background image

SERVICING

53 

L

INE  VOLTAGE  NOW  PRESENT

WARNING

These tests must be completed within a given time frame due 

to the operation of the ignition control.  
1.  Check for 120 volts from Line 1 (Hot) to Line 2 (Neutral) 

at the ignition control. No voltage, check the door switch 

connections and wire harness for continuity.

2.  Check for 24 volts from W to C terminal on the ignition 

control. No voltage. Check transformer, room thermostat, 

and wiring. 

 

If you have 24 volts coming off the transformer but receive 

approximately 13 volts on the terminal board between (C) 

and (R), check for blown fuse.

3.  Check for 120 volts to the induced draft blower by mea

-

suring voltage between Pin 1 (on the 2-pin connector) and 

Line (Neutral) on the control board. No voltage, replace 

ignition control.

4.  If voltage is present in Steps 1 through 3 and the induced 

draft blower is operating, check for 120 volts to the ignitor 

during the preheat cycle. Measure voltage between Pin 2 

(on the 2-pin connector) and Line (Neutral) on the control 

board. No voltage, check pressure switch.

5.  After the ignitor warm-up time, begin checking for 24 volts 

to the gas valve. Voltage will be present for seven seconds 

only if proof of flame has been established.            

S-314  CHECKING FLAME SENSOR

A flame sensing device is used in conjunction with the ignition 

control module to prove combustion. If proof of flame is not 

present the control will de-energize the gas valve and "retry" 

for ignition or lockout. 

WARNING

HIGH

 

VOLTAGE

D

ISCONNECT 

ALL

 POWER BEFORE SERVICING OR

INSTALLING THIS UNIT. 

M

ULTIPLE POWER SOURCES MAY

BE PRESENT. 

F

AILURE TO DO SO MAY CAUSE PROPERTY

DAMAGE, PERSONAL INJURY OR DEATH.

1.  Connect a micro-amp meter in series with this wire and 

the sensor terminal.

2.  Be sure the positive side of the meter is to  the sensor  

(depending on the model) and the negative side of the 

meter is to sensor terminal.

L

INE  VOLTAGE  NOW  PRESENT

WARNING

3.  Place the unit into a heating cycle.

4.  As  soon  as  flame  is  established  a  micro-amp  reading 

should be evident once proof of flame (micro-amp reading) 

is established, the hot surface ignitor will be de-energized.

5.  The Integrated Ignition controls will have 1 to 4 micro-

amps. If the micro-amp reading is less than the minimum 

specified, check for high resistance wiring connections, 

sensor to burner gap, dirty flame sensor, or poor grounding.

6.  If  absolutely  no  reading,  check  for  continuity  on  all 

components and if good - replace ignition control module.

NOTE: 

Contaminated  fuel  or  combustion  air  can  create  a 

nearly  invisible  coating  on  the  flame  sensor. This  coating 

works as an insulator causing a loss in the flame sense sig

-

nal. If this situation occurs the flame sensor must be cleaned 

with steel wool. 

ERROR CODE

Red LED Flash

Error / Condition

Flash Codes stored in memory (auto-erased after 14 days)

1

System Lockout (Retries Exceeded)

2

Pressure Switch stuck Closed

3

Pressure Switch stuck Open

4

Open High Temperature Limit Switch

5

Flame Sensed>4.25 Seconds with Gas Valve De-Energized

6

Open High Temperature Limit Switch

8

Igniter Relay Fault

10

Open Fuse

11

Igniter Open

12

Inducer Relay Error

Flash Codes NOT stored in memory

7

Low Flame Sense Signal

9

Twinning Fault

OFF

Control Failure / No Power / Internal Fault / IRQ Loss. Gas Heat-

ing Lockout (Gas valve energized when it should be 

 

de-energized) Or Gas Valve De-energized when it should 

 

be Energized

Rapid Flash Reverse Polarity

Continuous On Normal Operation

Summary of Contents for DM92SE

Page 1: ...gov ONLY PERSONNEL THAT HAVE BEEN TRAINED TO INSTALL ADJUST SERVICE OR REPAIR HEREINAFTER SERVICE THE EQUIPMENT SPECIFIED IN THIS MANUAL SHOULD SERVICE THE EQUIPMENT THE MANUFACTURER WILL NOT BE RESP...

Page 2: ...S AND SERVICERS RECOGNIZE SAFETY SYMBOLS WORDS AND LABELS Table of Contents IMPORTANT INFORMATION 2 4 PRODUCT IDENTIFICATION 5 8 INSTALLATION CONSIDERATIONS 9 27 SYSTEM OPERATION 28 ACCESSORIES 29 31...

Page 3: ...ing permanent brain damage or death Advertencia especial para la instalaci n de calentadores manejadoras de aire en reas cerradas como estacionamientos cuartos de servicio B10259 216 El mon xido de ca...

Page 4: ...manuel D Donotusethisapplianceifanyparthasbeenunderwater position 6 Attendrecinq 5 minutespourlaisser echapper tout le WHAT TO DO IF YOU SMELL GAS 5 Push thegascontrol leverto Position OFF ARRET sett...

Page 5: ...Revision D Daikin A InitialRelease B 1st Revision Configuration M Upflow Horizontal Major Revision C Downflow Horizontal A InitialRelease B 1st Revision Nox AFUE N Natural Gas 97 97 AFUE X Low NOx 80...

Page 6: ...2SE0805CN DM92SE1004CN DM92SE1005CN DM92SE1205DN Daikin Brand 92 Single Stage furnace 34 5 tall Upflow Horizontal Installation 1 stage gas valve induced draft Multi speed ECM motor 120 volt nitride ho...

Page 7: ...Cleaner A high efficiency air filtration device designed to remove dirt dust pollen and other microscopic particles from the air passing through it Flexible perfor mance range up to 2 000 CFM capacity...

Page 8: ...rminate outside the structure This kit is NOT intended for use with single pipe indirect vent installations 0170K00001S N A Side Wall Only Concentric Vent Kit This kit is to be used with 2 vent system...

Page 9: ...ols to their containers before touching any ungrounded object Product Application This product is designed for use as a residential home gas furnace It is not designed or certified for use in mobile h...

Page 10: ...ion Air Pipe Termination Locations section in this manual or the installation in structions to determine if the piping system from furnace to termination can be accomplished within the guidelines give...

Page 11: ...om of the confined space In a typical construction the clearance between the door and door frame is usually adequate to satisfy this ventilation requirement Furnace Suspension If suspending the furnac...

Page 12: ...CGA B149 Installation Codes Sections 7 2 7 3 or 7 4 or applicable provisions of the local building codes for determining the combustion air requirements for the appliances Most homes will require out...

Page 13: ...d by one or more openings in doors or floors having a total minimum free area of 2 in 2 1000 Btu hr 4400 mm2 kW of total input rating of all appliances 9 3 3 Outdoor Combustion Air Outdoor combustion...

Page 14: ...stalla tions shall provide an adequate supply of combustion ventilation and dilution air and shall be approved by the authority having jurisdiction 9 3 6 Mechanical CombustionAir Supply Where all comb...

Page 15: ...s recommended Failure to provide proper condensate drainage can result in property damage Leveling Leveling ensures proper condensate drainage from the heat exchanger and induced draft blower For prop...

Page 16: ...combustion to the outdoors as the vent pipe or flue pipe The pipe that supplies air for combustion to the furnace will be referred to as the intake pipe or combustion air pipe A condensing gas furnace...

Page 17: ...ING THE RUBBER ELBOW IS NOT DESIGNED TO SUPPORAT A LOAD WHEN THE RUBBER ELBOW IS MOUNTED EXTERNALLY TO THE FURNACE CABINET EXTREME CARE MUST BE TAKEN TO ADEQUATELY SUPPORT FIELD SUPPLIED VENT FLUE PIP...

Page 18: ...stacles between pipes etc ROOF LINE COMBUSTION AIR INTAKE OPTIONAL Not required for single pipe installation TEE OPTIONAL 96 MAX 3 MIN 12 MIN HEIGHT DIFFERENCE BETWEEN INTAKE AND VENT 12 MIN TO ROOF O...

Page 19: ...t through the side of the building or run vertically and exit through the roof of the building The pipes may be run through an existing unused chimney however they must extend a minimum of 12 inches a...

Page 20: ...rmination kit The termination kit must terminate outside the structure and must be installed per the instructions outlined below for vertical or horizontal termination Vertical termination is preferre...

Page 21: ...horizontally with the left side down there are two options for connecting the vent pipe to the furnace Option 1 Venting may be connected to the furnace vent pipe fitting on the original top now the en...

Page 22: ...gas and the altitude Refer to the National Fuel Gas Code NFPA 54 ANSI Z223 1 and information provided by the gas supplier to determine the proper orifice size A different pressure switch may be requi...

Page 23: ...may damage the gas valve and cause subsequent overfiring resulting in heat exchanger failure Disconnect this unit and shutoff valve from the gas supply piping system before pressure testing the suppl...

Page 24: ...RS AND LIQUIDS IN THE VICINITY OF THIS OR ANY OTHER APPLIANCE WHAT TO DO IF YOU SMELL GAS DO NOT TRY TO LIGHT ANY APPLIANCE DO NOT TOUCH ANY ELECTRICAL SWITCH DO NOT USE ANY PHONE IN YOUR BUILDING IMM...

Page 25: ...the unit rating plate An electrical disconnect must be provided at the furnace location NOTE Line polarity must be observed when making field connections WARNING IN 90 FURNACE UPRIGHT UPFLOW INSTALLAT...

Page 26: ...n the unit and the utility room wall so the blower will not interfere with combustion air or draft The room closet or alcove must not be used as a return air chamber When the furnace is used in connec...

Page 27: ...warm up period deliv ering gas to burners to establish flame 6 The control checks for a signal from the flame sensor within seven 4 seconds after the gas valve is ener gized Gas will only continue to...

Page 28: ...uced draft blower is off it waits until the fault is corrected The diagnostic light code for this problem is 2 flashes The probable cause is either a faulty pressure switch or wiring 4 Pressure Switch...

Page 29: ...nsult the Installation Instructions IO 635 SIDE WALL VENT KIT 0170K00001S This side wall only vent kit 0170K00001S is to be used with 2 vent systems This kit is NOT intended for use with single pipe i...

Page 30: ...ive a brief view of the kit and its application See the section in this manual under Vent Flue and Combustion Air Pipe Terminations for more information or consult the Installation and Operating Instr...

Page 31: ...ACCESSORIES 31 DAIKIN DM92SE Model Furnace Accessories...

Page 32: ...FURN C P3 2 P1 1 P3 8 REVERSING VALVE OUTPUT BREAK FOR ODT FURNACE DEMAND OUTPUT P1 3 R 24VAC K4 HP CALL FOR FURNACE DURING DEFROST W2 Y2 STAT Y2 FURN CALL FOR COMPRESSOR P2 7 P3 6 VDC Y2 O REVERSING...

Page 33: ...gle Stage Furnaces Wire as above for GMH AMH GDH AND GCH hybrid furnaces For installations made prior to 2 1 11 TW I L HER O AT CONN C ON 1 H 1 2ND H 2 1 C L Y1 2ND C L Y2 N U R C N C T nning Contro B...

Page 34: ...is wiring diagram is for reference only Not all wiring is as shown above Refer to the appropriate wiring diagram for the unit being serviced For use only with 80 or 90 Single Stage Furnaces NOTE Not c...

Page 35: ...TER VOLT OHM METER These then should be wired to the furnace accordingly CHECKING FOR PHASING PRIMARY TO SECONDARY OF UNMARKED TRANSFORMERS If meter reads approximately 96 volts the primary to seconda...

Page 36: ...9 947 45 20 40 80 160 400 20 45 90 180 360 900 46 78 157 391 21 43 86 171 343 857 47 19 38 76 153 383 22 41 82 164 327 818 48 75 150 375 23 39 78 157 313 783 49 147 367 24 37 75 150 300 750 50 18 36 7...

Page 37: ...n Control Test Control S 313 Gas Valve or Gas Supply Shut Off Turn Valves to On Position S 317 Faulty Induced Draft Blower Test Induced Draft Motor S 303 Faulty Blower Motor PSC Test Blower Motor PSC...

Page 38: ...ated control module diagnostic LED is flashing ONE 1 flash 1 FLASH Furnace lockout due to an excessive number of ignition retries 3 total 1 Failure to establish flame Cause may be no gas to burners fr...

Page 39: ...blower with correct replacement part Induced draft blower and circulation blower runs continuously No furnace operation Integrated control module diagnostic LED is flashing FIVE 5 flashes 5 FLASHES F...

Page 40: ...l module diagnostic LED is flashing ELEVEN 11 flashes 11 FLASHES Igniter Open Improperly connected igniter Bad igniter Poor unit ground Poor burner ground Check and correct wiring from integrated cont...

Page 41: ...d low firing rates If converted to L P gas check size of all orifices 2 Remove Draft Inducer Check the integrity of the gasket between the inducer and the collector box cover any air leak here will ha...

Page 42: ...ECKING PRIMARY LIMIT CONTROL 45 S 302 CHECKING FLAME ROLLOUT CONTROL 46 S 303 INDUCED DRAFT BLOWER MOTOR 47 S 304 CHECKING GAS VALVE REDUNDANT 47 S 305 CHECKING MAIN BURNERS 48 S 306 CHECKING ORIFICES...

Page 43: ...nsulation of the same gauge or its equivalent CHECKING THERMOSTAT WIRING AND ANTICIPATOR S 3A THERMOSTAT AND WIRING DISCONNECT ALL POWER BEFORE SERVICING WARNING 1 Remove the blower compartment door t...

Page 44: ...check and or replacement of transformer and check and or repair of control circuit reinstall blower compartment door 8 Turn on electrical power and verify proper unit operation S 16A CHECKING AIR CIRC...

Page 45: ...OFF ON ON OFF ON Motor Speed HEAT W T1 T2 T3 T4 DEFAULT SETTING FAN MOTOR SPEED DIP SWITCH SETTING S2 3 S2 4 3 4 3 4 3 4 3 4 Position OFF OFF ON OFF OFF ON ON ON Motor Speed FAN G T1 T2 T4 T1 T2 DEFA...

Page 46: ...y adjusting the circulator blower speed Increase blower speed to reduce temperature rise Decrease blower speed to increase temperature rise Refer to Circulator Blower Speed section in the Product Desi...

Page 47: ...AVOID POSSIBLE FIRE ONLY RESET THE AUXILIARY LIMIT CONTROL ONCE IF IT SHOULD OPEN A SECOND TIME A QUALIFIED SERVICER MUST DETERMINE WHY THE AUXILIARY LIMIT OPENED BEFORE RESETTING AGAIN To aid in ide...

Page 48: ...TO DO SO MAY CAUSE PROPERTY DAMAGE PERSONAL INJURY OR DEATH 1 Remove burner compartment door to gain access to the induced draft blower motor 2 Disconnect the motor wire leads from its connection poin...

Page 49: ...icult to adjust the flame properly WARNING DISCONNECT ALL GAS AND ELECTRICAL POWER SUPPLY 1 Check orifice visually for distortion and or burrs 2 Check orifice size with orifice sizing drills 3 If resi...

Page 50: ...NT UNRELIABLE OPERATION OR EQUIPMENT DAMAGE THE GAS MANIFOLD PRESSURE MUST BE AS SPECIFIED ON THE UNIT RATING PLATE ONLY MINOR ADJUSTMENTS SHOULD BE MADE BY ADJUSTING THE GAS VALVE PRESSURE REGULATOR...

Page 51: ...system j Remove the manometer hose from the hose barb fitting or outlet pressure boss k Remove the 1 8 NPT hose barb fitting from the outlet pressure tap Replace the outlet pressure boss plug and sea...

Page 52: ...altitude kit for your furnace S 312 CHECKING FOR DELAYED IGNITION Delayed ignition is a delay in lighting a combustible mixture of gas and air which has accumulated in the combustion chamber Furnace d...

Page 53: ...AMAGE PERSONAL INJURY OR DEATH 1 Connect a micro amp meter in series with this wire and the sensor terminal 2 Be sure the positive side of the meter is to the sensor depending on the model and the neg...

Page 54: ...erformance Maintenance Improper filter maintenance is the most common cause of inadequate heating or cooling performance Filters should be cleaned permanent or replaced disposable every two months or...

Page 55: ...e essential in solving abnormal problems however in many instances they may be rented from local sources Proper equipment promotes faster more efficient service and accurate repairs resulting in fewer...

Page 56: ...U per cubic foot gas and with proper inlet pressures and correct piping size full capacity will be obtained With propane gas no unit gas valve regulator is used however the second stage supply line pr...

Page 57: ...Y LIMIT AUTO RESET BL PU MANUAL RESET ROLLOUT LIMIT CONTROL S RD OR PK BK WH WH BLOWER INDUCED DRAFT AUXILIARY LIMIT CONTROLS C FS LIMIT CONTROLS AUXILIARY IGNITER HOT SURFACE IND IGN BLWR CIRCULATOR...

Reviews: