EKHBH/X016AB
Indoor unit for hot water heat pump system and options
Operation manual
12
[3] Auto restart
When power returns after a power supply failure, the auto restart
function reapplies the user interface settings at the time of the power
supply failure.
Note that with the function disabled the schedule timer will not be
activated when power returns to the unit after a power supply failure.
Press the
pr
button to enable the schedule timer again.
■
[3-00] Status: defines whether the auto restart function is
turned ON (0) or OFF (1).
[4] Backup heater operation and space heating off temperature
Backup heater operation
—
Applies only to units with optional
backup heater installed.
The operation of the backup heater can altogether be enabled or
disabled, or it can be disabled depending on operation of the booster
heater.
■
[4-00] Status: defines whether backup heater operation is
enabled (1) or disabled (0).
■
[4-01] Priority: defines whether backup heater and booster
heater can operate simultaneously (0), or if the booster
heater operation has priority over the backup heater
operation (1).
Space heating off temperature
■
[4-02] Space heating off temperature: outdoor temperature
above which space heating is turned off, to avoid
overheating.
[5] Equilibrium temperature and space heating priority
temperature
Equilibrium temperature — The 'equilibrium temperature' field
settings apply to operation of the optional backup heater. When the
equilibrium temperature function is enabled, operation of the backup
heater is restricted to low outdoor temperatures, i.e. when the
outdoor temperature equals or drops below the specified equilibrium
temperature. When the function is disabled, operation of the backup
heater is possible at all outdoor temperatures. Enabling this function
reduces the working time of the backup heater.
■
[5-00] Equilibrium temperature status: specifies whether the
equilibrium temperature function is enabled (1) or
disabled (0).
■
[5-01] Equilibrium temperature: outdoor temperature below
which operation of the backup heater is allowed.
Space heating priority temperature (applies only to installations
with a domestic hot water tank) — The 'space heating priority
temperature' field settings apply to operation of the 3-way valve and
the booster heater in the domestic hot water tank.
When the space heating priority function is enabled, it is assured that
the full capacity of the heat pump is used for space heating only
when the outdoor temperature equals or drops below the specified
space heating priority temperature, i.e. low outdoor temperature. In
this case the domestic water will only be heated by the booster
heater.
■
[5-02] Space heating priority status: specifies whether space
heating priority is enabled (1) or disabled (0).
■
[5-03] Space heating priority temperature: outdoor
temperature below which the domestic water will be heated
by the booster heater only, i.e. low outdoor temperature.
■
[5-04] Set point correction for domestic hot water
temperature: set point correction for the desired domestic hot
water temperature, to be applied at low outdoor temperature
when space heating priority is enabled. The corrected
(higher) set point will make sure that the total heat capacity
of the water in the tank remains approximately unchanged,
by compensating for the colder bottom water layer of the tank
(because the heat exchanger coil is not operational) with a
warmer top layer.
[6] DT for domestic water heating
Applies only to installations with a domestic hot water tank.
The 'DT (delta temperature) for domestic water heating' field settings
determine the temperatures at which heating of the domestic water
by the heat pump will be started (i.e., the heat pump ON
temperature) and stopped (i.e., the heat pump OFF temperature).
When the domestic hot water temperature drops below the heat
pump ON temperature (
T
HP ON
), heating of the domestic water by the
heat pump will be started. As soon as the domestic hot water
temperature reaches the heat pump OFF temperature (
T
HP OFF
) or
the user set point temperature (
T
U
), heating of the domestic water by
the heat pump will be stopped (by switching the 3-way valve).
The heat pump OFF temperature, and the heat pump ON
temperature, and its relation with field settings [6-00] and [6-01] are
explained in the illustration below.
■
[6-00] Start: temperature difference determining the heat
pump ON temperature (
T
HP ON
). See illustration.
■
[6-01] Stop: temperature difference determining the heat
pump OFF temperature (
T
HP OFF
). See illustration.
NOTE
It is therefore recommended to leave the auto restart
function enabled.
NOTE
When the priority field setting is set to ON (1),
space heating performance of the system
might be decreased at low outdoor
temperatures, since in case of domestic water
heating demand the backup heater will not be
available for space heating (space heating will
still be provided by the heat pump).
When the priority field setting is set to OFF (0),
make sure that electrical power consumption
does not exceed supply limits.
T
set
Domestic hot water set point temperature
T
U
User set point (as set on the user interface)
T
A
Ambient (outdoor) temperature
Space heating priority
T
U
User set point temperature (as set on the user interface)
T
HP MAX
Maximum heat pump temperature at sensor in domestic hot
water tank (55°C)
T
HP OFF
Heat pump OFF temperature
T
HP ON
Heat pump ON temperature
T
A
T
set
T
U
[5-03]
[5-04]
T
U
> T
HP MAX
T(
°
C)
70
T
U
55
T
HP MAX
48
T
HP OFF
41
T
HP ON
[6-01]
[6-00]
T
U
< T
HP MAX
T(
°
C)
45
T
U
= T
HP OFF
55
T
HP MAX
38
T
HP ON
[6-00]
T
U
= 45
°
C
[6-01] = 7
°
C
[6-00] = 7
°
C
T
U
= 70
°
C
[6-01] = 7
°
C
[6-00] = 7
°
C