Installation manual

22

EKHBH/X008BA

Indoor unit for air to water heat pump system

4PW54185-1B

Pump operation configuration

Without room thermostat: DIP switch SS2-3 = OFF

When no thermostat is connected to the indoor unit, pump operation
will be determined by the leaving water temperature.

To  force continuous pump operation when no room thermostat is
connected do the following:

-

set toggle switch SS2-3 to ON,

-

short-circuit the terminal numbers 1-2-4 on the terminal block 
in the switch box.

With room thermostat DIP switch: SS2-3 = ON

When the thermostat is connected to the indoor unit, the pump will
operate continuously whenever there is heating or cooling demand
requested by the thermostat.

Dual set point

When dual set point is enabled, the pump operation will be
determined depending on the status of the DIP switch SS2-3 and set
point selection contacts. Refer to the pump operation configurations
when the thermostat is connected or not as described above.

The following table summarizes the required configuration and wiring
at the terminal block (X2M: 1, 2, 4) in the switch box. Pump operation
is listed in the third column. The three last columns indicate whether
the following functionality is available on the user interface (UI) or
handled by the set point selection contacts SP1 and SP2:

space heating or cooling on/off (

y

)

heating/cooling changeover (

=

)

heating and cooling schedule timers (

pr

)

Domestic hot water tank installation configuration

Initial start-up at low outdoor ambient temperatures

During initial start-up and when water temperature is low, it is
important that the water is heated gradually. Failure to do so may
result in cracking of concrete floors due to rapid temperature change.
Please contact the responsible cast concrete building contractor for
further details.

To do so, the lowest leaving water set temperature can be decreased
to a value between 15°C and 25°C by adjusting the field setting
[9-01] (heating set point lower limit). Refer to 

"Field settings" on

page 23

.

Pre-operation checks

Checks before initial start-up

After the installation of the unit, check the following before switching
on the circuit breaker:

1

Field wiring

Make sure that the field wiring between local supply panel and
indoor unit, outdoor unit and indoor unit, indoor unit and valves
(when applicable), indoor unit and room thermostat (when
applicable), and indoor unit and domestic hot water tank has
been carried out according to the instructions described in the
chapter 

"Field wiring" on page 16

, according to the wiring

diagrams and according to European and national regulations.

2

Fuses or protection devices

Check that the fuses or the locally installed protection devices
are of the size and type specified in the chapter 

"Technical

specifications" on page 39

Make sure that neither a fuse nor a

protection device has been bypassed.

3

Backup heater circuit breaker F1B/F3B

Do not forget to turn on the backup heater circuit breaker F2B in
the switchbox (F1B/F3B depends on the backup heater type).
Refer to the wiring diagram.

4

Booster heater circuit breaker F2B

Do not forget to turn on the booster heater circuit breaker F2B in
the switch box (applies only to units with optional domestic hot
water tank installed).

5

Earth wiring

Make sure that the earth wires have been connected properly
and that the earth terminals are tightened.

NOTE

To  set the pump speed, refer to 

"Setting the pump

speed" on page 23

.

When dual set point is enabled, the "forced continuous
pump operation" is not possible. When SS2-3 is ON while
SP1 and SP2 are both closed, the pump operation will be
the same operation as "with room thermostat" and the
second set point will be the applicable set point. Refer to

"Dual set point control" on page 27

.

Dual set point

Configuration

Pump operation

y

y

y

y

=

=

=

=

 

p

p

p

pr

r

r

r

• [7-02]=1
• SS2-3 = OFF
• wiring:

determined by 
leaving water 
temperature

(a)

(a) The pump will stop when space heating/cooling is turned off or when the water 

reaches the desired water temperature as set on the user interface. With space 
heating/cooling turned on, the pump will then run every 5 minutes during 3 
minutes to check the water temperature.

UI

UI

UI

• [7-02]=1
• SS2-3 = ON
• wiring:

on when main or/and 
sub set point is 
requested

SP2/SP1

UI

SP1 =

First set point contact

SP2 =

Second set point contact

X2M

SP1

SP2

1

2

3

4

X2M

1

2

3

4

SP1

SP2

When  no domestic hot water tank  is
installed, toggle switch SS2-2 should be set to
OFF (default).

When a domestic hot water tank is installed,
toggle switch SS2-2 should be set to ON

When SS2-3 was set to ON without all necessary and
correct wiring connections between indoor unit and
switchbox of the domestic hot water tank, the error code 

AC

will be displayed on the user interface.

Heating between 15°C and 25°C is performed by the
backup heater only.

DANGER

Switch off all relevant power supply before making any
connections.

4

3

2

1

ON

OFF

4

3

2

1

ON

OFF

Summary of Contents for EKHBX008BA

Page 1: ...INSTALLATION MANUAL EKHBH008BA EKHBX008BA Indoor unit for air to water heat pump system...

Page 2: ...3 4 35 48 142 101 502 2 3 4 5 48 39 96 361 1 1 2 MBSP 1 MBSP 895 922 830 469 260 B B T T 2 350 300 500 1 2x 2x 1x 1x 1x 1 2 3 4 5 30 90 1 2 3 4...

Page 3: ...tion See Selecting an installation location on page 12 The units can be combined with Daikin fan coil units floor heating applications low temperature radiators Daikin domestic water heating applicati...

Page 4: ...case the benefit kWh rate power supply is of the type that power supply is not interrupted Refer to Connection to a benefit kWh rate power supply on page 19 for more details Scope of this manual This...

Page 5: ...ormal temperature or if you must touch them be sure to wear proper gloves Caution Earth the unit Earthing resistance should be according to local and national regulations Do not connect the earth wire...

Page 6: ...e as set on the user interface 1 Outdoor unit 6 Collector field supply 2 Indoor unit 7 Shut off valve 3 Heat exchanger FHL1 3 Floor heating loop 4 Pump T Room thermostat optional 5 Shut off valve Make...

Page 7: ...t and cannot be done by the user interface on the indoor unit Domestic water heating Domestic water heating is as described under Application 2 on page 4 Application 4 Space heating and cooling applic...

Page 8: ...hot water in such an application is always provided by the domestic hot water tank which is connected to the Daikin indoor unit The auxiliary boiler must be integrated in the piping work and in the fi...

Page 9: ...ke sure to install the outdoor unit in the shade so that it is not influenced by the sun Frequent switching may cause corrosion of the boiler in an early stage Contact the manufacturer of the boiler D...

Page 10: ...il unit optional 7 Collector zone B field supply FHL1 3 Floor heating loop field supply The advantage of the dual set point control is that the heat pump will can operate at the lowest required leavin...

Page 11: ...tely after operation as the refrigerant pipes may be hot or cold depending on the condition of the refrigerant flowing through the refrigerant piping compressor and other refrigerant cycle parts Your...

Page 12: ...es draining and filter replacement of the indoor unit 11 Water inlet connection 12 Water outlet connection 13 Drain and fill valves 14 Water filter The water filter removes dirt from the water to prev...

Page 13: ...ater tank 9 PCB fuse FU1 10 DIP switch SS2 The DIP switch SS2 provides 4 toggle switches to configure certain installation parameters See DIP switch settings overview on page 21 11 X13A socket The X13...

Page 14: ...the unit Be sure that sufficient precautions are taken in accordance with relevant local and national regulations in case of refrigerant leakage Dimensions and service space Unit of measurement mm Dim...

Page 15: ...collect on the cold refrigerant and water pipes This water is collected in the drain pan which must be connected to a drain For installation instructions refer to the instruction sheet delivered with...

Page 16: ...system to permit complete drainage of the circuit during maintenance Two drain valves integrated in the shut off valves are provided to drain the water from the indoor unit water system Make sure to...

Page 17: ...r circuit problems may occur Therefore always take into account the following when connecting the water circuit Use clean pipes only Hold the pipe end downwards when removing burrs Cover the pipe end...

Page 18: ...avoid air entering the circuit The unit might dispose some excessive water through the pressure relief valve Water quality must be according to EU directive 98 83 EC WARNING A main switch or other mea...

Page 19: ...ter tank optional require a dedicated power circuit for the booster heater Please refer to the domestic hot water tank installation manual Connection of the indoor unit power supply and communication...

Page 20: ...e figure below 2 Fix the cables with cable ties to the cable tie mountings to ensure strain relief 3 Depending on the required pump operation set DIP switch SS2 3 and field setting F 00 See Pump opera...

Page 21: ...Possible connections and requirements to connect the equipment to such power supply are illustrated in the figure below NOTE Two types of 3 way valves can be connected Wiring is different for each ty...

Page 22: ...om 1 When the signal is released again the voltage free contact will close and the unit will restart operation It is therefore important to leave the auto restart function enabled Refer to 3 Auto rest...

Page 23: ...a Only applicable in case DIP switch 2 ON Heating cooling priority Priority to highest demand side b b Heating cooling or domestic water heating mode can be restricted by schedule timer and or field...

Page 24: ...en applicable and indoor unit and domestic hot water tank has been carried out according to the instructions described in the chapter Field wiring on page 16 according to the wiring diagrams and accor...

Page 25: ...field settings are available These field settings are accessible and programmable through the user interface on the indoor unit Each field setting is assigned a 3 digit number or code for example 1 03...

Page 26: ...ific temperature 2 00 Operation interval day s of the week at which the domestic hot water should be heated 2 01 Status defines whether the disinfection function is turned on 1 or off 0 2 02 Start tim...

Page 27: ...t pump is active in domestic hot water mode The consequence of this functionality is that setting 8 03 is not relevant Results in optimum coverage of domestic hot water heated by heat pump in relation...

Page 28: ...The heat pump OFF temperature and the heat pump ON temperature and its relation with field settings 6 00 and 6 01 are explained in the illustration below 6 00 Start temperature difference determining...

Page 29: ...r set point for domestic hot water TU Refer to field setting 7 00 and the operation manual to select preferable set point If this high water temperature can be a potential risk for human injuries a mi...

Page 30: ...quest for space heating or space cooling domestic water heating by the heat pump will continue until the heat pump OFF temperature see field settings 6 on page 26 is reached When no room thermostat is...

Page 31: ...indoor unit or an auxiliary boiler The field setting bivalent operation apply only the indoor unit space heating operation and the permission signal for the auxiliary boiler When the bivalent operatio...

Page 32: ...dout of the unit model identification example 11 E 03 Readout of the liquid refrigerant temperature E 04 Readout of the inlet water temperature The combination of setting 4 03 0 2 with bivalent operat...

Page 33: ...ter kit is installed F 02 Bottom plate heater ON temperature defines the outdoor temperature below which the bottom plate heater will be activated by indoor unit in order to prevent ice build up in th...

Page 34: ...Priority 0 OFF 0 1 2 02 Space heating off temperature 25 14 25 1 C 03 Booster heater operation 3 0 1 2 3 04 Not applicable 2 Read only 5 Equilibrium temperature and space heating priority temperature...

Page 35: ...00 Switching off heaters 0 0 1 2 3 01 Unit connection to benefit kWh rate power supply 0 OFF 0 1 2 02 Not applicable Do not change the default value 0 03 Local shift value weather dependent 0 0 1 2 3...

Page 36: ...ndoor unit cover See Opening the indoor unit on page 9 Maintenance activities To display the last resolved error code push the z button 1 time Push the z button again 4 times to return to normal mode...

Page 37: ...tion TROUBLESHOOTING This section provides useful information for diagnosing and correcting certain troubles which may occur in the unit This troubleshooting and related corrective actions may only be...

Page 38: ...the system Purge air Water pressure at pump inlet is too low Check on the manometer that there is sufficient water pressure The water pressure must be 1 bar water is cold Check that the manometer is n...

Page 39: ...rotector by pressing the reset button refer to Main components on page 10 for location of the reset button Check the reset button of the thermal protector If both the thermal protector and the control...

Page 40: ...ealer PJ Failure of capacity setting Contact your local dealer U0 Refrigerant failure due to refrigerant leak Contact your local dealer U2 Main circuit voltage failure Contact your local dealer U4 Com...

Page 41: ...5 8 inch Expansion vessel volume 10 l 10 l maximum working pressure MWP 3 bar 3 bar Pump type water cooled water cooled no of speed 3 3 Sound pressure level Refer to technical data Refer to technical...

Page 42: ...4PW54185 1B Copyright 2009 Daikin...