5 Preparation

Installer reference guide

10

07C2V3

Daikin Altherma monobloc compact outdoor unit

4P598847-1 – 2019.10

Minimum water volume

Check  that  the  total  water  volume  in  the  installation  is  minimum
20 litre, the internal water volume of the outdoor unit NOT included.

INFORMATION

In  critical  processes,  or  in  rooms  with  a  high  heat  load,
extra water might be required.

NOTICE

When  circulation  in  each  space  heating/cooling  loop  is
controlled by remotely controlled valves, it is important that
the minimum water volume is guaranteed, even if all of the
valves are closed.

Maximum water volume

NOTICE

The maximum water volume depends on whether glycol is
added  to  the  water  circuit.  For  more  information  on  the
addition  of  glycol,  refer  to  the  installation  manual  of  the
domestic hot water tank.

Use the following graph to determine the maximum water volume for
the calculated pre-pressure.

20

2,4

2,1

1,8

1,5

1,2

0,9

1

0,6

0,3

70

120

170

150

105

185

220

270

A

B

A

Pre-pressure (bar)

B

Maximum water volume (l)
Water
Water + glycol

Example:  Maximum  water  volume  and  expansion  vessel  pre-
pressure

Installation

height

difference

(a)

Water volume

≤185/105 l

(b)

>185/105 l

(b)

≤7 m

No pre-pressure
adjustment is required.

Do the following:

▪ Decrease 

the 

pre-

pressure  according  to
the required installation
height  difference.  The
pre-pressure 

should

decrease by 0.1 bar for
each metre below 7 m.

▪ Check  if  the  water

volume 

does 

NOT

exceed  the  maximum
allowed water volume.

>7 m

Do the following:

▪ Increase 

the 

pre-

pressure  according  to
the 

required

installation 

height

difference.  The  pre-
pressure 

should

increase by 0.1 bar for
each metre above 7 m.

▪ Check  if  the  water

volume 

does 

NOT

exceed  the  maximum
allowed water volume.

The expansion vessel of
the outdoor unit is too
small for the installation.
In this case, it is
recommended to install
an extra vessel outside
the unit.

(a)

This is the height difference (m) between the highest point
of the water circuit and the outdoor unit. If the outdoor unit
is at the highest point of the installation, the installation
height is 0 m.

(b)

The maximum water volume is 185 l in case the circuit is
only filled with water, and 105 l in case the circuit is filled
with water and glycol.

Minimum flow rate

Check  that  the  minimum  flow  rate  (required  during  defrost/backup
heater operation) in the installation is guaranteed in all conditions.

NOTICE

If  glycol  was  added  to  the  water  circuit,  and  the
temperature  of  the  water  circuit  is  low,  the  flow  rate  will
NOT  be  displayed  on  the  user  interface.  In  this  case,  the
minimum  flow  rate  can  be  checked  by  way  of  the  pump
test (check that the user interface does NOT display error
7H).

NOTICE

When circulation in each or certain space heating loops is
controlled by remotely controlled valves, it is important that
the minimum flow rate is guaranteed, even if all valves are
closed. In case the minimum flow rate cannot be reached,
a flow error 7H will be generated (no heating or operation).

Minimum required flow rate

05+07 models

13 l/min

See  the  recommended  procedure  as  described  in  the  installation
manual of the domestic hot water tank.

5.3.4

Changing the pre-pressure of the
expansion vessel

NOTICE

Only a licensed installer may adjust the pre-pressure of the
expansion vessel.

The default pre-pressure of the expansion vessel is 1 bar. When it is
required  to  change  the  pre-pressure,  take  following  guidelines  into
account:

▪ Only use dry nitrogen to set the expansion vessel pre-pressure.

▪ Inappropriate  setting  of  the  expansion  vessel  pre-pressure  will

lead to malfunction of the system.

Changing the pre-pressure of the expansion vessel should be done
by  releasing  or  increasing  nitrogen  pressure  through  the  Schrader
valve of the expansion vessel.

a

a

Schrader valve

5.3.5

To check the water volume: Examples

Example 1

Summary of Contents for EBLQ-C2V3

Page 1: ...Installer reference guide Daikin Altherma monobloc compact outdoor unit English Installer reference guide Daikin Altherma monobloc compact outdoor unit EBLQ05C2V3 EBLQ07C2V3...

Page 2: ...outdoor unit 14 6 3 5 To provide drainage 14 6 3 6 To prevent the outdoor unit from falling over 15 6 4 Connecting water piping 15 6 4 1 About connecting the water piping 15 6 4 2 Precautions when co...

Page 3: ...y small animals Small animals that make contact with electrical parts can cause malfunctions smoke or fire CAUTION Do NOT touch the air inlet or aluminium fins of the unit NOTICE Do NOT place any obje...

Page 4: ...e nameplate of the unit It states the type of refrigerant and necessary amount The unit is factory charged with refrigerant and depending on pipe sizes and pipe lengths some systems require additional...

Page 5: ...arrying connections must be separated before the earth connection is The length of the conductors between the power supply stress relief and the terminal block itself must be as such that the current...

Page 6: ...ons Safety instructions that you must read before installing About the documentation What documentation exists for the installer About the box How to unpack the units and remove their accessories Abou...

Page 7: ...remote outdoor sensor can be installed to measure the outdoor temperature on another location e g to avoid direct sunlight to have an improved system behaviour For installation instructions see the in...

Page 8: ...of the unit Where the voltage fluctuates a lot In vehicles or vessels Where acidic or alkaline vapour is present Seaside installation Make sure the outdoor unit is NOT directly exposed to sea winds T...

Page 9: ...ovide adequate safeguards in the water circuit to ensure that the maximum pressure is NOT exceeded Water temperature All installed piping and piping accessories valve connections MUST withstand the fo...

Page 10: ...s case it is recommended to install an extra vessel outside the unit a This is the height difference m between the highest point of the water circuit and the outdoor unit If the outdoor unit is at the...

Page 11: ...to provide reliable electric service at competitive prices and are often authorized to bill clients at benefit rates E g time of use rates seasonal rates W rmepumpentarif in Germany and Austria This e...

Page 12: ...nstallation manual of the tank 6 Installation 6 1 Overview Installation This chapter describes what you have to do and know on site to install the system Typical workflow Installation typically consis...

Page 13: ...in accordance with the foundation drawing INFORMATION For information on the available options contact your dealer If the unit is installed directly on the floor prepare 4 sets of M8 or M10 anchor bo...

Page 14: ...ation places where water leaking from the unit due to a blocked drain pan can cause damage to the location Make sure that condensation water can be evacuated properly Install the unit on a base to mak...

Page 15: ...tank 3 Filling the water circuit 4 Protecting the water circuit against freezing addition of glycol 5 Filling the domestic hot water tank 6 Insulating the water piping INFORMATION For instructions re...

Page 16: ...e outdoor unit 4 Connecting the power supply of the domestic hot water tank 5 Connecting the power supply of the optional backup heater inside the domestic hot water tank if applicable 6 Connecting th...

Page 17: ...g b High voltage wiring main power supply 5 Make sure that the cable does NOT come in contact with sharp edges or hot gas piping 6 Install the switch box cover INFORMATION When installing field supply...

Page 18: ...CE Only connect NO normally open valves NO X5M X3M M2S 2 1 6 6 Finishing the outdoor unit installation 6 6 1 To close the outdoor unit 1 Close the switch box cover 2 Mount the top plate and the front...

Page 19: ...r further commissioning instructions see the installation manual of the domestic hot water tank 8 Hand over to the user Once the test run is finished and the unit operates properly please make sure th...

Page 20: ...or similarly qualified persons Booster heater of the domestic hot water tank See the installation manual of the domestic hot water tank 10 Troubleshooting 10 1 Overview Troubleshooting For instruction...

Page 21: ...he gas stop valve and stop forced cooling a c b d d e a Gas stop valve b Closing direction c Hexagonal wrench d Valve cap e Liquid stop valve 11 3 To start and stop forced cooling Confirm that DIP swi...

Page 22: ...CuT 7 9 CuT 1 4 3 2 t 12 7 CuT 12 7 CuT R4T 9 5 CuT 6 4 CuT 6 4 CuT M 6 4 CuT 6 4 CuT Discharge pipe thermistor Accumulator Compressor High pressure switch Muffler Muffler 4 way valve Pressure sensor...

Page 23: ...ensor S1PH High pressure switch S2 S503 Connector SA1 Surge arrestor SHEET METAL Terminal strip on fixed plate SW1 SW3 Push buttons SW2 SW5 DIP switches U Connector V Connector V2 V3 V401 Varistor W C...

Page 24: ...230 V earth Only for normal power supply installation MONOBLOC UNIT STANDARD PART POWER SUPPLY Control box 12 3 ESP curve Outdoor unit Note A flow error will occur when the minimum water flow rate is...

Page 25: ...duct or application explaining how to install configure and maintain it Operation manual Instruction manual specified for a certain product or application explaining how to operate it Maintenance inst...

Page 26: ......

Page 27: ......

Page 28: ...4P598847 1 2019 10 Copyright 2019 Daikin...

Reviews: