background image

5

5000

4500

4000

3500

3000

2500

2000

1500

1000

500

0      1      2      3      4       5      6      7      8       9

10

LEAK(S)
PRESENT

MINUTES

V

AC

U

U

M

 

IN

 

MI

C

R

O

N

S

CONDENSIBLES OR SMALL
LEAK PRESENT

NO LEAKS
NO CONDENSIBLES

Refer to the Remote Condensing Unit Service Manual for more
detailed instructions on system evacuation, preliminary charge
adjustment, and final charge adjustment.

ELECTRICAL CONNECTIONS

HIGH VOLTAGE! 

Disconnect ALL power before servicing.
Multiple power sources may be present. Failure to do
so may cause property damage, personal injury or

death due to electric shock. Wiring must conform with
NEC or CEC and all local codes. Undersized wires could cause

poor equipment performance, equipment damage or fire.

To avoid the risk of fire or equipment damage, use copper

conductors.

NOTICE

Units with reciprocating compressors and non-bleed TXV’s
require a Hard Start Kit.

This unit is designed for three phase operation. DO NOT OPERATE
ON A SINGLE PHASE POWER SUPPLY. Measure the power supply
to the unit. The supply voltage 

must

 be in agreement with the

unit rating plate power requirements and within the range listed
below:

RATED 

VOLTAGE

MINIMUM SUPPLY

VOLTAGE

MAXIMUM SUPPLY

VOLTAGE

208/230V

197

253

460V

414

506

The condensing unit rating plate lists pertinent electrical data nec-
essary for proper electrical service and overcurrent protection.
Wires should be sized to limit voltage drop to 2% (max.) from the
main breaker or fuse panel to the condensing unit.  Consult the
NEC, CEC, and all local codes to determine the correct wire gauge
and length.  The wire size must be sufficient to carry the Minimum
Circuit Ampacity (MCA) listed on the serial plate.

The supply voltage can be unbalanced (phase to phase) within
2%.  The following formula can be used to determine the percent-
age of voltage unbalance for your unit.

Percentage
Voltage
Unbalance

100 x

Max. Voltage Deviation From

Average Voltage
Average Voltage

Example:

L1-L2 = 220V
L2-L3 = 216V

Average Voltage

=

(220 + 216 + 213)/3

=

649/3

Maximum Deviation from Average = 220 - 216 = 4

% Voltage Unbalance = 100 x (4/216)

= 400/216

10

15

20

25

30

35

40

45

14

75

50

37

NR

NR

NR

NR

NR

12

118

79

59

47

NR

NR

NR

NR

10

188

125

95

75

63

54

NR

NR

8

301

201

150

120

100

86

75

68

6

471

314

235

188

157

134

118

110

*Based on NEC 1996

MAXIMUM ALLOWABLE LENGTH IN FEET

TO LIMIT VOLTAGE DROP TO 2%

Minimum Circuit Ampacity (MCA)

Wire Size

(AWG)

Example:

A 7 ½ Ton unit is to be installed. The distance from the 
building to the unit is 75’. Calculate the minimum wire size 
assuming no more than 2% voltage drop.

MCA for 7   Ton 230V unit = 43.3 (from S&R plate).

Applying previous table wire sizes less than #8 AWG cannot 
be used for circuits which have a rating of 45A. The #8 wire 
is not suitable since the maximum length for a 45A circuit 
is 68’. 
Solution: Use a #6 AWG wire suitable up to 110’. 

NOTE: It is the contractors’s responsibility to follow the NEC 
(USA) or CEC (Canada) when sizing the service wire for this 
unit.

½

*Always refer to the unit’s S&R plate for actual ratings.

Local codes often require a disconnect switch located near the
unit; do not install the switch on the unit.  Refer to the installation
instructions supplied with the indoor furnace/air handler for spe-
cific wiring connections and indoor unit configuration.  Likewise,
consult the instructions packaged with the thermostat for mount-
ing and location information.

Summary of Contents for DZ11TA Series

Page 1: ...tion damage or installation of incorrectly shipped units CODES REGULATIONS This product is designed and manufactured to comply with na tional codes Installation in accordance with such codes and or prevailing local codes regulations is the responsibility of the in staller The manufacturer assumes no responsibility for equip ment installed in violation of any codes or regulations Rated per formance...

Page 2: ...s preferred When possible mini mize the amount of bends and turns ROOFTOP INSTALLATIONS If it is necessary to install this unit on a roof structure ensure the roof structure can support the weight and that proper consider ation is given to the weather tight integrity of the roof Since the unit can vibrate during operation sound vibration transmission should be considered when installing the unit V...

Page 3: ... tubing clean and dry prior to and during installation Tubing should always be cut square keeping ends round and free from burrs Clean the tubing to prevent contamination Do NOT let refrigerant lines come in direct contact with plumbing ductwork floor joists wall studs floors and walls When running refrigerant lines through a foundation or wall openings should allow for sound and vibration absorbi...

Page 4: ...iers which are continually wet when the unit is operating NOTE Be careful not to kink or dent refrigerant lines Kinked or dented lines will cause poor performance or compressor damage Do NOT make final refrigerant line connection until plugs are removed from refrigerant tubing NOTE Before brazing verify indoor piston size by checking the piston kit chart packaged with indoor unit LEAK TESTING NITR...

Page 5: ...fficient to carry the Minimum Circuit Ampacity MCA listed on the serial plate The supply voltage can be unbalanced phase to phase within 2 The following formula can be used to determine the percent age of voltage unbalance for your unit Percentage Voltage Unbalance 100 x Max Voltage Deviation From Average Voltage Average Voltage Example L1 L2 220V L2 L3 216V Average Voltage 220 216 213 3 649 3 Max...

Page 6: ...y reduced compared to marked values To correct disconnect power and switch any two leads at the unit contactor and re observe HIGH VOLTAGE CONNECTIONS Route power supply and ground wires through the high voltage port and terminate in accordance with the wiring diagram pro vided inside the control panel cover LOW VOLTAGE CONNECTIONS Condensing unit control wiring requires a five conductor low volt ...

Page 7: ...rature 5 Using an additional electronic thermometer measure the ambient 6 Adjust the charge until the hot gas temperature equals 105º F ambient or 5º F Remove charge to increase the tem perature NOTE When adjusting the charge allow the compressor to operate for about 10 minutes before taking readings NOTE Subsequent opening and replace of the cap will require only 1 2 to 1 hex flat See the table b...

Page 8: ...t of equipment 1 1 x temp rise In other cases measurement of external static pressure is helpful For details see the Installation Instructions for your indoor unit TROUBLE SHOOTING ANALYSIS TABLE COMPLAINT PROBABLE CAUSE REMEDY 1 High Head Pressure 1 Excessive charge of refrigerant in system 2 Inadequate supply of air across the condenser coil 3 Non condensate gases in the system 1 Purge or pump d...

Page 9: ...low 375 425 CFM ton will cause excessive discharge pressures that may cause the high pres sure switch to function Low Return Air Temperatures Return ductwork temperatures that are less than 60 F will cause low discharge pressure low suction pressure and excessive de frost cycling Undercharging An undercharged system will cause low discharge pressure low suction pressure and an accumulation of fros...

Page 10: ...10 THIS PAGE LEFT INTENTIONALLY BLANK ...

Page 11: ...ER MOTOR RELAY CS COMPRESSOR SOLENOID HPS HIGH PRESSURE SWITCH CHS CRANKCASE HEATER SWITCH SSHR SECOND STAGE HEAT RELAY CONTROLS SHOWN WITH THERMOSTAT IN OFF POSITION WIRING CODE FACTORY WIRING HIGH VOLTAGE LOW VOLTAGE OPTIONAL HIGH VOLTAGE FIELD WIRING HIGH VOLTAGE LOW VOLTAGE LVJB CONTROL BO X BK BR PU BK DFT YL PK LPS DFT W O RV DC RVC BK BK CH BK W2 RD YL C T1 L1 T2 L2 T3 L3 YL RD FC PU BR PU ...

Page 12: ...12 Our continuing commitment to quality products may mean a change in specifications without notice 2018 5151 San Felipe St Suite 500 Houston TX 77056 www daikinac com ...

Reviews: