therefore important to leave the auto 
restart function enabled. Refer to 

"[3] Auto restart" on page 28

.

(2) When the signal is released again, the voltage free contact will open and 

the unit will restart operation. It is therefore important to leave the auto 
restart function enabled. Refer to 

"[3] Auto restart" on page 28

.

T

t

Target water temperature

T

A

Outdoor temperature

R

Range

L

Local shift value

[1-00], [1-01], 

[1-02], [1-03]

Applicable field setting of the weather dependent set 
point [1]

T

A

T

t

[1-03]

[1-00]

0

°

C

[1-01]

[1-02]

L

R

Summary of Contents for EKHVH008BB6V3

Page 1: ...INSTALLATION MANUAL EKHVH008BB6V3 EKHVX008BB6V3 EKHVH008BB6WN EKHVX008BB6WN EKHVH008BB9WN EKHVX008BB9WN Daikin Altherma indoor unit...

Page 2: ...van 05 siguiendo las disposiciones de 06 secondo le prescrizioni per 07 v v v 08 de acordo com o previsto em 09 10 under iagttagelse af bestemmelserne i 11 enligt villkoren i 12 gitt i henhold til bes...

Page 3: ...view 24 8 2 Room thermostat installation con guration 24 8 3 Pump operation con guration 24 8 4 Domestic hot water tank installation con guration 25 8 5 Pre operation checks 25 8 6 Powering up the ind...

Page 4: ...power supply before removing the switchbox service panel or before making any connections or touching electrical parts Do not touch any switch with wet ngers Touching a switch with wet ngers can caus...

Page 5: ...tion manual for further details Solar kit for domestic hot water tank option For information concerning the EKSOLHT solar kit refer to the installation manual of that kit Digital I O PCB kit option An...

Page 6: ...pply 11 Domestic hot water tank optional 12 Heat exchanger coil FHL1 3 Floor heating loop T1 3 Individual room thermostat optional M1 3 Individual motorised valve to control loop FHL1 3 eld supply Pum...

Page 7: ...cooling mode The outdoor unit 1 will start operating to achieve the target leaving hot cold water temperature In case of cooling mode the 2 way valve 13 will close as to prevent cold water running thr...

Page 8: ...iliary boiler must be integrated in the piping work and in the eld wiring according to the illustrations below 1 Outdoor unit 2 Indoor unit 3 Heat exchanger 4 Backup heater 5 Pump 6 Shut off valve 7 S...

Page 9: ...water temperature is determined automatically depending on the outdoor temperature During heating operation of the boiler the boiler will operate so as to achieve the target leaving water temperature...

Page 10: ...of both zones is above the thermostat set point the outdoor unit and pump will stop operating The advantage of the dual set point control is that the heat pump will can operate at the lowest required...

Page 11: ...ned 5 2 Main components in the unit 1 Air purge valve Remaining air in the water circuit will be automatically removed via the air purge valve 2 Temperature sensors thermistors Temperature sensors det...

Page 12: ...t water tank The motorized 3 way valve controls whether the water outlet is used for space heating or the domestic hot water tank 20 T piece option delivered with the EKHTS domestic hot water tank 21...

Page 13: ...entioned in 12 Unit speci cations on page 44 due to environmental noise and sound re ections Choose the installation location carefully and do not install in a sound sensitive environment e g living r...

Page 14: ...Space required for refrigerant piping in case of left installation and electrical wiring D Space required for switch box removal 6 3 Inspecting handling and unpacking the unit At delivery the unit mu...

Page 15: ...and electrical wiring For each of these a dedicated knock out hole is foreseen at the backside of the unit 1 Knock out hole for refrigerant piping 2 Knock out hole for electrical wiring 3 Knock out h...

Page 16: ...with the unit should be installed so that normal servicing can be accomplished without draining the system Drain taps must be provided at all low points of the system to permit complete drainage of th...

Page 17: ...e is higher than 30 C and the humidity is higher than RH 80 then the thickness of the insulation materials should be at least 20 mm in order to avoid condensation on the surface of the insulation WARN...

Page 18: ...7 Shut off valve 8 Collector eld supply 10 By pass valve eld supply FHL1 3 Floor heating loop eld supply T1 3 Individual room thermostat optional M1 3 Individual motorised valve to control loop FHL1 3...

Page 19: ...the pre pressure of the expansion vessel When it is required to change the default pre pressure of the expansion vessel 1 bar keep in mind the following guidelines Use only dry nitrogen to set the exp...

Page 20: ...V for PCB V1S V2S Spark suppression 1 2 X1M X9M Terminal strip L Live N Neutral Field wiring Terminal strip Connector Terminal Protective earth BLK Black BLU Blue BRN Brown GRN Green GRY Grey ORG Oran...

Page 21: ...installation use normal kWh rate power supply for indoor unit Indoor power supply from outdoor standard Indoor power supply from outdoor standard User interface User interface Outside unit Outside uni...

Page 22: ...ion cable Power circuit and cable requirements Power supply for the indoor unit is to be provided through the outdoor unit Data communication with the outdoor unit is provided through the same cable F...

Page 23: ...et point contact is enabled See also 3 5 Typical application examples on page 4 and 7 Dual set point control on page 30 Contact requirements The contact shall be a voltage free contact that ensure 230...

Page 24: ...se rates seasonal rates W rmepumpentarif in Germany and Austria This equipment allows for connection to such bene t rate power supply delivery systems Consult with the electricity company acting as pr...

Page 25: ...ote controller and the terminals inside the unit P1 to X2M 16 P2 to X2M 16a 4 Reattach the upper part of the remote controller First begin tting from the clips at the bottom 1 When the signal is relea...

Page 26: ...opening the switch box service panel and making any changes to the DIP switch settings DIP switch SS2 Description ON OFF 1 Not applicable for installer Default 2 Domestic hot water tank installation...

Page 27: ...n page 44 Make sure that neither a fuse nor a protection device has been bypassed 7 Internal wiring Visually check the switch box on loose connections or damaged electrical components 8 Pipe size and...

Page 28: ...oor unit Each eld setting is assigned a 3 digit number or code for example 1 03 which is indicated on the user interface display The rst digit 1 indicates the rst code or eld setting group The second...

Page 29: ...f ces Field settings for cooling operation 1 05 Weather dependent for cooling function enable 1 disable 0 1 06 Low ambient temperature Lo2_A low outdoor temperature 1 07 High ambient temperature Hi2_A...

Page 30: ...n of the 3 way valve and the backup heater during domestic hot water operation When the space heating priority function is enabled it is assured that the full capacity of the heat pump is used as much...

Page 31: ...shing Powerful domestic water heating is deactivated automatically when the set point for the domestic hot water is reached Scheduled continuous domestic hot water reheat 6 05 Reheat de nes whether th...

Page 32: ...t setting If it seems that the domestic hot water night storage operation is not suf cient for your needs an additional scheduled reheat during daytime can be set A B C 6 08 B T t 2 03 6 07 Tdhw 6 04...

Page 33: ...0 Heating set point upper limit maximum leaving water temperature for heating operation 9 01 Heating set point lower limit minimum leaving water temperature for heating operation 9 02 Cooling set poin...

Page 34: ...iler When the bivalent operation function is enabled the indoor unit will stop automatically in space heating operation when the outdoor temperature drops below bivalent ON temperature and the permiss...

Page 35: ...ontact will close and the unit will go in forced off mode 2 When backup heater is forced off at bene t kWh rate power supply it is possible to de ne if pump operation is forced off or permited Refer t...

Page 36: ...ature below which space cooling is turned off Bottom plate heater control Applies only to installation with an outdoor unit ERLQ or in case the option bottom plate heater kit is installed F 02 Bottom...

Page 37: ...with domestic hot water tank without built in booster heater 4 05 5 60 xed 5 C 04 Interval for combination with domestic hot water tank without built in booster heater 4 05 5 60 40 60 5 min 3 Auto re...

Page 38: ...me 30 5 95 5 min 02 Anti recycling time 0 5 0 10 0 5 hour 03 Not applicable Do not change the default value 04 Additional running time at 4 02 F 01 95 0 95 5 min 9 Heating and cooling set point ranges...

Page 39: ...Depending on model 03 Liquid refrigerant temperature Read only 1 C 04 Inlet water temperature Read only 1 C F Option setup 00 Pump operation stop 0 0 1 01 Space cooling permission temperature 20 10 3...

Page 40: ...ng screed dry out program The program is used to dry out the screed of an under oor heating during the construction of a house Disclaimer 1 Even though the program will be executed automatically the d...

Page 41: ...times so the t icon will be displayed 2 To start the Under oor heating dry out program press the y button 3 The Under oor heating dry out program will start and display the action and temperature sett...

Page 42: ...supply is turned off because of high voltage risk The heater of the compressor may operate even in stop mode Please note that some sections of the electric component box are hot Make sure you do not t...

Page 43: ...l installer 11 1 General guidelines Before starting the troubleshooting procedure carry out a thorough visual inspection of the unit and look for obvious defects such as loose connections or defective...

Page 44: ...o return POSSIBLE CAUSES CORRECTIVE ACTION There is air in the system Purge air Water pressure at pump inlet is too low Check on the manometer that there is suf cient water pressure The water pressure...

Page 45: ...n Reset the thermal protector by pressing the reset button refer to 5 2 Main components in the unit on page 9 for location of the reset button Check the reset button of the thermal protector If both t...

Page 46: ...use Corrective action EKHVH008BB6V3 EKHVH008BB6WN EKHVH008BB9WN EKHVX008BB6V3 EKHVX008BB6WN EKHVX008BB9WN Casing material Pre coated sheet metal Pre coated sheet metal Dimensions HxWxD mm 705x600x695...

Page 47: ...NOTES NOTES...

Page 48: ...4PW64329 1 07 2010 Copyright 2010 Daikin...

Reviews: