IM
1133-C
DIII-NET COMMUNICATION GATEWAY
38
www.DaikinApplied.com
Appendix B
Configurable Parameters
Table 4 defines the different parameters that are available in the D3 Set Up menu. The default values and acceptable ranges of
values are also included.
Table 2 DIII Set-Up Menu
Menu Item
Description
Default
Range
ItouchVer
Sets the Version of Intelligent Touch
Controller software
std
‘Std’ / ‘USw/Stp’ / ‘USw/oStp’
Unit D3 Addr
Particular address for unit
N/A
1-00 - 8-15
Set D3 Addr
Saves particular DIII address
No
Yes / No (reverts back to no)
Temp Display
Selects which temperature to display
DAT
None, DAT, Space, RAT, OAT
This is a list of the menu items in the DIII Status Menu on the MicroTech III controller. Also listed is a description of the item,
its default value, range of values or enumerations, if it can be read or written to, and which controller can change the value of the
parameter. Most of the DIII Status Menu items read in values from the Intelligent Touch Controller and display them on the
MicroTech III controller. Not all menu items will always be shown on the MicroTech III controller. There are items that will not
show unless other parameters are set to a specific value. Refer to the OM 920 for more information.
Table 3 DIII Status Menu
Menu Items
Description
Default
Range
R / W
D3 Com Sts
Displays status of D3 Gateway
OK
OK, Error
Read
D3 Addr Err
Displays address error
OK
OK, Error
Read
D3 On/Off
Displays D3 on or off
On
On, Off
Read
D3 Mode
Displays D3 mode
Auto
Auto, Cooling, Heating, Fan
Read
D3 Clg Spt
Displays cooling set point
N/A
0 - 100°F
Read
D3 Htg Spt
Displays heating set point
N/A
0 - 120°F
Read
D3 SAF Spd
Displays fan speed parameter
N/A
Low, Med, High
Read
D3 Min Load
Displays max load to enable economizer
20%
0 - 100%
Read
D3 Max Load
Displays min load to enable economizer
50%
0 - 100%
Read
D3 Eco Ena
Displays if Economizer is enabled
N/A
(Disabled, Enabled)
Read
D3 SWVersion
Displays software version
N/A
N/A
Read
OAAdd1-16
Displays valid Air-Net address
N/A
0 - 16
Read
OAAdd17-32
Displays valid Air-Net address
N/A
17 - 32
Read
OAAdd33-49
Displays valid Air-Net address
N/A
33 - 49
Read
OAAdd49-64
Displays valid Air-Net address
N/A
49 - 64
Read
SelectOAAddr
Selects OA unit address to displays setup for
N/A
0 - 64
R / W
CurrOAAddr
Displays current OA address selected
N/A
0 - 64
Read