5 Preparation

Installer reference guide

11

07C2V3
Daikin Altherma monobloc compact outdoor unit
4P598847-1 – 2019.10

The outdoor unit is installed 5 m below the highest point in the water
circuit. The total water volume in the water circuit is 100 l.

No actions or adjustments are required.

Example 2

The outdoor unit is installed at the highest point in the water circuit.
The total water volume in the water circuit is 350 l. The concentration
of propylene glycol is 35%.

Actions:

▪ Because  the  total  water  volume  (350  l)  is  more  than  the  default

water volume (105 l), the pre-pressure must be decreased.

▪ The required pre-pressure is:

Pg = (0.3+(H/10)) bar = (0.3+(0/10)) bar = 0.3 bar

▪ The  corresponding  maximum  water  volume  at  0.3  bar  is  150  l.

(See the graph in the chapter above).

▪ Because  350  l  is  more  than  150  l,  the  expansion  vessel  is  NOT

appropriate  for  the  installation.  Therefore  the  system  requires  an
external expansion vessel.

5.4

Preparing electrical wiring

5.4.1

About preparing electrical wiring

INFORMATION

Also  read  the  precautions  and  requirements  in  the
"General safety precautions" chapter.

WARNING

▪ If  the  power  supply  has  a  missing  or  wrong  N-phase,

equipment might break down.

▪ Establish  proper  earthing.  Do  NOT  earth  the  unit  to  a

utility  pipe,  surge  absorber,  or  telephone  earth.
Incomplete earthing may cause electrical shock.

▪ Install the required fuses or circuit breakers.

▪ Secure  the  electrical  wiring  with  cable  ties  so  that  the

cables  do  NOT  come  in  contact  with  sharp  edges  or
piping, particularly on the high-pressure side.

▪ Do  NOT  use  taped  wires,  stranded  conductor  wires,

extension  cords,  or  connections  from  a  star  system.
They can cause overheating, electrical shock or fire.

▪ Do  NOT  install  a  phase  advancing  capacitor,  because

this  unit  is  equipped  with  an  inverter.  A  phase
advancing  capacitor  will  reduce  performance  and  may
cause accidents.

WARNING

▪ All  wiring  MUST  be  performed  by  an  authorised

electrician  and  MUST  comply  with  the  applicable
legislation.

▪ Make electrical connections to the fixed wiring.

▪ All  components  procured  on-site  and  all  electrical

construction  MUST  comply  with  the  applicable
legislation.

WARNING

ALWAYS use multicore cable for power supply cables.

5.4.2

About preferential kWh rate power supply

Electricity  companies  throughout  the  world  work  hard  to  provide
reliable  electric  service  at  competitive  prices  and  are  often
authorized  to  bill  clients  at  benefit  rates.  E.g.  time-of-use  rates,
seasonal rates, Wärmepumpentarif in Germany and Austria, ...

This  equipment  allows  for  connection  to  such  preferential  kWh  rate
power supply delivery systems.

Consult  with  the  electricity  company  acting  as  provider  at  the  site
where  this  equipment  is  to  be  installed  to  know  whether  it  is
appropriate to connect the equipment in one of the preferential kWh
rate power supply delivery systems available, if any.

When  the  equipment  is  connected  to  such  preferential  kWh  rate
power supply, the electricity company is allowed to:

▪ interrupt power supply to the equipment for certain periods of time;

▪ demand  that  the  equipment  only  consumes  a  limited  amount  of

electricity during certain periods of time.

The  domestic  hot  water  tank  is  designed  to  receive  an  input  signal
by  which  it  switches  the  outdoor  unit  into  forced-off  mode.  At  that
moment, the compressor will not operate.

The  wiring  to  the  unit  is  different  depending  on  whether  the  power
supply is interrupted or not.

5.4.3

Overview of electrical connections except
external actuators

Normal power

supply

Preferential kWh rate power supply

Power supply is
NOT interrupted

Power supply is

interrupted

580

1 50

0

0

a

2

1

3

e

c

d

580

1 50

0

0

1

3

4

2

e

b

d

c

During preferential
kWh rate power
supply activation,
power supply is NOT
interrupted. The
outdoor unit is turned
off by the control.

Remark:

 The

electricity company
must always allow the
power consumption
of the hydro part of
the outdoor unit (and
of the domestic hot
water tank, if part of
the system).

580

1 50

0

0

580

1 50

0

0

a

b

e

c

d

3

2

1

5

4

During preferential
kWh rate power
supply activation,
power supply is
interrupted
immediately or after
some time by the
electricity company.
In this case, the
hydro part of the
outdoor unit (and the
control box, if part of
the system) must be
powered by a
separate normal
power supply.

a

Normal power supply

b

Preferential kWh rate power supply

c

Hydro part of the outdoor unit

d

Refrigerant part of the outdoor unit

e

Domestic hot water tank

1

Power supply for outdoor unit

2

Interconnection cable to domestic hot water tank

3

Power supply for domestic hot water tank

4

Preferential kWh rate power supply (voltage free contact)

5

Normal kWh rate power supply (to power the hydro part of
the outdoor unit in the event of a power supply interruption
of the preferential kWh rate power supply)

Summary of Contents for EBLQ-C2V3

Page 1: ...Installer reference guide Daikin Altherma monobloc compact outdoor unit English Installer reference guide Daikin Altherma monobloc compact outdoor unit EBLQ05C2V3 EBLQ07C2V3...

Page 2: ...outdoor unit 14 6 3 5 To provide drainage 14 6 3 6 To prevent the outdoor unit from falling over 15 6 4 Connecting water piping 15 6 4 1 About connecting the water piping 15 6 4 2 Precautions when co...

Page 3: ...y small animals Small animals that make contact with electrical parts can cause malfunctions smoke or fire CAUTION Do NOT touch the air inlet or aluminium fins of the unit NOTICE Do NOT place any obje...

Page 4: ...e nameplate of the unit It states the type of refrigerant and necessary amount The unit is factory charged with refrigerant and depending on pipe sizes and pipe lengths some systems require additional...

Page 5: ...arrying connections must be separated before the earth connection is The length of the conductors between the power supply stress relief and the terminal block itself must be as such that the current...

Page 6: ...ons Safety instructions that you must read before installing About the documentation What documentation exists for the installer About the box How to unpack the units and remove their accessories Abou...

Page 7: ...remote outdoor sensor can be installed to measure the outdoor temperature on another location e g to avoid direct sunlight to have an improved system behaviour For installation instructions see the in...

Page 8: ...of the unit Where the voltage fluctuates a lot In vehicles or vessels Where acidic or alkaline vapour is present Seaside installation Make sure the outdoor unit is NOT directly exposed to sea winds T...

Page 9: ...ovide adequate safeguards in the water circuit to ensure that the maximum pressure is NOT exceeded Water temperature All installed piping and piping accessories valve connections MUST withstand the fo...

Page 10: ...s case it is recommended to install an extra vessel outside the unit a This is the height difference m between the highest point of the water circuit and the outdoor unit If the outdoor unit is at the...

Page 11: ...to provide reliable electric service at competitive prices and are often authorized to bill clients at benefit rates E g time of use rates seasonal rates W rmepumpentarif in Germany and Austria This e...

Page 12: ...nstallation manual of the tank 6 Installation 6 1 Overview Installation This chapter describes what you have to do and know on site to install the system Typical workflow Installation typically consis...

Page 13: ...in accordance with the foundation drawing INFORMATION For information on the available options contact your dealer If the unit is installed directly on the floor prepare 4 sets of M8 or M10 anchor bo...

Page 14: ...ation places where water leaking from the unit due to a blocked drain pan can cause damage to the location Make sure that condensation water can be evacuated properly Install the unit on a base to mak...

Page 15: ...tank 3 Filling the water circuit 4 Protecting the water circuit against freezing addition of glycol 5 Filling the domestic hot water tank 6 Insulating the water piping INFORMATION For instructions re...

Page 16: ...e outdoor unit 4 Connecting the power supply of the domestic hot water tank 5 Connecting the power supply of the optional backup heater inside the domestic hot water tank if applicable 6 Connecting th...

Page 17: ...g b High voltage wiring main power supply 5 Make sure that the cable does NOT come in contact with sharp edges or hot gas piping 6 Install the switch box cover INFORMATION When installing field supply...

Page 18: ...CE Only connect NO normally open valves NO X5M X3M M2S 2 1 6 6 Finishing the outdoor unit installation 6 6 1 To close the outdoor unit 1 Close the switch box cover 2 Mount the top plate and the front...

Page 19: ...r further commissioning instructions see the installation manual of the domestic hot water tank 8 Hand over to the user Once the test run is finished and the unit operates properly please make sure th...

Page 20: ...or similarly qualified persons Booster heater of the domestic hot water tank See the installation manual of the domestic hot water tank 10 Troubleshooting 10 1 Overview Troubleshooting For instruction...

Page 21: ...he gas stop valve and stop forced cooling a c b d d e a Gas stop valve b Closing direction c Hexagonal wrench d Valve cap e Liquid stop valve 11 3 To start and stop forced cooling Confirm that DIP swi...

Page 22: ...CuT 7 9 CuT 1 4 3 2 t 12 7 CuT 12 7 CuT R4T 9 5 CuT 6 4 CuT 6 4 CuT M 6 4 CuT 6 4 CuT Discharge pipe thermistor Accumulator Compressor High pressure switch Muffler Muffler 4 way valve Pressure sensor...

Page 23: ...ensor S1PH High pressure switch S2 S503 Connector SA1 Surge arrestor SHEET METAL Terminal strip on fixed plate SW1 SW3 Push buttons SW2 SW5 DIP switches U Connector V Connector V2 V3 V401 Varistor W C...

Page 24: ...230 V earth Only for normal power supply installation MONOBLOC UNIT STANDARD PART POWER SUPPLY Control box 12 3 ESP curve Outdoor unit Note A flow error will occur when the minimum water flow rate is...

Page 25: ...duct or application explaining how to install configure and maintain it Operation manual Instruction manual specified for a certain product or application explaining how to operate it Maintenance inst...

Page 26: ......

Page 27: ......

Page 28: ...4P598847 1 2019 10 Copyright 2019 Daikin...

Reviews: