EKHBH/X016AB

Indoor unit for hot water heat pump system and options

Operation manual

12

[3] Auto restart

When power returns after a power supply failure, the auto restart
function reapplies the user interface settings at the time of the power
supply failure.

Note that with the function disabled the schedule timer will not be
activated when power returns to the unit after a power supply failure.
Press the 

pr

 button to enable the schedule timer again.

[3-00] Status: defines whether the auto restart function is
turned ON (0) or OFF (1).

[4] Backup heater operation and space heating off temperature

Backup heater operation 

— 

Applies only to units with optional

backup heater installed.
The operation of the backup heater can altogether be enabled or
disabled, or it can be disabled depending on operation of the booster
heater.

[4-00] Status: defines whether backup heater operation is
enabled (1) or disabled (0).

[4-01] Priority: defines whether backup heater and booster
heater can operate simultaneously (0), or if the booster
heater operation has priority over the backup heater
operation (1).

Space heating off temperature

[4-02] Space heating off temperature: outdoor temperature
above which space heating is turned off, to avoid
overheating.

[5] Equilibrium temperature and space heating priority
temperature

Equilibrium temperature  — The 'equilibrium temperature' field
settings apply to operation of the optional backup heater. When the
equilibrium temperature function is enabled, operation of the backup
heater is restricted to low outdoor temperatures, i.e. when the
outdoor temperature equals or drops below the specified equilibrium
temperature. When the function is disabled, operation of the backup
heater is possible at all outdoor temperatures. Enabling this function
reduces the working time of the backup heater.

[5-00] Equilibrium temperature status: specifies whether the
equilibrium temperature function is enabled (1) or
disabled (0).

[5-01] Equilibrium temperature: outdoor temperature below
which operation of the backup heater is allowed.

Space heating priority temperature  (applies only to installations
with a domestic hot water tank) — The 'space heating priority
temperature' field settings apply to operation of the 3-way valve and
the booster heater in the domestic hot water tank.
When the space heating priority function is enabled, it is assured that
the full capacity of the heat pump is used for space heating only
when the outdoor temperature equals or drops below the specified
space heating priority temperature, i.e. low outdoor temperature. In
this case the domestic water will only be heated by the booster
heater.

[5-02] Space heating priority status: specifies whether space
heating priority is enabled (1) or disabled (0).

[5-03] Space heating priority temperature: outdoor
temperature below which the domestic water will be heated
by the booster heater only, i.e. low outdoor temperature.

[5-04] Set point correction for domestic hot water
temperature: set point correction for the desired domestic hot
water temperature, to be applied at low outdoor temperature
when space heating priority is enabled. The corrected
(higher) set point will make sure that the total heat capacity
of the water in the tank remains approximately unchanged,
by compensating for the colder bottom water layer of the tank
(because the heat exchanger coil is not operational) with a
warmer top layer.

[6] DT for domestic water heating

Applies only to installations with a domestic hot water tank.

The 'DT (delta temperature) for domestic water heating' field settings
determine the temperatures at which heating of the domestic water
by  the heat pump will be started (i.e., the heat pump ON
temperature) and stopped (i.e., the heat pump OFF temperature).
When the domestic hot water temperature drops below the heat
pump ON temperature (

T

HP ON

), heating of the domestic water by the

heat pump will be started. As soon as the domestic hot water
temperature reaches the heat pump OFF temperature (

T

HP OFF

) or

the user set point temperature (

T

U

), heating of the domestic water by

the heat pump will be stopped (by switching the 3-way valve).

The heat pump OFF temperature, and the heat pump ON
temperature, and its relation with field settings [6-00] and [6-01] are
explained in the illustration below.

[6-00] Start: temperature difference determining the heat
pump ON temperature (

T

HP ON

). See illustration.

[6-01] Stop: temperature difference determining the heat
pump OFF temperature (

T

HP OFF

). See illustration.

NOTE

It is therefore recommended to leave the auto restart
function enabled.

NOTE

When the priority field setting is set to ON (1),
space heating performance of the system
might be decreased at low outdoor
temperatures, since in case of domestic water
heating demand the backup heater will not be
available for space heating (space heating will
still be provided by the heat pump).

When the priority field setting is set to OFF (0),
make sure that electrical power consumption
does not exceed supply limits.

T

set

Domestic hot water set point temperature

T

U

User set point (as set on the user interface)

T

A

Ambient (outdoor) temperature

Space heating priority

T

U

User set point temperature (as set on the user interface)

T

HP MAX

Maximum heat pump temperature at sensor in domestic hot 
water tank (55°C)

T

HP OFF

Heat pump OFF temperature

T

HP ON

Heat pump ON temperature

T

A

T

set

T

U

[5-03]

[5-04]

T

> T

HP MAX

T(

°

C)

70

T

U

55

T

HP MAX

48

T

HP OFF

41

T

HP ON

[6-01]

[6-00]

T

< T

HP MAX

T(

°

C)

45

T

U

 = T

HP OFF

55

T

HP MAX

38

T

HP ON

[6-00]

T

= 45

°

C

[6-01] =  7

°

C

[6-00] =  7

°

C

T

= 70

°

C

[6-01] =  7

°

C

[6-00] =  7

°

C

Summary of Contents for EKHBH016AB

Page 1: ...OPERATION MANUAL EKHBH016AB EKHBX016AB Indoor unit for hot water heat pump system and options ...

Page 2: ...mbined with Daikin fan coil units floor heating low temperature radiators the Daikin domestic hot water tanks and the solar option kit The hot water heat pump system indoor unit range consists of two main versions a heating cooling EKHBX version and a heating only EKHBH version Both versions can optionally be delivered with an integrated backup heater for additional heating capacity during cold ou...

Page 3: ...ow electricity cost tariffs in mind To do this program both the domestic water heating and booster heating schedule timer Refer to Programming in chapter Programming and consulting the schedule timer on page 7 OPERATING THE DIGITAL CONTROLLER Operating the EKHB unit comes down to operating the digital controller Features and functions The digital controller is a state of the art controller that of...

Page 4: ...ected when programming the schedule timer 10 INSPECTION REQUIRED k and l These icons indicate that inspection is required on the installation Consult your Daikin dealer 11 SET TEMPERATURE DISPLAY 9 The display shows the current set temperature of the installation 12 SETTING Not used For installation purposes only 13 NOT AVAILABLE n This icon is displayed whenever a non installed option is addresse...

Page 5: ...he domestic hot water tank is not installed 34 QUIET MODE BUTTON s This button enables or disables quiet mode If the controller is set in permission level 2 or 3 refer to Field settings on page 10 the quiet mode button will not be operable Setting up the controller After initial installation the user can set the clock and day of the week The controller is equipped with a schedule timer that enable...

Page 6: ...perable when the outdoor ambient temperature rises above a certain temperature as set through field setting 4 02 refer to Field settings on page 10 Temperature range for cooling 5 C to 22 C 3 Switch on the unit by pushing the y button The operation LED 0 lights up Selection and setting of domestic water heating w 1 Use the v button to activate domestic water heating w Icon w appears on the display...

Page 7: ...ions 2 Quiet mode refer to Programming quiet mode booster heating or domestic water heating on page 9 Switch the mode on or off at a scheduled time Five actions can be programmed per mode These actions are repeated daily 3 Booster heating refer to Programming quiet mode booster heating or domestic water heating on page 9 Allow or disallow booster heating at a scheduled time Five actions can be pro...

Page 8: ...ement but will simplify the interpretation of the program later If 2 or more actions are programmed for the same day and at the same time only the action with the highest action number will be executed You can always alter add or remove the programmed actions later When programming heating actions time and set point cooling actions are added automatically at the same time but with the predefined d...

Page 9: ...t x to switch cooling or heating and the controller off 9 set the temperature by means of the bi and bj buttons a to select automatic temperature calculation only in heating mode 10 Use the pi and pj buttons to set the correct action time 11 Repeat steps 8 to 10 to program the other actions of the selected day When all actions have been programmed make sure that the display shows the highest actio...

Page 10: ...ult 2 Press the button The actual mode is blinking 3 Press the button to confirm the selected mode The actual day is blinking 4 Select the day you would like to consult by means of the pi and pj buttons The selected day is blinking 5 Press the button to confirm the selected day The first programmed action of the selected day appears 6 Use the pi and pj buttons to consult the other programmed actio...

Page 11: ...aneously for 5 seconds to delete the selected mode Deleting a day of the week cooling or heating mode 1 Use the button to select the operation mode cooling or heating you want to delete 2 Press the button The actual mode is blinking 3 Press the button to confirm the selected mode The actual day is blinking 4 Select the day you would like to delete by means of the pi and pj buttons The selected day...

Page 12: ...ld be higher than Hi_Ti as for colder outdoor temperatures i e Lo_A warmer water is required 1 03 Set point at high ambient temperature Hi_Ti the target outgoing water temperature when the outdoor temperature equals or rises above the high ambient temperature Hi_A Note that the Hi_Ti value should be lower than Lo_Ti as for warmer outdoor temperatures i e Hi_A less warm water suffices 2 Disinfectio...

Page 13: ...atus specifies whether space heating priority is enabled 1 or disabled 0 5 03 Space heating priority temperature outdoor temperature below which the domestic water will be heated by the booster heater only i e low outdoor temperature 5 04 Set point correction for domestic hot water temperature set point correction for the desired domestic hot water temperature to be applied at low outdoor temperat...

Page 14: ...hed Note that when the unit is configured to work with a room thermostat refer to the installation manual the maximum running timer will only be taken into account when there is a request for space cooling or space heating When there is no request for room cooling or room heating domestic water heating by the heat pump will continue until the heat pump OFF temperature see field settings 5 is reach...

Page 15: ...iet operation might be overridden when higher performance is required In certain cases this might result in less quiet operation of the outdoor unit to meet the requested performance A 00 Quiet mode type defines whether quiet mode A 0 or quiet mode B 2 is selected A 01 Parameter 01 do not change this setting Leave it set to its default value C Solar priority mode For information concerning the EKS...

Page 16: ...5 1 C 5 Equilibrium temperature and space heating priority temperature 00 Equilibrium temperature status 1 ON 0 1 01 Equilibrium temperature 0 15 20 1 C 02 Space heating priority status 0 OFF 0 1 03 Space heating priority temperatures 0 15 20 1 C 04 Set point correction for domestic hot water temperature 10 0 20 1 C 6 DT for domestic water heating 00 Start 5 1 20 1 C 01 Stop 2 2 10 1 C 7 Domestic ...

Page 17: ...r local Daikin dealer The schedule timer does work but the programmed actions are executed at the wrong time e g 1 hour too late or too early Check if the clock and the day of the week are set correctly correct if necessary DISPOSAL REQUIREMENTS Dismantling of the unit treatment of the refrigerant of oil and of other parts must be done in accordance with relevant local and national legislation Do ...