IM
1133-C
DIII-NET COMMUNICATION GATEWAY
33
www.DaikinApplied.com
Figure 51, Adjusting Fan Speed from the iTouch Manager
Advanced Settings
The Detailed Setup screen allows multiple changes to be made to a unit at once. As well as containing standard controls such as
On/Off and Setpoints, this screen also has several advanced settings.
Main Tab
– Unit Settings
1.
Access the Indoor Devices list. See section “Turning a Unit On and Off” steps 1 and 2.
2.
Select the unit to be modified and press “Settings” at the bottom of the sidebar. See Figure 52.
Figure 52, Accessing Detailed Settings
3.
Changes can be made to the unit in the Detailed Settings screen. See Figure 53. Adjustable parameters include:
a.
On/Off – Turn unit on or off
b.
Operation Mode – Has no effect on Daikin AHUs.
c.
Setback Setpoint – Sets unoccupied setpoints for certain types of units. Has no effect on Daikin AHUs.
d.
Cool Setpoint – modifies active setpoint. See section “
Adjusting Setpoints
”
e.
Heat Setpoint – modifies active setpoint. See section “
Adjusting Setpoints
”
f.
Min. Cool/Heat SP Differential – Sets the minimum difference between Cool and Heat Setpoints. Because
both parameters control the active setpoint on an AHU, this differential should be set to zero.
g.
Setpoint Tracking Mode – determines whether the iTM tracks changes to the setpoints.
4.
Select the checkbox next to an item to change its value.
Checkboxes must remain checked to apply changes.
Selected Unit
Change Fan Speed
Selected Unit
Detailed/Advanced
Settings