background image

EKHBH/X016AA

Indoor unit for air to water heat pump and sanitary warm water tank for air to water heat pump system

4PW36977-1B

Operation manual

12

[3] Auto restart

When power returns after a power supply failure, the auto restart
function reapplies the user interface settings at the time of the power
supply failure.

Note that with the function disabled the schedule timer will not be
activated when power returns to the unit after a power supply failure.
Press the 

pr

 button to enable the schedule timer again.

[3-00] Status: defines whether the auto restart function is
turned ON (0) or OFF (1).

[4] Backup heater operation and space heating off temperature

Backup heater operation 

— 

Applies only to units with optional

backup heater installed.
The operation of the backup heater can altogether be enabled or
disabled, or it can be disabled depending on operation of the booster
heater.

[4-00] Status: defines whether backup heater operation is
enabled (1) or disabled (0).

[4-01] Priority: defines whether backup heater and booster
heater can operate simultaneously (0), or if the booster
heater operation has priority over the backup heater
operation (1).

Space heating off temperature

[4-02] Space heating off temperature: outdoor temperature
above which space heating is turned off, to avoid
overheating.

[5] Equilibrium temperature and space heating priority
temperature

Equilibrium temperature  — The 'equilibrium temperature' field
settings apply to operation of the optional backup heater. When the
equilibrium temperature function is enabled, operation of the backup
heater is restricted to low outdoor temperatures, i.e. when the
outdoor temperature equals or drops below the specified equilibrium
temperature. When the function is disabled, operation of the backup
heater is possible at all outdoor temperatures. Enabling this function
reduces the working time of the backup heater.

[5-00] Equilibrium temperature status: specifies whether the
equilibrium temperature function is enabled (1) or
disabled (0).

[5-01] Equilibrium temperature: outdoor temperature below
which operation of the backup heater is allowed.

Space heating priority temperature  (applies only to installations
with a sanitary water tank) — The 'space heating priority
temperature' field settings apply to operation of the 3-way valve and
the booster heater in the sanitary water tank.
When the space heating priority function is enabled, it is assured that
the full capacity of the heat pump is used for space heating only
when the outdoor temperature equals or drops below the specified
space heating priority temperature, i.e. low outdoor temperature. In
this case the sanitary water will only be heated by the booster heater.

[5-02] Space heating priority status: specifies whether space
heating priority is enabled (1) or disabled (0).

[5-03] Space heating priority temperature: outdoor
temperature below which the sanitary water will be heated by
the booster heater only, i.e. low outdoor temperature.

[5-04] Set point correction for sanitary water temperature: set
point correction for the desired sanitary water temperature, to
be applied at low outdoor temperature when space heating
priority is enabled. The corrected (higher) set point will make
sure that the total  heat capacity of the water in the tank
remains approximately unchanged, by compensating for the
colder bottom water layer of the tank (because the heat
exchanger coil is not operational) with a warmer top layer.

[6] DT for sanitary water heating

Applies only to installations with a sanitary water tank.

The 'DT (delta temperature) for sanitary water heating' field settings
determine the temperatures at which heating of the sanitary water by
the heat pump will be started (i.e., the heat pump ON temperature)
and stopped (i.e., the heat pump OFF temperature).
When the sanitary water temperature drops below the heat pump ON
temperature (

T

HP ON

), heating of the sanitary water by the heat pump

will be started. As soon as the sanitary water temperature reaches
the heat pump OFF temperature (

T

HP OFF

) or the user set point

temperature (

T

U

), heating of the sanitary water by the heat pump will

be stopped (by switching the 3-way valve).

The heat pump OFF temperature, and the heat pump ON
temperature, and its relation with field settings [6-00] and [6-01] are
explained in the illustration below.

[6-00] Start: temperature difference determining the heat
pump ON temperature (

T

HP ON

). See illustration.

[6-01] Stop: temperature difference determining the heat
pump OFF temperature (

T

HP OFF

). See illustration.

NOTE

It is therefore recommended to leave the auto restart
function enabled.

NOTE

When the priority field setting is set to ON (1),
space heating performance of the system
might be decreased at low outdoor
temperatures, since in case of sanitary water
heating demand the backup heater will not be
available for space heating (space heating will
still be provided by the heat pump).

When the priority field setting is set to OFF (0),
make sure that electrical power consumption
does not exceed supply limits.

T

set

Sanitary water set point temperature

T

U

User set point (as set on the user interface)

T

A

Ambient (outdoor) temperature

Space heating priority

T

U

User set point temperature (as set on the user interface)

T

HP MAX

Maximum heat pump temperature at sensor in sanitary 
water tank (55°C)

T

HP OFF

Heat pump OFF temperature

T

HP ON

Heat pump ON temperature

T

A

T

set

T

U

[5-03]

[5-04]

T

> T

HP MAX

T(

°

C)

70

T

U

50

T

HP MAX

48

T

HP OFF

41

T

HP ON

[6-01]

[6-00]

T

< T

HP MAX

T(

°

C)

45

T

U

 = T

HP OFF

50

T

HP MAX

38

T

HP ON

[6-00]

T

= 45

°

C

[6-01] =  2

°

C

[6-00] =  7

°

C

T

= 70

°

C

[6-01] =  2

°

C

[6-00] =  7

°

C

Summary of Contents for EKHBH016AA

Page 1: ...OPERATION MANUAL EKHBH016AA EKHBX016AA Indoor unit for air to water heat pump and sanitary warm water tank for air to water heat pump system ...

Page 2: ... the reversible air to water Daikin ERHQ heat pumps These units are designed for wall mounted indoor installation and used for both heating and cooling applications The units can be combined with Daikin fan coil units floor heating low temperature radiators and the Daikin EKSWW sanitary water tanks The indoor unit range consists of two main versions a heating cooling EKHBX version and a heating on...

Page 3: ...r in the evening or in the morning only allow sanitary water heating during early morning and early evening Also keep hours with low electricity cost tariffs in mind To do this program both the sanitary water heating and booster heating schedule timer Refer to Programming in chapter Programming and consulting the schedule timer on page 7 OPERATING THE DIGITAL CONTROLLER Operating the EKHB unit com...

Page 4: ...tallation Consult your Daikin Dealer 11 SET TEMPERATURE DISPLAY 9 The display shows the current set temperature of the installation 12 SETTING Not used For installation purposes only 13 NOT AVAILABLE n This icon is displayed whenever a non installed option is addressed or a function is not available 14 DEFROST STARTUP MODE ICON d This icon indicates that the defrost startup mode is active 15 COMPR...

Page 5: ... in schedule timer programming mode In weather dependent set point mode the buttons are used to adjust the shift value Finally the buttons are also used to select the weekday while setting the clock 33 SANITARY TEMPERATURE ADJUST BUTTONS wbi and wbj These buttons are used to adjust the current set point of the sanitary water temperature The buttons are not used when the sanitary water tank is not ...

Page 6: ... appears on the display as well as the corresponding water temperature set point 2 Use the bi and bj buttons to set the desired water temperature Temperature range for heating 25 C to 55 C The temperature for heating can be set as low as 15 C see Field settings on page 10 However the temperature for heating should only be set lower than 25 C during commissioning of the installation When set lower ...

Page 7: ...th a set point weather dependent or manually set Five actions per weekday can be programmed totalling 35 actions 2 Quiet mode refer to Programming quiet mode booster heating or sanitary heating on page 9 Switch the mode on or off at a scheduled time Five actions can be programmed per mode These actions are repeated daily 3 Booster heating refer to Programming quiet mode booster heating or sanitary...

Page 8: ...action This is not a requirement but will simplify the interpretation of the program later If 2 or more actions are programmed for the same day and at the same time only the action with the highest action number will be executed You can always alter add or remove the programmed actions later When programming heating actions time and set point cooling actions are added automatically at the same tim...

Page 9: ... 9 Use the ba button to select x to switch cooling or heating and the controller off 9 set the temperature by means of the bi and bj buttons a to select automatic temperature calculation only in heating mode 10 Use the pi and pj buttons to set the correct action time 11 Repeat steps 8 to 10 to program the other actions of the selected day When all actions have been programmed make sure that the di...

Page 10: ...ng or heating you want to consult 2 Press the button The actual mode is blinking 3 Press the button to confirm the selected mode The actual day is blinking 4 Select the day you would like to consult by means of the pi and pj buttons The selected day is blinking 5 Press the button to confirm the selected day The first programmed action of the selected day appears 6 Use the pi and pj buttons to cons...

Page 11: ... the and ba button simultaneously for 5 seconds to delete the selected mode Deleting a day of the week cooling or heating mode 1 Use the button to select the operation mode cooling or heating you want to delete 2 Press the button The actual mode is blinking 3 Press the button to confirm the selected mode The actual day is blinking 4 Select the day you would like to delete by means of the pi and pj...

Page 12: ...e higher than Hi_Ti as for colder outdoor temperatures i e Lo_A warmer water is required 1 03 Set point at high ambient temperature Hi_Ti the target outgoing water temperature when the outdoor temperature equals or rises above the high ambient temperature Hi_A Note that the Hi_Ti value should be lower than Lo_Ti as for warmer outdoor temperatures i e Hi_A less warm water suffices 2 Disinfection fu...

Page 13: ...er heater 5 02 Space heating priority status specifies whether space heating priority is enabled 1 or disabled 0 5 03 Space heating priority temperature outdoor temperature below which the sanitary water will be heated by the booster heater only i e low outdoor temperature 5 04 Set point correction for sanitary water temperature set point correction for the desired sanitary water temperature to be...

Page 14: ...8 01 Maximum running time specifies the maximum time period during which sanitary water heating can be activated even when the target sanitary water temperature has not yet been reached Note that when the unit is configured to work with a room thermostat refer to the installation manual the maximum running timer will only be taken into account when there is a request for space cooling or space hea...

Page 15: ...ation In certain cases this might result in reduced performance In quiet mode B quiet operation might be overridden when higher performance is required In certain cases this might result in less quiet operation of the outdoor unit to meet the requested performance A 00 Quiet mode type defines whether quiet mode A 0 or quiet mode B 2 is selected A 01 Parameter 01 do not change this setting Leave it...

Page 16: ...N 0 1 01 Priority 0 OFF 0 1 02 Space heating off temperature 35 14 35 1 C 5 Equilibrium temperature and space heating priority temperature 00 Equilibrium temperature status 1 ON 0 1 01 Equilibrium temperature 0 15 20 1 C 02 Space heating priority status 0 OFF 0 1 03 Space heating priority temperatures 0 15 20 1 C 04 Set point correction for sanitary water temperature 10 0 20 1 C 6 DT for sanitary ...

Page 17: ...rror codes appears Consult your local Daikin dealer The schedule timer does work but the programmed actions are executed at the wrong time e g 1 hour too late or too early Check if the clock and the day of the week are set correctly correct if necessary DISPOSAL REQUIREMENTS Dismantling of the unit treatment of the refrigerant of oil and of other parts must be done in accordance with relevant loca...

Page 18: ...NOTES NOTES ...

Page 19: ......

Page 20: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PW36977 1B Copyright Daikin ...

Reviews: