5.9 Accessory Items 

 

5.9.1 Filter 

 

Air handling units can be supplied with flat 

filters and/or bag filters. There are 2 types 
of  filter  frame,  sliding  frame  or  universal 

clip.  Insert  the  filter  into  the  frame  by 
following airflow arrow indicated.  

 

5.9.2 Mixing Box 

 

Fresh  air  and  return  air  dampers  can  be 
linked  together  and  drives  by  the  same 

actuator if both are same size. Care must 
be  taken  to  ensure  dampers  are  in  open 

position  while  the  fan  is  running  whether 
they are integral with central plant control 
or  associated  ductwork  under  negative 

pressure condition. 

 

5.9.3 Variable Pitch Pulley 

 

Modifications  of  the  pulley  diameter  must 
be  done  when  stationery  by  moving  the 

adjustable  flange.  Each  complete  rotation 
of  one  of  the  two  disks  results  in  a 

variation  of  the  pulley  diameter.  (See 
Table  2  &  Figure  27)  When  the  required 
diameter  is  obtained,  adjustable  flange  is 

locked  by  tighten  the  four  clamp  screws. 
To  get  the  same  diameter  in  the  two 

grooves  of  pulleys,  screw  the  two  mobile 
flanges  on  the  central  flange.  Then 

unscrew  the  two  mobile  flanges  by  the 
same  number  of  turnings  to  get  the 
required diameter. 

Note that the belt  centre line shifts when 
diameter changes. Driven pulley may need 
realignment. 

 

 

Figure 27 – Variable Pitch Pulley 

 

5.9.4 Heat Wheel 

 

Follow 

Heat 

Wheel 

manufacturer 

recommendations  for  proper  installation 

procedure. Apply silicone to air leak spots 
at baffle plates. (If applicable) 

Refer  to  assembly  of  heat  wheel  baffle 
plates  at  Appendix  9.1  when  the  heat 
wheel section not able to ship in complete 

build up. 

 

5.9.5 Heat Pipe 

 

After  installation  of  Heat  Pipe  with  refers 
to  manufacturer  recommendations,  site 

installer to install heat pipe baffle plates at 
site,  this  is  to  avoid  air  bypass  heat 
pipe/main  cooling  coil  from  top  and  side. 

(If applicable) 
 

5.9.6 Electric Heater 

 

Power  supply  to  electric  heater  and 
electric  connection  is  in  accordance  with 

wiring  diagram  in  terminal  box  of  electric 
heater.  

The  rated  voltage  of  electric  heater  is 
240V, single phase. 

 

IMPORTANT 

IT  IS  ADVICED  TO  INTERLOCK 

ELECTRICAL 

HEATER 

WITH 

BLOWER  TO  ENSURE  HEATER  IS 

NOT  ENERGIZED  WHEN  THERE  IS 

NO AIR FLOW. 

 

 
 
 

Summary of Contents for DM AHU

Page 1: ...LATION OPERATION MAINTENANCE VER O AHU01 DEC20 15 The design and construction are subject to change without any notice for future improvement MODELS DM AHU DS AHU AHUR VRV AHU Double Skin Modular Air...

Page 2: ...rtificate which is determined by International National or Local Codes and Regulation Place of service should be equipped with the necessary protective equipment which provide safe maintenance 1 4 Uni...

Page 3: ...truck 4 Storage For external storage prior to installation the units must be protected from dust rain constant sun exposure and rodents Although covered in shrink wrapped plastic sheeting this is not...

Page 4: ...carefully assembled to desired unit arrangement The air handling units are design to use section joint brackets to combine two sections Section joints for cabinet and base frame are shown in Figure 5...

Page 5: ...on joint WARNING CABINET SECTION JOINTS ARE NOT INTENDED FOR LIFTING PURPOSE AND PULLING CABINET FROM A DISTANCE TO JOIN SECTION TOGETHER When the cabinets are penta post to penta post arrangement or...

Page 6: ...hipped out from factory See Figure 15 Figure 14 Restrained Spring Isolator Figure 15 Removing of U Shaped Plate 5 5 Arrangement VRV AHU Control box and expansion valve kit are installed on the air han...

Page 7: ...joints or flexible fittings are to be provided in all piping connections particularly those adjacent to heating source to absorb expansion and contraction strains Failure to comply will result in dama...

Page 8: ...valve and not to a common header When two or more coils are connected to a common suction line never place the bulb on the common line Thermostatic expansion valve is to be equipped with external equa...

Page 9: ...r control refer to the VFD manual for wire size and requirements Figure 22 3 phases motor connection diagram 5 7 2 Motor Cabling Motor wiring must go downward from motor terminal box to prevent conden...

Page 10: ...he diameter of smaller pulley Table 2 Adjusted Pitch Diameter Model VPT100Z1 VPT120A1 A2 VPT139A1 A2 VPT156A1 A2 VPT177A1 A2 VPT178B2 Max Pitch mm 96 114 4 133 4 150 4 171 4 171 Min Pitch mm 82 9 96 1...

Page 11: ...ee Table 2 Figure 27 When the required diameter is obtained adjustable flange is locked by tighten the four clamp screws To get the same diameter in the two grooves of pulleys screw the two mobile fla...

Page 12: ...out Notes 1 Elbows should not be closer than 2 1 2 times the Duct Equivalent Diameter Refer to Formula 1 2 Dampers should be placed at least fan diameters downstream of the fan discharge Formula 1 Duc...

Page 13: ...ther For DX coils it is advisable that the refrigerant is to be pumped into the condenser If this is not possible refrigerant shall be purged out WARNING DO NOT HEAT ANY PART ON DX COIL IF REFRIGERANT...

Page 14: ...20mm 6 1 5 Coils Check the pipe work to coil is correctly connected and the fins are free from foreign matter or damage Check that the condensate drain is trap Ensure good sealing of silicon around th...

Page 15: ...or cap screw are in secure position CAUTION HIGH AIR TEMPERATURE IN FAN SECTION CAN CAUSE MOTOR OVERHEAT AND DAMAGE ON DRAW THROUGH AIR HANDLERS ADJUST THE DISCHARGE AIR TEMPERATURE OF THE HEATING SE...

Page 16: ...ling heating efficiency Dry cleaning is done by using a powerful vacuum cleaner on the dust accumulated side If coil is very dirty coils need to be removed for wet cleaning by trained personnel Ensure...

Page 17: ...IR VELOCITY SHOULD NOT BE LOWER THAN 2 0 m s 7 7 Heat Wheel Heat Pipe The unit should be maintained in line with the manufacturer recommendation Please refer installation and maintenance manual for de...

Page 18: ...not evenly supported on foundation j Fan assembly s tolerance is out of range a Consult manufacturer b Remove transport bracket c Check pulley alignment d Re tension belts e Replace vibration isolato...

Page 19: ...he heat wheel baffle top 8 Assembled back the remaining panels 9 2 AHU Water Quality Water quality requirements Water softening treatment must be given in advance to prevent scaling in the heat exchan...

Page 20: ...Yes No 5 Correct incoming voltage that supplied to motor L1 L2 __________ L2 L3 __________ L3 L1 __________ 6 Rotate fan wheel whether it can rotate freely and without abnormal noise Answer Yes No 7 A...

Page 21: ...Are the AHU sections joined with section joint properly Answer Yes No 4 Are the joining between AHU sections sealed properly Answer Yes No Start Up Checking 1 Is fan rotated in correct direction Answe...

Reviews: