![Daikin EHYHBH05AAV3 Service Manual Download Page 91](http://html1.mh-extra.com/html/daikin/ehyhbh05aav3/ehyhbh05aav3_service-manual_4358735091.webp)
ESIE13-02A
Error Codes: Gas Condensing Boiler
91
Part 4 Troubleshooting
4
3
4
5
4
2.4.4
No heating (CH)
2.4.5
Symptom: No space heating
Possible causes
Corrective action
Heat pump error.
Check the user interface.
Communication problem with the heat pump.
Make sure the communication cable is properly
installed.
Incorrect heat pump settings.
Check the settings in the heat pump manual.
The service display displays "_", the gas boiler is
switched off.
Switch on the gas boiler with
f
.
No current (24 V).
Check the wiring.
Check the connector X4.
Replace the faulty pump.
The burner does NOT fire on space heating:
sensor S1 or S2 faulty.
Replace sensor S1 or S2. See "Error codes of
the gas boiler" on page 87.
Burner does NOT ignite.
See "2.4.1-Burner does not ignite" on page 89.
Summary of Contents for EHYHBH05AAV3
Page 16: ...Introduction ESIE13 02A 16 3 1 4 5...
Page 29: ...ESIE13 02A Functionality 29 Part 1 System Outline 3 1 4 5...
Page 30: ...Functionality ESIE13 02A Part 1 System Outline 30 3 1 1 4 5...
Page 35: ...ESIE13 02A Wiring Diagrams 35 Part 1 System Outline 3 1 4 5...
Page 36: ...Wiring Diagrams ESIE13 02A Part 1 System Outline 36 3 1 1 4 5...
Page 38: ...Wiring Diagrams ESIE13 02A Part 1 System Outline 38 3 1 1 4 5 3 3 Cable Dimensions...
Page 39: ...ESIE13 02A Wiring Diagrams 39 Part 1 System Outline 3 1 4 5...
Page 50: ...Outdoor Unit ESIE13 02A Part 2 Specifications 50 3 1 2 5...
Page 51: ...ESIE13 02A 51 Part 3 Commissioning 4 3 4 5 3 Part 3 Commissioning See Note on page 6...
Page 52: ...ESIE13 02A Part 3 Commissioning 52 3 1 3 5...
Page 98: ...Error Codes Hydro box ESIE13 02A Part 4 Troubleshooting 98 3 1 4 5 Troubleshooting...
Page 115: ...ESIE13 02A Error Codes Outdoor Units 115 Part 4 Troubleshooting 4 3 4 5 4 Troubleshooting...
Page 170: ...Maintenance Schedule ESIE13 02A Part 6 Maintenance 170 3 1 6...