ESIE13-02A
Error Codes: Outdoor Units
109
Part 4 Troubleshooting
4
3
4
5
4
4.4
E5
Compressor Motor Lock
Remote controller
display
E5
Method of
malfunction
detection
Inverter PC board takes the position signal from UVW line connected between the inverter and
compressor, and detects the position signal pattern.
Malfunction
decision conditions
The position signal with 3 times cycle as imposed frequency is detected when compressor motor
operates normally, but 2 times cycle when compressor motor locks. When the position signal in 2 times
cycle is detected.
Supposed causes
Compressor lock
High differential pressure (2.6MPa or more) starting
Incorrect UVW wiring
Faulty inverter PC board
Stop valve is left in closed.
Summary of Contents for EHYHBH05AAV3
Page 16: ...Introduction ESIE13 02A 16 3 1 4 5...
Page 29: ...ESIE13 02A Functionality 29 Part 1 System Outline 3 1 4 5...
Page 30: ...Functionality ESIE13 02A Part 1 System Outline 30 3 1 1 4 5...
Page 35: ...ESIE13 02A Wiring Diagrams 35 Part 1 System Outline 3 1 4 5...
Page 36: ...Wiring Diagrams ESIE13 02A Part 1 System Outline 36 3 1 1 4 5...
Page 38: ...Wiring Diagrams ESIE13 02A Part 1 System Outline 38 3 1 1 4 5 3 3 Cable Dimensions...
Page 39: ...ESIE13 02A Wiring Diagrams 39 Part 1 System Outline 3 1 4 5...
Page 50: ...Outdoor Unit ESIE13 02A Part 2 Specifications 50 3 1 2 5...
Page 51: ...ESIE13 02A 51 Part 3 Commissioning 4 3 4 5 3 Part 3 Commissioning See Note on page 6...
Page 52: ...ESIE13 02A Part 3 Commissioning 52 3 1 3 5...
Page 98: ...Error Codes Hydro box ESIE13 02A Part 4 Troubleshooting 98 3 1 4 5 Troubleshooting...
Page 115: ...ESIE13 02A Error Codes Outdoor Units 115 Part 4 Troubleshooting 4 3 4 5 4 Troubleshooting...
Page 170: ...Maintenance Schedule ESIE13 02A Part 6 Maintenance 170 3 1 6...