EKHBH/X016AB
Indoor unit for hot water heat pump system and options
Operation manual
14
Example
[9] Cooling and heating set points
The purpose of this field setting is to prevent the user from selecting
a wrong (i.e., too hot or too cold) leaving water temperature. Thereto
the heating temperature set point range and the cooling temperature
set point range available to the user can be configured.
■
[9-00] Heating set point upper limit: maximum leaving water
temperature for heating operation.
■
[9-01] Heating set point lower limit: minimum leaving water
temperature for heating operation.
■
[9-02] Cooling set point upper limit: maximum leaving water
temperature for cooling operation.
■
[9-03] Cooling set point lower limit: minimum leaving water
temperature for cooling operation.
[A] Quiet mode
This field setting allows to select the desired quiet mode. Two quiet
modes are available: quiet mode A and quiet mode B.
In quiet mode A, priority is given to the outdoor unit operating quietly
under all circumstances. Fan and compressor speed (and thus
performance) will be limited to a certain percentage of the speed at
normal operation. In certain cases, this might result in reduced
performance.
In quiet mode B, quiet operation might be overridden when higher
performance is required. In certain cases, this might result in less
quiet operation of the outdoor unit to meet the requested
performance.
■
[A-00] Quiet mode type: defines whether quiet mode A (0) or
quiet mode B (2) is selected.
■
[A-01] Parameter 01: do not change this setting. Leave it set
to its default value.
[C] Solar priority mode
For information concerning the EKSOLHW solar kit, refer to the
installation manual of that kit.
NOTE
■
Take care that [8-03] is always smaller than the
maximum running time [8-01].
■
By adapting the booster heater delay time versus
the maximum running time, an optional balance
can be found between the energy efficiency and
the heat up time.
■
However, if the booster heater delay time is set
too high, it might take a long time before the
domestic hot water reaches its set temperature
upon domestic water heating mode request.
Energy saving settings
Quick heating settings (default)
[8-01]
20~95 min
30 min
[8-03]
20~95 min
20 min
■
In case of a floor heating application, it is important to
limit the maximum leaving water temperature at
heating operation according to the specifications of
the floor heating installation.
■
In case of a floor cooling application, it is important to
limit the minimum leaving water temperature at
cooling operation to 16°C to prevent condensation on
the floor.
Do not set other values than the ones mentioned.