background image

 

Installation manual

 

4

 

EKHBH/X008BA

 

Indoor unit for air to water heat pump system

 

4PW54185-1B

 

T

 

YPICAL

 

 

 

APPLICATION

 

 

 

EXAMPLES

 

The application examples given below are for illustration purposes
only.

 

Application 1

 

Space heating only application with the room thermostat connected
to the indoor unit.

 

Pump operation and space heating

 

When the room thermostat (T) is connected to the indoor unit, the
pump (4) will operate when there is a heating request from the room
thermostat, and the outdoor unit will start operating to achieve the
target leaving water temperature as set on the user interface.

When the room temperature is above the thermostat set point, the
outdoor unit and pump will stop operating.

 

Application 2

 

Space heating only application without room thermostat connected to
the indoor unit. The temperature in each room is controlled by a valve
on each water circuit. Domestic hot water is provided through the
domestic hot water tank which is connected to the indoor unit.

 

Pump operation

 

With no thermostat connected to the indoor unit (2), the pump (4) can
be configured to operate either as long as the indoor unit is on, or
until the required water temperature is reached.

 

Space heating

 

The outdoor unit (1) will operate to achieve the target leaving water
temperature as set on the user interface.

 

1

 

Outdoor unit

 

6

 

Collector (field supply)

 

2

 

Indoor unit

 

7

 

Shut-off valve

 

3

 

Heat exchanger

 

FHL1..3

 

Floor heating loop 

 

4

 

Pump

 

T

 

Room thermostat 
(optional)

 

5

 

Shut-off valve

 

Make sure to connect the thermostat wires to the correct
terminals (see 

"Connection of the thermostat cable" on

page 18

) and to configure the DIP switch toggle switches

correctly (see 

"Room thermostat installation configuration"

on page 21

).

FHL1

FHL2

FHL3

T

5

6

4

3

2

1

7

1

Outdoor unit

10

Domestic hot water tank 
(optional)

2

Indoor unit

3

Heat exchanger

11

Booster heater

4

Pump

12

Heat exchanger coil

5

Shut-off valve

FHL1..3

Floor heating loop 

6

Collector (field supply)

T1..3

Individual room 
thermostat (optional)

7

Shut-off valve

8

Motorised 3-way valve 
(delivered with 
domestic hot water 
tank)

M1..3

Individual motorised 
valve to control loop 
FHL1 (field supply)

9

By-pass valve 
(field supply)

NOTE

Details on pump configuration can be found under

"Pump operation configuration" on page 22

.

NOTE

When circulation in each space heating loop (FHL1..3)
is controlled by remotely controlled valves (M1..3), it is
important to provide a by-pass valve (9) to avoid the
flow switch safety device from being activated.

The by-pass valve should be selected as such that at
all time the minimum water flow as mentioned under

"Water pipework" on page 14

 is guaranteed.

It is recommended to select a pressure difference
controlled by-pass valve.

M

FHL1

FHL2

FHL3

M1

T1

M2

T2

M3

T3

5

4

3

2

1

12

10

11

7

8

6

9

Summary of Contents for EKHBX008BA

Page 1: ...INSTALLATION MANUAL EKHBH008BA EKHBX008BA Indoor unit for air to water heat pump system...

Page 2: ...3 4 35 48 142 101 502 2 3 4 5 48 39 96 361 1 1 2 MBSP 1 MBSP 895 922 830 469 260 B B T T 2 350 300 500 1 2x 2x 1x 1x 1x 1 2 3 4 5 30 90 1 2 3 4...

Page 3: ...tion See Selecting an installation location on page 12 The units can be combined with Daikin fan coil units floor heating applications low temperature radiators Daikin domestic water heating applicati...

Page 4: ...case the benefit kWh rate power supply is of the type that power supply is not interrupted Refer to Connection to a benefit kWh rate power supply on page 19 for more details Scope of this manual This...

Page 5: ...ormal temperature or if you must touch them be sure to wear proper gloves Caution Earth the unit Earthing resistance should be according to local and national regulations Do not connect the earth wire...

Page 6: ...e as set on the user interface 1 Outdoor unit 6 Collector field supply 2 Indoor unit 7 Shut off valve 3 Heat exchanger FHL1 3 Floor heating loop 4 Pump T Room thermostat optional 5 Shut off valve Make...

Page 7: ...t and cannot be done by the user interface on the indoor unit Domestic water heating Domestic water heating is as described under Application 2 on page 4 Application 4 Space heating and cooling applic...

Page 8: ...hot water in such an application is always provided by the domestic hot water tank which is connected to the Daikin indoor unit The auxiliary boiler must be integrated in the piping work and in the fi...

Page 9: ...ke sure to install the outdoor unit in the shade so that it is not influenced by the sun Frequent switching may cause corrosion of the boiler in an early stage Contact the manufacturer of the boiler D...

Page 10: ...il unit optional 7 Collector zone B field supply FHL1 3 Floor heating loop field supply The advantage of the dual set point control is that the heat pump will can operate at the lowest required leavin...

Page 11: ...tely after operation as the refrigerant pipes may be hot or cold depending on the condition of the refrigerant flowing through the refrigerant piping compressor and other refrigerant cycle parts Your...

Page 12: ...es draining and filter replacement of the indoor unit 11 Water inlet connection 12 Water outlet connection 13 Drain and fill valves 14 Water filter The water filter removes dirt from the water to prev...

Page 13: ...ater tank 9 PCB fuse FU1 10 DIP switch SS2 The DIP switch SS2 provides 4 toggle switches to configure certain installation parameters See DIP switch settings overview on page 21 11 X13A socket The X13...

Page 14: ...the unit Be sure that sufficient precautions are taken in accordance with relevant local and national regulations in case of refrigerant leakage Dimensions and service space Unit of measurement mm Dim...

Page 15: ...collect on the cold refrigerant and water pipes This water is collected in the drain pan which must be connected to a drain For installation instructions refer to the instruction sheet delivered with...

Page 16: ...system to permit complete drainage of the circuit during maintenance Two drain valves integrated in the shut off valves are provided to drain the water from the indoor unit water system Make sure to...

Page 17: ...r circuit problems may occur Therefore always take into account the following when connecting the water circuit Use clean pipes only Hold the pipe end downwards when removing burrs Cover the pipe end...

Page 18: ...avoid air entering the circuit The unit might dispose some excessive water through the pressure relief valve Water quality must be according to EU directive 98 83 EC WARNING A main switch or other mea...

Page 19: ...ter tank optional require a dedicated power circuit for the booster heater Please refer to the domestic hot water tank installation manual Connection of the indoor unit power supply and communication...

Page 20: ...e figure below 2 Fix the cables with cable ties to the cable tie mountings to ensure strain relief 3 Depending on the required pump operation set DIP switch SS2 3 and field setting F 00 See Pump opera...

Page 21: ...Possible connections and requirements to connect the equipment to such power supply are illustrated in the figure below NOTE Two types of 3 way valves can be connected Wiring is different for each ty...

Page 22: ...om 1 When the signal is released again the voltage free contact will close and the unit will restart operation It is therefore important to leave the auto restart function enabled Refer to 3 Auto rest...

Page 23: ...a Only applicable in case DIP switch 2 ON Heating cooling priority Priority to highest demand side b b Heating cooling or domestic water heating mode can be restricted by schedule timer and or field...

Page 24: ...en applicable and indoor unit and domestic hot water tank has been carried out according to the instructions described in the chapter Field wiring on page 16 according to the wiring diagrams and accor...

Page 25: ...field settings are available These field settings are accessible and programmable through the user interface on the indoor unit Each field setting is assigned a 3 digit number or code for example 1 03...

Page 26: ...ific temperature 2 00 Operation interval day s of the week at which the domestic hot water should be heated 2 01 Status defines whether the disinfection function is turned on 1 or off 0 2 02 Start tim...

Page 27: ...t pump is active in domestic hot water mode The consequence of this functionality is that setting 8 03 is not relevant Results in optimum coverage of domestic hot water heated by heat pump in relation...

Page 28: ...The heat pump OFF temperature and the heat pump ON temperature and its relation with field settings 6 00 and 6 01 are explained in the illustration below 6 00 Start temperature difference determining...

Page 29: ...r set point for domestic hot water TU Refer to field setting 7 00 and the operation manual to select preferable set point If this high water temperature can be a potential risk for human injuries a mi...

Page 30: ...quest for space heating or space cooling domestic water heating by the heat pump will continue until the heat pump OFF temperature see field settings 6 on page 26 is reached When no room thermostat is...

Page 31: ...indoor unit or an auxiliary boiler The field setting bivalent operation apply only the indoor unit space heating operation and the permission signal for the auxiliary boiler When the bivalent operatio...

Page 32: ...dout of the unit model identification example 11 E 03 Readout of the liquid refrigerant temperature E 04 Readout of the inlet water temperature The combination of setting 4 03 0 2 with bivalent operat...

Page 33: ...ter kit is installed F 02 Bottom plate heater ON temperature defines the outdoor temperature below which the bottom plate heater will be activated by indoor unit in order to prevent ice build up in th...

Page 34: ...Priority 0 OFF 0 1 2 02 Space heating off temperature 25 14 25 1 C 03 Booster heater operation 3 0 1 2 3 04 Not applicable 2 Read only 5 Equilibrium temperature and space heating priority temperature...

Page 35: ...00 Switching off heaters 0 0 1 2 3 01 Unit connection to benefit kWh rate power supply 0 OFF 0 1 2 02 Not applicable Do not change the default value 0 03 Local shift value weather dependent 0 0 1 2 3...

Page 36: ...ndoor unit cover See Opening the indoor unit on page 9 Maintenance activities To display the last resolved error code push the z button 1 time Push the z button again 4 times to return to normal mode...

Page 37: ...tion TROUBLESHOOTING This section provides useful information for diagnosing and correcting certain troubles which may occur in the unit This troubleshooting and related corrective actions may only be...

Page 38: ...the system Purge air Water pressure at pump inlet is too low Check on the manometer that there is sufficient water pressure The water pressure must be 1 bar water is cold Check that the manometer is n...

Page 39: ...rotector by pressing the reset button refer to Main components on page 10 for location of the reset button Check the reset button of the thermal protector If both the thermal protector and the control...

Page 40: ...ealer PJ Failure of capacity setting Contact your local dealer U0 Refrigerant failure due to refrigerant leak Contact your local dealer U2 Main circuit voltage failure Contact your local dealer U4 Com...

Page 41: ...5 8 inch Expansion vessel volume 10 l 10 l maximum working pressure MWP 3 bar 3 bar Pump type water cooled water cooled no of speed 3 3 Sound pressure level Refer to technical data Refer to technical...

Page 42: ...4PW54185 1B Copyright 2009 Daikin...

Reviews: