Daikin EKHVH008BB6V3 Installation Manual Download Page 10

Installation manual

8

EKHVH/X00 EKHVH/9WN

Daikin Altherma indoor unit

4PW64329-1 – 07.2010

Application 6

Space heating with room thermostat application through floor heating
loops and fan coil units. The floor heating loops and fan coil units
require different operating water temperatures.

The floor heating loops require a lower water temperature in heating
mode compared to fan coil units. To achive these two set points, a
mixing station is used to adapt the water temperature according to
requirements of the floor heating loops. The fan coil units are directly
connected to the indoor unit water circuit and the floor heating loops
after the mixing station. The control of this mixing station is not done
by the indoor unit.

The operation and configuration of the field water circuit is the
responsibility of the installer.

Daikin only offers a dual set point control function. By this function
two set points can be generated. Depending on the required water
temperature (floor heating loops and/or fan coil units are required)
first set point or second set point can be activated.

1

Outdoor unit

2

Indoor unit

3

Heat exchanger

4

Backup heater

5

Pump

6

Shut-off valve

7

Shut-off valve

8

Collector zone A (field supply)

9

Collector zone B (field supply)

10

Mixing station (field supply)

T1

Room thermostat for zone A (optional)

T2

Room thermostat for zone B (optional)

FCU1...3

Fan coil unit (optional)

FHL1...3

Floor heating loop (field supply)

Pump operation and space heating

When the room thermostat for the floor heating loop (T1) and the fan
coil units (T2) are connected to the indoor unit, the pump (4) will
operate when there is a request for heating from T1 and/or T2. The
outdoor unit will start operating to achieve the target leaving water
temperature. The target leaving water temperature depends on which
room thermostat is requesting heating.

When the room temperature of both zones is above the thermostat
set point, the outdoor unit and pump will stop operating.

The advantage of the dual set point control is that the heat
pump will/can operate at the lowest required leaving water
temperature when only floor heating is required. Higher
leaving water temperatures are only required in case fan
coil units are operating.
This results in a better performance of the heat pump.

FHL1

FHL2

FHL3

T1

T2

FCU1

FCU2

FCU3

6

4

3

2

1

7

10

8

9

B

A

5

Set point

Field setting

Thermo status

Zone A

First

UI

ON

OFF

ON

OFF

Zone B

Second

[7-03]

OFF

ON

ON

OFF

Resulting water temperature

UI

[7-03]

[7-03]

Result pump operation

ON

ON

ON

OFF

NOTICE

Make sure to connect the thermostat wires to the
correct terminals (see 

"5. 

Overview of unit" on

page 9

).

Make sure to configure the field settings [7-02], [7-03]
and [7-04] correctly. Refer to 

"[7] Dual set point

control" on page 30

.

Make sure to configure the DIP switch SS2-3 on the
PCB of the EKHV switch box correctly. Refer to

"8.2. Room thermostat installation configuration" on
page 24

.

The request signals for space heating can be
implemented in two different ways (installer choice).
-

Thermo ON/OFF signal from room thermostat

-

Status signal (active/not active) from the mixing 
station

It is the installers responsibility to make sure no
unwanted situations can occur (e.g. too high water
temperatures towards floor heating loops, etc.)

Daikin does not offer any type of mixing station. Dual
set point control only provides the possibility to use
two set points.

When only zone A request heating, zone B will be fed
with water at a temperature equal to the first set point.
This can lead to unwanted heating of zone B.

When only zone B request heating, the mixing station
will be fed with water at a temperature equal to the
second set point.
Depending on the control of the mixing station, the
floor heating loop can still receive water at a
temperature equal to set point of the mixing station.

NOTICE

Be aware that the actual water temperature through the
floor heating loops depends on the control and setting of
the mixing station.

Summary of Contents for EKHVH008BB6V3

Page 1: ...INSTALLATION MANUAL EKHVH008BB6V3 EKHVX008BB6V3 EKHVH008BB6WN EKHVX008BB6WN EKHVH008BB9WN EKHVX008BB9WN Daikin Altherma indoor unit...

Page 2: ...van 05 siguiendo las disposiciones de 06 secondo le prescrizioni per 07 v v v 08 de acordo com o previsto em 09 10 under iagttagelse af bestemmelserne i 11 enligt villkoren i 12 gitt i henhold til bes...

Page 3: ...view 24 8 2 Room thermostat installation con guration 24 8 3 Pump operation con guration 24 8 4 Domestic hot water tank installation con guration 25 8 5 Pre operation checks 25 8 6 Powering up the ind...

Page 4: ...power supply before removing the switchbox service panel or before making any connections or touching electrical parts Do not touch any switch with wet ngers Touching a switch with wet ngers can caus...

Page 5: ...tion manual for further details Solar kit for domestic hot water tank option For information concerning the EKSOLHT solar kit refer to the installation manual of that kit Digital I O PCB kit option An...

Page 6: ...pply 11 Domestic hot water tank optional 12 Heat exchanger coil FHL1 3 Floor heating loop T1 3 Individual room thermostat optional M1 3 Individual motorised valve to control loop FHL1 3 eld supply Pum...

Page 7: ...cooling mode The outdoor unit 1 will start operating to achieve the target leaving hot cold water temperature In case of cooling mode the 2 way valve 13 will close as to prevent cold water running thr...

Page 8: ...iliary boiler must be integrated in the piping work and in the eld wiring according to the illustrations below 1 Outdoor unit 2 Indoor unit 3 Heat exchanger 4 Backup heater 5 Pump 6 Shut off valve 7 S...

Page 9: ...water temperature is determined automatically depending on the outdoor temperature During heating operation of the boiler the boiler will operate so as to achieve the target leaving water temperature...

Page 10: ...of both zones is above the thermostat set point the outdoor unit and pump will stop operating The advantage of the dual set point control is that the heat pump will can operate at the lowest required...

Page 11: ...ned 5 2 Main components in the unit 1 Air purge valve Remaining air in the water circuit will be automatically removed via the air purge valve 2 Temperature sensors thermistors Temperature sensors det...

Page 12: ...t water tank The motorized 3 way valve controls whether the water outlet is used for space heating or the domestic hot water tank 20 T piece option delivered with the EKHTS domestic hot water tank 21...

Page 13: ...entioned in 12 Unit speci cations on page 44 due to environmental noise and sound re ections Choose the installation location carefully and do not install in a sound sensitive environment e g living r...

Page 14: ...Space required for refrigerant piping in case of left installation and electrical wiring D Space required for switch box removal 6 3 Inspecting handling and unpacking the unit At delivery the unit mu...

Page 15: ...and electrical wiring For each of these a dedicated knock out hole is foreseen at the backside of the unit 1 Knock out hole for refrigerant piping 2 Knock out hole for electrical wiring 3 Knock out h...

Page 16: ...with the unit should be installed so that normal servicing can be accomplished without draining the system Drain taps must be provided at all low points of the system to permit complete drainage of th...

Page 17: ...e is higher than 30 C and the humidity is higher than RH 80 then the thickness of the insulation materials should be at least 20 mm in order to avoid condensation on the surface of the insulation WARN...

Page 18: ...7 Shut off valve 8 Collector eld supply 10 By pass valve eld supply FHL1 3 Floor heating loop eld supply T1 3 Individual room thermostat optional M1 3 Individual motorised valve to control loop FHL1 3...

Page 19: ...the pre pressure of the expansion vessel When it is required to change the default pre pressure of the expansion vessel 1 bar keep in mind the following guidelines Use only dry nitrogen to set the exp...

Page 20: ...V for PCB V1S V2S Spark suppression 1 2 X1M X9M Terminal strip L Live N Neutral Field wiring Terminal strip Connector Terminal Protective earth BLK Black BLU Blue BRN Brown GRN Green GRY Grey ORG Oran...

Page 21: ...installation use normal kWh rate power supply for indoor unit Indoor power supply from outdoor standard Indoor power supply from outdoor standard User interface User interface Outside unit Outside uni...

Page 22: ...ion cable Power circuit and cable requirements Power supply for the indoor unit is to be provided through the outdoor unit Data communication with the outdoor unit is provided through the same cable F...

Page 23: ...et point contact is enabled See also 3 5 Typical application examples on page 4 and 7 Dual set point control on page 30 Contact requirements The contact shall be a voltage free contact that ensure 230...

Page 24: ...se rates seasonal rates W rmepumpentarif in Germany and Austria This equipment allows for connection to such bene t rate power supply delivery systems Consult with the electricity company acting as pr...

Page 25: ...ote controller and the terminals inside the unit P1 to X2M 16 P2 to X2M 16a 4 Reattach the upper part of the remote controller First begin tting from the clips at the bottom 1 When the signal is relea...

Page 26: ...opening the switch box service panel and making any changes to the DIP switch settings DIP switch SS2 Description ON OFF 1 Not applicable for installer Default 2 Domestic hot water tank installation...

Page 27: ...n page 44 Make sure that neither a fuse nor a protection device has been bypassed 7 Internal wiring Visually check the switch box on loose connections or damaged electrical components 8 Pipe size and...

Page 28: ...oor unit Each eld setting is assigned a 3 digit number or code for example 1 03 which is indicated on the user interface display The rst digit 1 indicates the rst code or eld setting group The second...

Page 29: ...f ces Field settings for cooling operation 1 05 Weather dependent for cooling function enable 1 disable 0 1 06 Low ambient temperature Lo2_A low outdoor temperature 1 07 High ambient temperature Hi2_A...

Page 30: ...n of the 3 way valve and the backup heater during domestic hot water operation When the space heating priority function is enabled it is assured that the full capacity of the heat pump is used as much...

Page 31: ...shing Powerful domestic water heating is deactivated automatically when the set point for the domestic hot water is reached Scheduled continuous domestic hot water reheat 6 05 Reheat de nes whether th...

Page 32: ...t setting If it seems that the domestic hot water night storage operation is not suf cient for your needs an additional scheduled reheat during daytime can be set A B C 6 08 B T t 2 03 6 07 Tdhw 6 04...

Page 33: ...0 Heating set point upper limit maximum leaving water temperature for heating operation 9 01 Heating set point lower limit minimum leaving water temperature for heating operation 9 02 Cooling set poin...

Page 34: ...iler When the bivalent operation function is enabled the indoor unit will stop automatically in space heating operation when the outdoor temperature drops below bivalent ON temperature and the permiss...

Page 35: ...ontact will close and the unit will go in forced off mode 2 When backup heater is forced off at bene t kWh rate power supply it is possible to de ne if pump operation is forced off or permited Refer t...

Page 36: ...ature below which space cooling is turned off Bottom plate heater control Applies only to installation with an outdoor unit ERLQ or in case the option bottom plate heater kit is installed F 02 Bottom...

Page 37: ...with domestic hot water tank without built in booster heater 4 05 5 60 xed 5 C 04 Interval for combination with domestic hot water tank without built in booster heater 4 05 5 60 40 60 5 min 3 Auto re...

Page 38: ...me 30 5 95 5 min 02 Anti recycling time 0 5 0 10 0 5 hour 03 Not applicable Do not change the default value 04 Additional running time at 4 02 F 01 95 0 95 5 min 9 Heating and cooling set point ranges...

Page 39: ...Depending on model 03 Liquid refrigerant temperature Read only 1 C 04 Inlet water temperature Read only 1 C F Option setup 00 Pump operation stop 0 0 1 01 Space cooling permission temperature 20 10 3...

Page 40: ...ng screed dry out program The program is used to dry out the screed of an under oor heating during the construction of a house Disclaimer 1 Even though the program will be executed automatically the d...

Page 41: ...times so the t icon will be displayed 2 To start the Under oor heating dry out program press the y button 3 The Under oor heating dry out program will start and display the action and temperature sett...

Page 42: ...supply is turned off because of high voltage risk The heater of the compressor may operate even in stop mode Please note that some sections of the electric component box are hot Make sure you do not t...

Page 43: ...l installer 11 1 General guidelines Before starting the troubleshooting procedure carry out a thorough visual inspection of the unit and look for obvious defects such as loose connections or defective...

Page 44: ...o return POSSIBLE CAUSES CORRECTIVE ACTION There is air in the system Purge air Water pressure at pump inlet is too low Check on the manometer that there is suf cient water pressure The water pressure...

Page 45: ...n Reset the thermal protector by pressing the reset button refer to 5 2 Main components in the unit on page 9 for location of the reset button Check the reset button of the thermal protector If both t...

Page 46: ...use Corrective action EKHVH008BB6V3 EKHVH008BB6WN EKHVH008BB9WN EKHVX008BB6V3 EKHVX008BB6WN EKHVX008BB9WN Casing material Pre coated sheet metal Pre coated sheet metal Dimensions HxWxD mm 705x600x695...

Page 47: ...NOTES NOTES...

Page 48: ...4PW64329 1 07 2010 Copyright 2010 Daikin...

Reviews: