background image

8

HIGH VOLTAGE! 

Disconnect ALL power before servicing. Multiple

power sources may be present. Failure to do so may

cause property damage, personal injury or death.

4. Disconnect outdoor fan by removing the purple lead from

the Condenser Fan Defrost Relay.

5. Restart unit and allow frost to accumulate.

6. After a few minutes the defrost thermostat should close.  To

verify the position of the thermostat check for 24V between
“DFT” and “C” on the defrost board.  Should the defrost ther-
mostat fail to close after a heavy build-up of frost and the
thermostat is less than 28

°

, the thermostat is to be replaced.

7. After the thermostat has closed, short across the test pins

with the a screwdr

iver blade until the reversing valve shifts.

This could take up to 22 seconds depending upon the posi-
tion of the timing setting on the defrost board.  Immediately
upon the action of the reversing valve, remove the short.

Note:

  If this short is not removed immediately, the defrost

activity will last only 3 seconds.

8. After defrost has terminated (up to 10 minutes) check the

defrost thermostat for 24V between “DF

T” and “C”.  This

reading should be 0V (open sensor).

9. Shut off power to the unit.

HIGH VOLTAGE! 

Disconnect ALL power before servicing. Multiple

power sources may be present. Failure to do so may

cause property damage, personal injury or death.

10. Replace outdoor fan mo

tor wire removed in Step 4.

NOTE: 

The compressor “run time’ is accumulative during multiple

heating cycles. The timer will reset to zero only when the defrost
sensor returns to an open condition. If the room thermostat is
operating in the “EM HT” mode, no accumulation of compressor
time is recorded.

TROUBLESHOOTING

Qualified Installer/Servicer only

When troubleshooting, the first step should always be to check
for clean coils, clean filter(s), and proper airflow. Indoor airflow
should be 375 to 425 CFM per ton of cooling based on the size of
the outdoor unit. The most common way of establishing indoor
airflow is heating temperature rise. Indoor airflow will then be
(Heating output of equipment) / (1.1 x temp. rise). In other cases,
measurement of external static pressure is helpful. For details,
see the Installation Instructions for your indoor unit.

TROUBLE SHOOTING ANALYSIS TABLE 

 

 

COMPLAINT  

PROBABLE CAUSE 

REMEDY 

1. High Head Pressure 

1. Excessive charge of refrigerant in system. 
2. Inadequate supply of air across the 

condenser coil. 

3. Non-condensate gases in the system. 

1. Purge or pump-down excessive charge. 
2. Make certain that coil is not fouled in any 

way, or that air is not re-circulating. 

3. Purge these gases from  the system. 

Recharge system, if necessary. 

2. Low Head Pressure 

1. System low on refrigerant. 
2. Compressor valves broken. 

1. Charge system until sight glass is clear of bubbles. 
2. Replace compressor. 

3. Low Suction Pressure 

1. Liquid line valve closed. 
2. Restricted liquid line. 
3. The bulb of the thermal expansion valve 

has lost its charge. 

 
4. System low on refrigerant. 
 
5. Dirty filters. 
6. Coil frosted up. 
7. Flash gas in the liquid line. 
8. Quantity of air through evaporator  not adequate. 

1. Open the liquid line valve. 
2. Replace filter-dryer. 
3. Detach the bulb from the suction line and hold 

in one hand. If no liquid refrigerant goes through 
the valve, replace the valve. 

4. Test the unit for leaks. Add refrigerant until sight 

glass is free from bubbles, after repairing leak. 

5. Clean or replace filter. 
6. Defrost and clean coil. Clean or replace filters. 
7. Excessive liquid line drop. Check liquid line size. 
8. Increase the blower speed. 

4. High Suction Pressure 

1. Expansion valve stuck open. 
2. Expansion valve bulb not in contact with 

suction line. 

3. Suction and/or discharge valve leaking or broken. 

1. Correct valve action or replace the valve. 
2. Fasten bulb securely to suction line. 
 
3. Replace compressor. 

5. Compressor will not start. 

1. Disconnect switch open. 
2. Blown fuse or fuse at disconnect switch. 
3. Thermostat set too high. 
4. Selector switch in "Off" position. 
5. Contactor and/or relay coils burned out. 
6. Loose or open electrical connection in either 

the control or power circuit. 

1. Close the disconnect switch. 
2. Check  the cause of  failure and replace the fuse. 
3. Adjust to lower temperature. 
4. Turn selector switch knob to "Cool" position. 
5. Replace contactor and/or relay. 
6. Inspect  and secure all electrical connections. 

Summary of Contents for DZ11TA Series

Page 1: ...tion damage or installation of incorrectly shipped units CODES REGULATIONS This product is designed and manufactured to comply with na tional codes Installation in accordance with such codes and or prevailing local codes regulations is the responsibility of the in staller The manufacturer assumes no responsibility for equip ment installed in violation of any codes or regulations Rated per formance...

Page 2: ...s preferred When possible mini mize the amount of bends and turns ROOFTOP INSTALLATIONS If it is necessary to install this unit on a roof structure ensure the roof structure can support the weight and that proper consider ation is given to the weather tight integrity of the roof Since the unit can vibrate during operation sound vibration transmission should be considered when installing the unit V...

Page 3: ... tubing clean and dry prior to and during installation Tubing should always be cut square keeping ends round and free from burrs Clean the tubing to prevent contamination Do NOT let refrigerant lines come in direct contact with plumbing ductwork floor joists wall studs floors and walls When running refrigerant lines through a foundation or wall openings should allow for sound and vibration absorbi...

Page 4: ...iers which are continually wet when the unit is operating NOTE Be careful not to kink or dent refrigerant lines Kinked or dented lines will cause poor performance or compressor damage Do NOT make final refrigerant line connection until plugs are removed from refrigerant tubing NOTE Before brazing verify indoor piston size by checking the piston kit chart packaged with indoor unit LEAK TESTING NITR...

Page 5: ...fficient to carry the Minimum Circuit Ampacity MCA listed on the serial plate The supply voltage can be unbalanced phase to phase within 2 The following formula can be used to determine the percent age of voltage unbalance for your unit Percentage Voltage Unbalance 100 x Max Voltage Deviation From Average Voltage Average Voltage Example L1 L2 220V L2 L3 216V Average Voltage 220 216 213 3 649 3 Max...

Page 6: ...y reduced compared to marked values To correct disconnect power and switch any two leads at the unit contactor and re observe HIGH VOLTAGE CONNECTIONS Route power supply and ground wires through the high voltage port and terminate in accordance with the wiring diagram pro vided inside the control panel cover LOW VOLTAGE CONNECTIONS Condensing unit control wiring requires a five conductor low volt ...

Page 7: ...rature 5 Using an additional electronic thermometer measure the ambient 6 Adjust the charge until the hot gas temperature equals 105º F ambient or 5º F Remove charge to increase the tem perature NOTE When adjusting the charge allow the compressor to operate for about 10 minutes before taking readings NOTE Subsequent opening and replace of the cap will require only 1 2 to 1 hex flat See the table b...

Page 8: ...t of equipment 1 1 x temp rise In other cases measurement of external static pressure is helpful For details see the Installation Instructions for your indoor unit TROUBLE SHOOTING ANALYSIS TABLE COMPLAINT PROBABLE CAUSE REMEDY 1 High Head Pressure 1 Excessive charge of refrigerant in system 2 Inadequate supply of air across the condenser coil 3 Non condensate gases in the system 1 Purge or pump d...

Page 9: ...low 375 425 CFM ton will cause excessive discharge pressures that may cause the high pres sure switch to function Low Return Air Temperatures Return ductwork temperatures that are less than 60 F will cause low discharge pressure low suction pressure and excessive de frost cycling Undercharging An undercharged system will cause low discharge pressure low suction pressure and an accumulation of fros...

Page 10: ...10 THIS PAGE LEFT INTENTIONALLY BLANK ...

Page 11: ...ER MOTOR RELAY CS COMPRESSOR SOLENOID HPS HIGH PRESSURE SWITCH CHS CRANKCASE HEATER SWITCH SSHR SECOND STAGE HEAT RELAY CONTROLS SHOWN WITH THERMOSTAT IN OFF POSITION WIRING CODE FACTORY WIRING HIGH VOLTAGE LOW VOLTAGE OPTIONAL HIGH VOLTAGE FIELD WIRING HIGH VOLTAGE LOW VOLTAGE LVJB CONTROL BO X BK BR PU BK DFT YL PK LPS DFT W O RV DC RVC BK BK CH BK W2 RD YL C T1 L1 T2 L2 T3 L3 YL RD FC PU BR PU ...

Page 12: ...12 Our continuing commitment to quality products may mean a change in specifications without notice 2018 5151 San Felipe St Suite 500 Houston TX 77056 www daikinac com ...

Reviews: