5 Preparation

Installer reference guide

9

07C2V3
Daikin Altherma monobloc compact outdoor unit
4P598847-1 – 2019.10

5.3

Preparing water piping

5.3.1

Water circuit requirements

INFORMATION

Also  read  the  precautions  and  requirements  in  the
"General safety precautions" chapter.

NOTICE

In  case  of  plastic  pipes,  make  sure  they  are  fully  oxygen
diffusion  tight  according  to  DIN  4726.  The  diffusion  of
oxygen into the piping can lead to excessive corrosion.

Connecting piping – Legislation.

 Make all piping connections in

accordance  with  the  applicable  legislation  and  the  instructions  in
the "Installation" chapter, respecting the water inlet and outlet.

Connecting  piping  –  Force.

  Do  NOT  use  excessive  force  when

connecting  the  piping.  Deformation  of  the  piping  can  cause
malfunctioning of the unit.

Connecting  piping  –  Tools.

  Only  use  appropriate  tooling  to

handle  brass,  which  is  a  soft  material.  If  NOT,  pipes  will  get
damaged.

Connecting piping – Air, moisture, dust.

 If air, moisture or dust

gets into the circuit, problems may occur. To prevent this:

▪ Only use clean pipes

▪ Hold the pipe end downwards when removing burrs.

▪ Cover the pipe end when inserting it through a wall, to prevent

dust and/or particles from entering the pipe.

▪ Use a decent thread sealant to seal connections.

NOTICE

If  glycol  is  present  in  the  system,  make  sure  the  thread
sealant used is resistant to glycol.

Closed  circuit.

  Use  the  outdoor  unit  ONLY  in  a  closed  water

system.  Using  the  system  in  an  open  water  system  will  lead  to
excessive corrosion.

Piping  length.

  It  is  recommended  to  avoid  long  runs  of  piping

between the domestic hot water tank and the hot water end point
(shower, bath,…) and to avoid dead ends.

Piping  diameter.

  Select  the  water  piping  diameter  in  relation  to

the required water flow and the available external static pressure
of the pump. See 

"12 Technical data" 

[

4

 22] for the external static

pressure curves of the outdoor unit.

Water flow.

 It is required to guarantee a minimum flow of 13 l/min.

When the flow is lower, the system will stop operation and display
error 7H.

Minimum required flow rate

05+07 models

13 l/min

Field  supply  components  –  Water  and  glycol.

  Only  use

materials  that  are  compatible  with  the  water  (and,  if  applicable,
glycol)  used  in  the  system,  and  with  the  materials  used  in  the
outdoor unit.

Field supply components – Water pressure and temperature.

Check  that  all  components  in  the  field  piping  can  withstand  the
water pressure and water temperature.

Water pressure.

 The maximum water pressure is 3 bar. Provide

adequate  safeguards  in  the  water  circuit  to  ensure  that  the
maximum pressure is NOT exceeded.

Water  temperature.

  All  installed  piping  and  piping  accessories

(valve, 

connections,…) 

MUST 

withstand 

the 

following

temperatures:

Water circuit

Water temperature

Space heating

65°C

Domestic hot water

89°C

Drainage – Low points.

 Provide drain taps at all low points of the

system in order to allow complete drainage of the water circuit.

Drainage – Pressure relief valve.

 Provide a proper drain for the

pressure  relief  valve  to  avoid  water  coming  into  contact  with
electrical parts.

Air vents.

 Provide air vents at all high points of the system, which

must also be easily accessible for servicing. The outdoor unit has
a  manual  air  purge  valve.  The  backup  heater  (option)  has  an
automatic  air  purge  valve.  Check  that  automatic  air  purge  valves
are NOT tightened too much, so that the automatic release of air
from the water circuit is possible.

Zn-coated parts.

 Never use zinc coated parts in the water circuit.

Because  the  internal  water  circuit  of  the  unit  uses  copper  piping,
excessive corrosion may occur.

Non-brass  metallic  piping.

  When  using  non-brass  metallic

piping,  insulate  the  brass  and  non-brass  properly  so  that  they  do
NOT  make  contact  with  each  other.  This  to  prevent  galvanic
corrosion.

Filter.

  It  is  strongly  recommended  to  install  an  additional  filter  on

the  heating  water  circuit.  Especially  to  remove  metallic  particles
from foul heating piping, it is recommended to use a magnetic or
cyclone  filter,  which  can  remove  small  particles.  Small  particles
may  damage  the  unit  and  will  NOT  be  removed  by  the  standard
filter of the heat pump system.

Thermostatic  mixing  valves.

  In  accordance  with  the  applicable

legislation,  it  may  be  necessary  to  install  thermostatic  mixing
valves.

Hygienic measures.

 The installation must be in compliance with

the  applicable  legislation  and  may  require  additional  hygienic
installation measures.

Recirculation  pump.

  In  accordance  with  the  applicable

legislation,  it  may  be  required  to  connect  a  recirculation  pump  in
between the hot water end point and the recirculation connection
of the domestic hot water tank.

c

d

a

b

a

Recirculation connection

b

Hot water connection

c

Shower

d

Recirculation pump

5.3.2

Formula to calculate the expansion vessel
pre-pressure

The  pre-pressure  (Pg)  of  the  vessel  depends  on  the  installation
height difference (H):

Pg=0.3+(H/10) (bar)

5.3.3

To check the water volume and flow rate

The outdoor unit has an expansion vessel of 7 litre with a factory-set
pre-pressure of 1 bar.

To make sure that the unit operates properly:

▪ You must check the minimum and maximum water volume.

▪ You  might  need  to  adjust  the  pre-pressure  of  the  expansion

vessel.

Summary of Contents for EBLQ-C2V3

Page 1: ...Installer reference guide Daikin Altherma monobloc compact outdoor unit English Installer reference guide Daikin Altherma monobloc compact outdoor unit EBLQ05C2V3 EBLQ07C2V3...

Page 2: ...outdoor unit 14 6 3 5 To provide drainage 14 6 3 6 To prevent the outdoor unit from falling over 15 6 4 Connecting water piping 15 6 4 1 About connecting the water piping 15 6 4 2 Precautions when co...

Page 3: ...y small animals Small animals that make contact with electrical parts can cause malfunctions smoke or fire CAUTION Do NOT touch the air inlet or aluminium fins of the unit NOTICE Do NOT place any obje...

Page 4: ...e nameplate of the unit It states the type of refrigerant and necessary amount The unit is factory charged with refrigerant and depending on pipe sizes and pipe lengths some systems require additional...

Page 5: ...arrying connections must be separated before the earth connection is The length of the conductors between the power supply stress relief and the terminal block itself must be as such that the current...

Page 6: ...ons Safety instructions that you must read before installing About the documentation What documentation exists for the installer About the box How to unpack the units and remove their accessories Abou...

Page 7: ...remote outdoor sensor can be installed to measure the outdoor temperature on another location e g to avoid direct sunlight to have an improved system behaviour For installation instructions see the in...

Page 8: ...of the unit Where the voltage fluctuates a lot In vehicles or vessels Where acidic or alkaline vapour is present Seaside installation Make sure the outdoor unit is NOT directly exposed to sea winds T...

Page 9: ...ovide adequate safeguards in the water circuit to ensure that the maximum pressure is NOT exceeded Water temperature All installed piping and piping accessories valve connections MUST withstand the fo...

Page 10: ...s case it is recommended to install an extra vessel outside the unit a This is the height difference m between the highest point of the water circuit and the outdoor unit If the outdoor unit is at the...

Page 11: ...to provide reliable electric service at competitive prices and are often authorized to bill clients at benefit rates E g time of use rates seasonal rates W rmepumpentarif in Germany and Austria This e...

Page 12: ...nstallation manual of the tank 6 Installation 6 1 Overview Installation This chapter describes what you have to do and know on site to install the system Typical workflow Installation typically consis...

Page 13: ...in accordance with the foundation drawing INFORMATION For information on the available options contact your dealer If the unit is installed directly on the floor prepare 4 sets of M8 or M10 anchor bo...

Page 14: ...ation places where water leaking from the unit due to a blocked drain pan can cause damage to the location Make sure that condensation water can be evacuated properly Install the unit on a base to mak...

Page 15: ...tank 3 Filling the water circuit 4 Protecting the water circuit against freezing addition of glycol 5 Filling the domestic hot water tank 6 Insulating the water piping INFORMATION For instructions re...

Page 16: ...e outdoor unit 4 Connecting the power supply of the domestic hot water tank 5 Connecting the power supply of the optional backup heater inside the domestic hot water tank if applicable 6 Connecting th...

Page 17: ...g b High voltage wiring main power supply 5 Make sure that the cable does NOT come in contact with sharp edges or hot gas piping 6 Install the switch box cover INFORMATION When installing field supply...

Page 18: ...CE Only connect NO normally open valves NO X5M X3M M2S 2 1 6 6 Finishing the outdoor unit installation 6 6 1 To close the outdoor unit 1 Close the switch box cover 2 Mount the top plate and the front...

Page 19: ...r further commissioning instructions see the installation manual of the domestic hot water tank 8 Hand over to the user Once the test run is finished and the unit operates properly please make sure th...

Page 20: ...or similarly qualified persons Booster heater of the domestic hot water tank See the installation manual of the domestic hot water tank 10 Troubleshooting 10 1 Overview Troubleshooting For instruction...

Page 21: ...he gas stop valve and stop forced cooling a c b d d e a Gas stop valve b Closing direction c Hexagonal wrench d Valve cap e Liquid stop valve 11 3 To start and stop forced cooling Confirm that DIP swi...

Page 22: ...CuT 7 9 CuT 1 4 3 2 t 12 7 CuT 12 7 CuT R4T 9 5 CuT 6 4 CuT 6 4 CuT M 6 4 CuT 6 4 CuT Discharge pipe thermistor Accumulator Compressor High pressure switch Muffler Muffler 4 way valve Pressure sensor...

Page 23: ...ensor S1PH High pressure switch S2 S503 Connector SA1 Surge arrestor SHEET METAL Terminal strip on fixed plate SW1 SW3 Push buttons SW2 SW5 DIP switches U Connector V Connector V2 V3 V401 Varistor W C...

Page 24: ...230 V earth Only for normal power supply installation MONOBLOC UNIT STANDARD PART POWER SUPPLY Control box 12 3 ESP curve Outdoor unit Note A flow error will occur when the minimum water flow rate is...

Page 25: ...duct or application explaining how to install configure and maintain it Operation manual Instruction manual specified for a certain product or application explaining how to operate it Maintenance inst...

Page 26: ......

Page 27: ......

Page 28: ...4P598847 1 2019 10 Copyright 2019 Daikin...

Reviews: