
INSTALLATION CONSIDERATIONS
10
National Fire Protection Association
1 Batterymarch Park
Quincy, MA 02169-7471
CSA International
8501 East Pleasant Valley
Cleveland, OH 44131
A copy of the CAN/CGA B149 Installation Codes can be
obtained from:
CSA International
178 Rexdale Boulevard
Etobicoke, Ontario, Canada M9W, 1R3
The rated heating capacity of the furnace should be greater
than or equal to the total heat loss of the area to be heated. The
total heat loss should be calculated by an approved method
or in accordance with “ASHRAE Guide” or “Manual J-Load
Calculations” published by the Air Conditioning Contractors
of America.
Location Requirements and Considerations
WARNING
T
O PREVENT POSSIBLE EQUIPMENT DAMAGE, PROPERTY DAMAGE, PERSONAL
INJURY OR DEATH, THE FOLLOWING BULLET POINTS MUST BE OBSERVED
WHEN INSTALLING THE UNIT.
Follow the instructions listed below when selecting a furnace
location. Refer also to the guidelines provided in the
Combus-
tion and Ventilation Air Requirements
section in this manual
or the installation instructions for details.
•
Centrally locate the furnace with respect to the proposed
or existing air distribution system.
•
Ensure the temperature of the return air entering the
furnace is between 55°F and 100°F when the furnace
is heating.
•
If the furnace is installed in an application where the
typical operating sound level of a furnace is deemed
objectionable, an optional sound reduction kit is avail
-
able. Consult your local distributor for more details.
•
Provide provisions for venting combustion products
outdoors through a proper venting system. Special
consideration should be given to vent/flue pipe routing
and combustion air intake pipe when applicable.
90% Furnaces:
Refer to
the
Vent/Flue Pipe and Com-
bustion Air Pipe -Termination Locations
section in this
manual or the installation instructions for appropriate
termination locations. Also for 90% furnaces, refer to the
Vent/Flue Pipe and Combustion Air Pipe -Termination
Locations
section in this manual or the installation in-
structions to determine if the piping system from furnace
to termination can be accomplished within the guidelines
given
. NOTE:
The length of flue and/or combustion
air piping can be a limiting factor in the location of the
furnace.
•
Locate the 90% furnace so that the condensate can be
piped at a downward slope away from the furnace to
the drain. Do not locate the furnace or its condensate
drainage system in any area subject to below freezing
temperatures without proper freeze protection. Refer
to
the
Condensate Drain Lines and Trap
section in this
manual or the installation instructions for further details.
•
Set the 90% furnace on a level floor to enable proper
condensate drainage. If the floor becomes wet or damp
at times, place the furnace above the floor on a concrete
base sized approximately 1-1/2" larger than the base
of the furnace. Refer to the
Horizontal Applications and
Considerations
section in this manual or the installation
instructions for leveling of horizontal furnaces.
•
Ensure upflow or horizontal furnaces are not installed
directly on carpeting, or any other combustible material.
The only combustible material allowed is wood.
•
A special accessory subbase must be used for upright
counterflow unit installations over any combustible
material (including wood). Refer to subbase instructions
for installation details. (
NOTE:
A subbase will not be
required if an air conditioning coil is located beneath
the furnace between the supply air opening and the
combustible floor.
•
Exposure to contaminated combustion air will result in
safety and performance-related problems. Do not install
the furnace where the combustion air is exposed to the
following substances:
chlorinated waxes or cleaners
chlorine-based swimming pool chemicals
water softening chemicals
deicing salts or chemicals
carbon tetrachloride
halogen type refrigerants
cleaning solutions (such as perchloroethylene)
printing inks
paint removers
varnishes
hydrochloric acid
cements and glues
antistatic fabric softeners for clothes dryers
and masonry acid wash
ing materials