background image

 

EKHBH/X016AA

Indoor unit for air to water heat pump and sanitary warm water tank for air to water heat pump system

4PW36977-1B

 

Operation manual

 

2

 

O

 

PERATING

 

 

 

THE

 

 

 

UNIT

 

I

 

NTRODUCTION

 

The 

 heat pump system is designed to provide

you a comfortable indoor climate for many years at low energy
consumption.

To  get the most comfort with the lowest energy consumption out of
your system, it is very important to observe the items listed below.

Defining possible schedule timer actions for each day and filling out
the form at the very end of this manual can help you minimize the
energy consumption. Ask your installer for support if required.

 

 

Make sure the 

 heat pump system works at

the lowest possible hot water temperature required to heat your
house.

To optimize this, make sure the weather dependent set point is
used and configured to match the installation environment.
Refer to 

"Field settings" on page 10

.

 

 

Make sure the equilibrium temperature field setting is configured
correctly.

Refer to 

"Field settings" on page 10

.

This function applies to operation of the optional backup heater.
Setting the equilibrium temperature correctly will avoid the
backup heater to operate when the heat pump has sufficient
capacity to heat up your house.

 

 

It is advised to install a room thermostat connected to the indoor
unit. This will prevent excessive space heating and will stop the
outdoor unit and the indoor circulation pump when the room
temperature is above the thermostat set point.

 

 

Next recommendations only apply to installations with an
optional sanitary water tank.

 

 

Make sure the sanitary water is only heated up to the
sanitary water temperature you require.
Start with a low sanitary water temperature set point (e.g.
45°C), and only increase if you feel that the sanitary water
supply temperature is not sufficient.

 

 

Make sure both the sanitary water heating and booster
heating only start 1 to 2 hours before you expect sanitary
water usage.
In case you only need a lot of sanitary water in the evening or
in the morning, only allow sanitary water heating during early
morning and early evening. Also keep hours with low
electricity cost tariffs in mind.
To  do this, program both the sanitary water heating and
booster heating schedule timer. Refer to Programming in
chapter 

"Programming and consulting the schedule timer" on

page 7

.

 

O

 

PERATING

 

 

 

THE

 

 

 

DIGITAL

 

 

 

CONTROLLER

 

Operating the EKHB* unit comes down to operating the digital
controller.

 

Features and functions

 

The digital controller is a state of the art controller that offers full
control over your installation. It can control a cooling/heating and a
heating only installation.

Both installations are available in multiple versions which vary in
capacity, electrical supply and installed equipment (backup heater in
the indoor unit or a sanitary water tank with a booster heater).

 

Basic controller functions

 

The basic controller functions are:

 

 

Turning the unit ON/OFF.

 

 

Operation mode change-over:
-

space heating (refer to 

page 5

),

-

space cooling (refer to 

page 5

) (*),

-

sanitary heating (refer to 

page 5

) (*).

 

 

Selection of features:
-

quiet mode (refer to 

page 5

),

-

weather dependent control (refer to 

page 6

).

 

 

Temperature set point adjustment (refer to 

page 5

).

 

Clock function

 

The clock functions are:

 

 

24 hour real time clock.

 

 

Day of the week indicator.

 

Schedule timer function

 

The schedule timer function allows the user to schedule the
operation of the installation according to a daily or a weekly program.

 

Never let the digital controller get wet. This may cause an
electric shock or fire.

Never press the buttons of the digital controller with a hard,
pointed object. This may damage the digital controller.

Never inspect or service the digital controller yourself, ask
a qualified service person to do this.

 

NOTE

 

 

Descriptions in this manual that apply to a specific
installation or that depend on the installed
equipment, are marked with an asterisk (*).

 

 

Some functions described in this manual may not
be available or should not be available. Ask your
installer or your local Daikin dealer for more
information on permission levels.

 

NOTE

 

(*) The functions "space cooling" and "sanitary
heating" can only be selected when the corresponding
equipment is installed.

Summary of Contents for EKHBH016AA

Page 1: ...OPERATION MANUAL EKHBH016AA EKHBX016AA Indoor unit for air to water heat pump and sanitary warm water tank for air to water heat pump system ...

Page 2: ... the reversible air to water Daikin ERHQ heat pumps These units are designed for wall mounted indoor installation and used for both heating and cooling applications The units can be combined with Daikin fan coil units floor heating low temperature radiators and the Daikin EKSWW sanitary water tanks The indoor unit range consists of two main versions a heating cooling EKHBX version and a heating on...

Page 3: ...r in the evening or in the morning only allow sanitary water heating during early morning and early evening Also keep hours with low electricity cost tariffs in mind To do this program both the sanitary water heating and booster heating schedule timer Refer to Programming in chapter Programming and consulting the schedule timer on page 7 OPERATING THE DIGITAL CONTROLLER Operating the EKHB unit com...

Page 4: ...tallation Consult your Daikin Dealer 11 SET TEMPERATURE DISPLAY 9 The display shows the current set temperature of the installation 12 SETTING Not used For installation purposes only 13 NOT AVAILABLE n This icon is displayed whenever a non installed option is addressed or a function is not available 14 DEFROST STARTUP MODE ICON d This icon indicates that the defrost startup mode is active 15 COMPR...

Page 5: ... in schedule timer programming mode In weather dependent set point mode the buttons are used to adjust the shift value Finally the buttons are also used to select the weekday while setting the clock 33 SANITARY TEMPERATURE ADJUST BUTTONS wbi and wbj These buttons are used to adjust the current set point of the sanitary water temperature The buttons are not used when the sanitary water tank is not ...

Page 6: ... appears on the display as well as the corresponding water temperature set point 2 Use the bi and bj buttons to set the desired water temperature Temperature range for heating 25 C to 55 C The temperature for heating can be set as low as 15 C see Field settings on page 10 However the temperature for heating should only be set lower than 25 C during commissioning of the installation When set lower ...

Page 7: ...th a set point weather dependent or manually set Five actions per weekday can be programmed totalling 35 actions 2 Quiet mode refer to Programming quiet mode booster heating or sanitary heating on page 9 Switch the mode on or off at a scheduled time Five actions can be programmed per mode These actions are repeated daily 3 Booster heating refer to Programming quiet mode booster heating or sanitary...

Page 8: ...action This is not a requirement but will simplify the interpretation of the program later If 2 or more actions are programmed for the same day and at the same time only the action with the highest action number will be executed You can always alter add or remove the programmed actions later When programming heating actions time and set point cooling actions are added automatically at the same tim...

Page 9: ... 9 Use the ba button to select x to switch cooling or heating and the controller off 9 set the temperature by means of the bi and bj buttons a to select automatic temperature calculation only in heating mode 10 Use the pi and pj buttons to set the correct action time 11 Repeat steps 8 to 10 to program the other actions of the selected day When all actions have been programmed make sure that the di...

Page 10: ...ng or heating you want to consult 2 Press the button The actual mode is blinking 3 Press the button to confirm the selected mode The actual day is blinking 4 Select the day you would like to consult by means of the pi and pj buttons The selected day is blinking 5 Press the button to confirm the selected day The first programmed action of the selected day appears 6 Use the pi and pj buttons to cons...

Page 11: ... the and ba button simultaneously for 5 seconds to delete the selected mode Deleting a day of the week cooling or heating mode 1 Use the button to select the operation mode cooling or heating you want to delete 2 Press the button The actual mode is blinking 3 Press the button to confirm the selected mode The actual day is blinking 4 Select the day you would like to delete by means of the pi and pj...

Page 12: ...e higher than Hi_Ti as for colder outdoor temperatures i e Lo_A warmer water is required 1 03 Set point at high ambient temperature Hi_Ti the target outgoing water temperature when the outdoor temperature equals or rises above the high ambient temperature Hi_A Note that the Hi_Ti value should be lower than Lo_Ti as for warmer outdoor temperatures i e Hi_A less warm water suffices 2 Disinfection fu...

Page 13: ...er heater 5 02 Space heating priority status specifies whether space heating priority is enabled 1 or disabled 0 5 03 Space heating priority temperature outdoor temperature below which the sanitary water will be heated by the booster heater only i e low outdoor temperature 5 04 Set point correction for sanitary water temperature set point correction for the desired sanitary water temperature to be...

Page 14: ...8 01 Maximum running time specifies the maximum time period during which sanitary water heating can be activated even when the target sanitary water temperature has not yet been reached Note that when the unit is configured to work with a room thermostat refer to the installation manual the maximum running timer will only be taken into account when there is a request for space cooling or space hea...

Page 15: ...ation In certain cases this might result in reduced performance In quiet mode B quiet operation might be overridden when higher performance is required In certain cases this might result in less quiet operation of the outdoor unit to meet the requested performance A 00 Quiet mode type defines whether quiet mode A 0 or quiet mode B 2 is selected A 01 Parameter 01 do not change this setting Leave it...

Page 16: ...N 0 1 01 Priority 0 OFF 0 1 02 Space heating off temperature 35 14 35 1 C 5 Equilibrium temperature and space heating priority temperature 00 Equilibrium temperature status 1 ON 0 1 01 Equilibrium temperature 0 15 20 1 C 02 Space heating priority status 0 OFF 0 1 03 Space heating priority temperatures 0 15 20 1 C 04 Set point correction for sanitary water temperature 10 0 20 1 C 6 DT for sanitary ...

Page 17: ...rror codes appears Consult your local Daikin dealer The schedule timer does work but the programmed actions are executed at the wrong time e g 1 hour too late or too early Check if the clock and the day of the week are set correctly correct if necessary DISPOSAL REQUIREMENTS Dismantling of the unit treatment of the refrigerant of oil and of other parts must be done in accordance with relevant loca...

Page 18: ...NOTES NOTES ...

Page 19: ......

Page 20: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PW36977 1B Copyright Daikin ...

Reviews: