![Daikin EHYHBH05AAV3 Service Manual Download Page 121](http://html1.mh-extra.com/html/daikin/ehyhbh05aav3/ehyhbh05aav3_service-manual_4358735121.webp)
ESIE13-02A
Error Codes: Outdoor Units
121
Part 4 Troubleshooting
4
3
4
5
4
4.9
H9, J3, J5, J6, J7, J8
Thermistor or Related Abnormality (Outdoor Unit)
Remote controller
display
H9, J3, J5, J6, J7, J8
Method of
malfunction
detection
Abnormality is detected according to the temperature detected by each individual thermistor.
Malfunction
decision conditions
When thermistor is disconnected or short-circuited during operation
Supposed causes
Faulty thermistor
Faulty connection of connector
Faulty outdoor unit PC board (control PC board)
Troubleshooting
(*) See also "Check No.4 - Resistance Conversion Table (Ambient, Coil, Fin)" on page 153.
Caution
Be sure to turn off power switch before connect or disconnect connector, or parts damage may be
occurred.
YES
YES
NO
Check connectors for
connection.
Connect correctly.
Replace the thermistor.
* Replace the outdoor unit PC board
(A1P) ERHQ***V3* / ERLQ***V3*
* Replace the control PC board (A1P)
ERHQ***W1* / ERLQ***W1*
Remove thermistor from
outdoor unit PC board,
then measure the
resistance using a tester.
H9 : Malfunction of outdoor temperature thermistor system
J3 : Malfunction of discharge pipe thermistor system
J5 : Malfunction of suction pipe thermistor system
J6 : Malfunction of heat exchange thermistor
J7: Malfunction of subcooling heat exchanger thermistor
J8: Malfunction of liquid thermistor
Normal?
Normal?
NO
Summary of Contents for EHYHBH05AAV3
Page 16: ...Introduction ESIE13 02A 16 3 1 4 5...
Page 29: ...ESIE13 02A Functionality 29 Part 1 System Outline 3 1 4 5...
Page 30: ...Functionality ESIE13 02A Part 1 System Outline 30 3 1 1 4 5...
Page 35: ...ESIE13 02A Wiring Diagrams 35 Part 1 System Outline 3 1 4 5...
Page 36: ...Wiring Diagrams ESIE13 02A Part 1 System Outline 36 3 1 1 4 5...
Page 38: ...Wiring Diagrams ESIE13 02A Part 1 System Outline 38 3 1 1 4 5 3 3 Cable Dimensions...
Page 39: ...ESIE13 02A Wiring Diagrams 39 Part 1 System Outline 3 1 4 5...
Page 50: ...Outdoor Unit ESIE13 02A Part 2 Specifications 50 3 1 2 5...
Page 51: ...ESIE13 02A 51 Part 3 Commissioning 4 3 4 5 3 Part 3 Commissioning See Note on page 6...
Page 52: ...ESIE13 02A Part 3 Commissioning 52 3 1 3 5...
Page 98: ...Error Codes Hydro box ESIE13 02A Part 4 Troubleshooting 98 3 1 4 5 Troubleshooting...
Page 115: ...ESIE13 02A Error Codes Outdoor Units 115 Part 4 Troubleshooting 4 3 4 5 4 Troubleshooting...
Page 170: ...Maintenance Schedule ESIE13 02A Part 6 Maintenance 170 3 1 6...