background image

10

Cleaning

Due to the fact that drain pans in any air conditioning 

unit will have some moisture in them, algae and fungus 

will grow due to airborne bacteria and spores. Periodic 

cleaning is necessary to prevent this build-up from plugging 

the drain.

STARTUP, ADJUSTMENTS, AND CHECKS

WARNING

HIGH VOLTAGE!

To avoid personal injury or death 

due to electrical shock, bond the 

frame of this unit to the building 

electrical ground by use of the 

grounding terminal provided or 

other acceptable means. Disconnect 

all power before servicing or 

installing this unit.

CAUTION

To prevent property damage or personal 

injury, do not start the unit until all necessary 

pre-checks and tests have been performed.

WARNING

MOVING MACHINERY HAZARD!

To prevent possible personal injury or death, 

disconnect power to the unit and padlock in the 

“OFF” position before servicing fans.

Pre-Startup Instructions

On new installations, or if a major component has been 

replaced, the operation of the unit must be checked.

Check unit operation as outlined in the following 

instructions. If any sparking, odors, or unusual sounds 

are encountered, shut off electrical power and recheck for 

wiring errors, or obstructions in or near the blower motors. 

Duct covers must be removed before operating unit.

The Startup, Adjustments, and Checks procedure provides 

a step-by-step sequence which, if followed, will assure the 

proper startup of the equipment in the minimum amount of 

time. Air balancing of duct system is not considered part 

of this procedure. However, it is an important phase of any 

air conditioning system startup and should be performed 

upon completion of the Startup, Adjustments, and Checks 

procedure. The Startup, Adjustments, and Checks 

procedure at outside ambients below 55°F should be 

limited to a readiness check of the refrigeration system with 

the required final check and calibration left to be completed 

when the outside ambient rises above 55°F.

Temporary Heating Or Cooling

If the unit is to be used for temporary heating or cooling, a 

“Startup, Adjustments, and Checks” must first be performed 

in accordance with this manual. Damage or repairs due to 

failure to comply with these requirements are not covered 

under the warranty. 

After 

the machines are used for 

temporary heating or cooling, inspect the coils, fans, and 

motors for unacceptable levels of construction dust and dirt 

and install new filters.

Contractor Responsibility

The installing contractor must be certain that:

• 

All supply and return air ductwork is in place, properly 

sealed, and corresponds with installation instructions.

All thermostats 

and sensors

 are mounted and wired in 

accordance with installation instructions.

• 

All electric power, all gas, hot water or steam line 

connections, and the condensate drain installation 

have been made to each unit on the job. These 

main supply lines must be functional and capable of 

operating all units simultaneously.

• 

All filters are in place.

Roof Curb Installation Check

Inspect the roof curb for correct installation. The unit and curb 

assembly should be level. Inspect the flashing of the roof 

mounting curb to the roof, especially at the corners, for good 

workmanship. Also check for leaks around gaskets. Note any 

deficiencies in a separate report and forward to the contractor. 

Obstructions, Fan Clearance and Wiring

Remove any extraneous construction and shipping materials 

that may be found during this procedure. Rotate all fans 

manually to check for proper clearances and that they rotate 

freely. Check for bolts and screws that may have jarred loose 

during shipment to the job site.  Re-tighten if necessary. Re-

tighten all electrical connectio

ns.

Field Duct Connections

Verify that all duct connections are tight and that there is no 

air bypass between supply and return.

Filter Section Check

Remove filter section access panels and check that filters 

are properly installed. Note airflow arrows on filter frames.

Pre-startup Precautions

It is important to your safety that the unit has been properly 

grounded during installation. Check ground lug connection in 

main control box for tightness prior to closing circuit breaker 

or disconnect switch. Verify that supply voltage on line side of 

disconnect agrees with voltage on unit identification plate and 

is within the utilization voltage range as indicated in Appendix 

B Electrical Data.

System Voltage - 

That nominal voltage value assigned to a 

circuit or system for the purpose of designating its voltage class.

Nameplate Voltage - 

That voltage assigned to a piece of 

equipment for the purpose of designating its voltage class 

and for the purpose of defining the minimum and maximum 

voltage at which the equipment will operate.

Summary of Contents for DBC0363B Series

Page 1: ...t specified in this manual only licensed personnel should servise the equipment Improper installation adjustment servicing or repair of the equipment specified in this manual or attempting to install...

Page 2: ...ce CAUTION Sheet metal parts screws clips and similar items inherently have sharp edges and it is necessary that the installer and service personnel exercise caution WARNING Do not connect to or use a...

Page 3: ...ld also where applicable follow information presented in accepted industry guides such as the ASHRAE Handbooks The manufacturer assumes no responsibility for equipment installed in violation of any co...

Page 4: ...Installations Only To avoid possible property damage or personal injury the roof must have sufficient structural strength to carry the weight of the unit s and snow or water loads as required by local...

Page 5: ...ntenance and proper unit operation A clearance of 48 is recommended on all sides of the unit to facilitate possible parts replacement to allow service access and to insure proper ventilation and conde...

Page 6: ...to protect unit base frame from fork lift damage Removal is accomplished by extracting the sheet metal retainers and pulling the struts through the base of the unit Refer to rigging label on the unit...

Page 7: ...MUM OVERCURRENT DEVICE SIZE SHOWN ON UNIT DATA PLATE All line voltage connections must be made through weatherproof fittings All exterior power supply and ground wiring must be in approved weatherproo...

Page 8: ...f unit due to operation on improper line voltage or with excessive phase unbalance constitutes product abuse and is not covered by the warranty It may cause severe damage to the unit s electrical comp...

Page 9: ...may be required before entering thermostat sub base NOTE Refer to unit wiring diagrams for thermostat or remote sensor connections CIRCULATING AIR AND FILTERS Ductwork The supply duct from the unit t...

Page 10: ...d for temporary heating or cooling inspect the coils fans and motors for unacceptable levels of construction dust and dirt and install new filters Contractor Responsibility The installing contractor m...

Page 11: ...it is best to have a variable pitched motor sheave for the purpose of airflow balancing but once the balance has been achieved fixed sheaves maintain alignment and minimize vibration more effectively...

Page 12: ...ck that the compressor is operating correctly The scroll compressors in these units MUST operate in the proper rotation To ensure the compressors are operating in the correct direction check the compr...

Page 13: ...e by redirecting refrigerant flow through the refrigerant circuit external to the compressor This is accomplished by the reversing valve Hot discharge vapor from the compressor is directed to the indo...

Page 14: ...ilters should be cleaned or replaced These few steps will help to keep the product up time to a maximum The Service section that follows should help in identifying problems if the unit does not operat...

Page 15: ...STATIC BELT DRIVE DOWNSHOT ESP In H2 O TURNS OPEN 0 1 2 3 4 5 CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP 0 7 1481 1020 0 57 0 8 1370 1020 0 53 0 9 1434 1080 0 62 1247 102...

Page 16: ...250 950 0 42 989 885 0 30 DBC036 C HIGH STATIC BELT DRIVE HORIZONTAL ESP In H2 O TURNS OPEN 0 1 2 3 4 5 CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP 0 8 1539 1020 0 59 0 9 1...

Page 17: ...FM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP 0 6 1996 1200 1 05 1872 1135 0 88 1741 1075 0 74 0 7 1922 1200 1 01 1790 1135 0 84 1650 1075 0 70 0 8 1985 1265 1 17 1845 1200 0 97 1703 1135...

Page 18: ...HIGH STATIC BELT DRIVE HORIZONTAL ESP In H2 O TURNS OPEN 0 1 2 3 4 5 CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP 0 6 1895 1075 0 81 0 7 1958 1135 0 93 1802 1075 0 76 0 8 18...

Page 19: ...BELT DRIVE DOWNSHOT ESP In H2 O TURNS OPEN 0 1 2 3 4 5 CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP 0 6 2237 1245 1 27 2072 1175 1 03 0 7 2333 1315 1 48 2164 1245 1 23 1990 1175 0 99 0...

Page 20: ...65 DBC060 C HIGH STATIC BELT DRIVE HORIZONTAL ESP In H2 O TURNS OPEN 0 1 2 3 4 5 CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP 0 6 2394 1245 1 37 2239 1175 1 12 0 7 2320 1245...

Page 21: ...175 1 05 1900 1110 0 86 DBC072 S HIGH STATIC BELT DRIVE DOWNSHOT ESP In H2 O TURNS OPEN 0 1 2 3 4 5 CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP 0 6 2630 1385 1 88 2492 1315...

Page 22: ...1110 0 84 DBC072 S HIGH STATIC BELT DRIVE HORIZONTAL ESP In H2 O TURNS OPEN 0 1 2 3 4 5 CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP 0 6 2655 1385 1 90 2520 1315 1 62 2369 1...

Page 23: ...5 0 26 DBH036 C HIGH STATIC BELT DRIVE DOWNSHOT ESP In H2 O TURNS OPEN 0 1 2 3 4 5 CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP 0 8 1587 1020 0 61 0 9 1456 1020 0 56 1 0 151...

Page 24: ...0 35 Note VL34 and AK61 pulleys used on standard static unit DBH036 C HIGH STATIC BELT DRIVE HORIZONTAL ESP In H2 O TURNS OPEN 0 1 2 3 4 5 CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP C...

Page 25: ...O TURNS OPEN 0 1 2 3 4 5 CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP 0 6 2003 1075 0 85 0 7 1898 1075 0 81 0 8 1936 1135 0 91 1788 1075 0 76 0 9 1979 1200 1 05 1833 1135 0...

Page 26: ...RNS OPEN 0 1 2 3 4 5 CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP 0 6 1885 1075 0 80 0 7 1955 1135 0 92 1791 1075 0 76 0 8 1865 1135 0 88 1691 1075 0 72 0 9 1948 1200 1 03 1...

Page 27: ...H2 O TURNS OPEN 0 1 2 3 4 5 CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP 0 6 2397 1310 1 53 2278 1245 1 31 2145 1180 1 10 2003 1115 0 92 0 7 2334 1310 1 48 2208 1245 1 26 2...

Page 28: ...TURNS OPEN 0 1 2 3 4 5 CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP 0 6 2421 1310 1 55 2297 1245 1 32 2161 1180 1 11 2016 1115 0 92 0 7 2357 1310 1 50 2227 1245 1 27 2083 11...

Page 29: ...7 4 17 4 25 25 9 6 8 7 27 0 26 1 35 35 1 7 1 5 19 1 18 9 25 25 9 6 8 7 1 7 1 5 28 7 27 6 35 35 EH B 3S05 3 76 5 00 10 4 12 0 17 4 19 3 25 25 9 6 8 7 29 3 30 2 35 35 1 7 1 5 19 4 21 2 25 25 9 6 8 7 1 7...

Page 30: ...30 9 6 8 7 30 8 29 9 40 40 1 7 1 5 22 9 22 7 30 30 9 6 8 7 1 7 1 5 32 5 31 4 40 40 EH B 3S05 3 76 5 00 10 4 12 0 21 2 21 2 30 30 9 6 8 7 30 8 30 2 40 40 1 7 1 5 22 9 22 7 30 30 9 6 8 7 1 7 1 5 32 5 3...

Page 31: ...7 1 5 55 0 62 0 60 70 9 6 8 7 1 7 1 5 67 0 72 9 70 80 EH B 3S20 15 0 19 9 41 5 47 9 57 9 65 8 60 70 9 6 8 7 69 9 76 7 70 80 1 7 1 5 60 0 67 7 60 70 9 6 8 7 1 7 1 5 72 0 78 6 80 80 DBC0484B 460 3 60 1...

Page 32: ...7B 575 3 60 1 4 36 33 1 0 25 0 55 Belt Drive Standard Static 1 5 2 3 8 3 15 3 5 11 8 15 0 6 8 9 15 3 5 0 6 12 4 15 EH B 7S05 5 4 81 8 89 15 3 5 13 3 15 0 6 9 64 15 3 5 0 6 14 15 EH B 7S10 10 9 62 14 9...

Page 33: ...76 5 00 10 4 12 0 25 1 25 1 40 40 9 6 8 7 34 7 33 8 50 45 1 7 1 5 26 8 26 6 40 40 9 6 8 7 1 7 1 5 36 4 35 3 50 45 EH B 3S10 7 51 10 0 20 8 24 1 30 1 34 1 40 40 9 6 8 7 42 1 44 9 50 45 1 7 1 5 32 2 35...

Page 34: ...5 55 0 62 0 60 70 9 6 8 7 1 7 1 5 67 0 72 9 70 80 EH B 3S20 15 0 19 9 41 5 47 9 57 9 65 8 60 70 9 6 8 7 69 9 76 7 70 80 1 7 1 5 60 0 67 7 60 70 9 6 8 7 1 7 1 5 72 0 78 6 80 80 DBC0604B 460 3 60 1 7 0...

Page 35: ...575 3 60 1 5 13 39 5 1 0 33 0 67 Belt Drive Standard Static 1 1 2 8 28 15 3 5 11 8 15 0 6 8 88 15 3 5 0 6 12 4 15 EH B 7S05 5 4 81 8 28 15 3 5 11 9 15 0 6 8 88 15 3 5 0 6 12 6 15 EH B 7S10 10 9 62 13...

Page 36: ...1 5 31 7 31 5 45 45 9 6 8 7 1 7 1 5 41 3 40 2 50 50 EH B 3S10 7 51 10 0 20 8 24 1 33 6 37 6 45 45 9 6 8 7 45 6 48 4 50 50 1 7 1 5 35 7 39 4 45 45 9 6 8 7 1 7 1 5 47 7 50 3 50 60 EH B 3S15 11 3 15 0 3...

Page 37: ...6 8 7 71 4 78 2 80 80 1 7 1 5 61 5 69 2 70 70 9 6 8 7 1 7 1 5 73 5 80 1 80 90 EH B 3S30 21 6 28 8 60 0 69 3 82 6 94 1 90 100 9 6 8 7 94 6 105 100 110 1 7 1 5 84 7 96 0 90 100 9 6 8 7 1 7 1 5 96 7 107...

Page 38: ...0 DBC0727S 575 3 60 1 6 35 55 3 1 0 33 0 67 2 speed Belt Drive High Static 2 2 4 11 15 3 5 14 5 20 0 6 11 6 15 3 5 0 6 15 1 20 EH B 7S05 5 4 81 11 15 3 5 14 5 20 0 6 11 6 15 3 5 0 6 15 1 20 EH B 7S10...

Page 39: ...45 EH B 3S10 7 51 10 0 20 8 24 1 43 5 47 5 45 50 9 6 8 7 53 1 56 2 60 60 1 7 1 5 45 2 49 0 50 50 9 6 8 7 1 7 1 5 54 8 57 7 60 60 EH B 3S15 11 3 15 0 31 3 36 1 56 5 62 5 60 70 9 6 8 7 66 1 71 2 70 80...

Page 40: ...H0367B 575 3 60 1 3 78 36 5 1 0 17 0 39 Belt Drive Standard Static 1 5 2 3 7 42 15 3 5 10 9 15 0 6 8 02 15 3 5 0 6 11 5 15 EH B 7S05 5 4 81 13 4 15 3 5 16 9 20 0 6 14 15 3 5 0 6 17 5 20 EH B 7S10 10 9...

Page 41: ...37 5 43 3 68 1 75 4 70 80 9 6 8 7 77 7 84 1 80 90 1 7 1 5 69 8 76 9 70 80 9 6 8 7 1 7 1 5 79 4 85 6 80 90 EH B 3S20 15 0 19 9 41 5 47 9 73 1 81 1 80 90 9 6 8 7 82 7 89 8 90 90 1 7 1 5 74 8 82 6 80 90...

Page 42: ...3 29 3 30 0 5 25 5 30 4 3 0 5 29 8 30 EH B 4S15 15 18 32 6 35 4 3 36 9 40 0 5 33 1 35 4 3 0 5 37 4 40 EH B 4S18 18 21 7 37 1 40 4 3 41 4 45 0 5 37 6 40 4 3 0 5 41 9 45 EH B 4S20 20 24 1 40 1 45 4 3 44...

Page 43: ...3 5 23 8 25 0 6 20 9 25 3 5 0 6 24 4 25 EH B 7S15 15 14 4 26 3 30 3 5 29 8 30 0 6 26 9 30 3 5 0 6 30 4 35 EH B 7S18 18 17 3 29 9 30 3 5 33 4 35 0 6 30 5 35 3 5 0 6 34 35 EH B 7S20 20 19 2 32 4 35 3 5...

Page 44: ...7 5 43 3 72 3 79 5 80 80 9 6 8 7 81 9 88 2 90 90 1 7 1 5 74 0 81 0 80 90 9 6 8 7 1 7 1 5 83 6 89 7 90 90 EH B 3S20 15 0 19 9 41 5 47 9 77 2 85 2 80 90 9 6 8 7 86 8 93 9 90 100 1 7 1 5 78 9 86 7 80 90...

Page 45: ...4 3 30 7 35 0 5 26 9 30 4 3 0 5 31 2 35 EH B 4S15 15 18 34 35 4 3 38 3 40 0 5 34 5 35 4 3 0 5 38 8 40 EH B 4S18 18 21 7 38 5 40 4 3 42 8 45 0 5 39 40 4 3 0 5 43 3 45 EH B 4S20 20 24 1 41 5 45 4 3 45...

Page 46: ...4 25 0 6 21 1 25 3 5 0 6 24 6 25 EH B 7S15 15 14 4 26 6 30 3 5 30 1 35 0 6 27 2 30 3 5 0 6 30 7 35 EH B 7S18 18 17 3 30 2 35 3 5 33 7 35 0 6 30 8 35 3 5 0 6 34 3 35 EH B 7S20 20 19 2 32 6 35 3 5 36 1...

Page 47: ...THRU THE BASE UTILITIES RETURN 11 X 25 SUPPLY 12 X 17 Horizontal Discharge Vertical Discharge NOTE Refer to IOD 7082 included in the literature pack for installing horizontal duct covers 48 5 16 74 A...

Page 48: ...975 X X X DBC048 1300 X X X X X DBC060 1625 X X X X X DBC072 1950 X X X X X X DBH036 975 X X X DBH048 1300 X X X X X DBH060 1625 X X X X X Note Adjust the pulley setting as needed to achieve the mini...

Page 49: ...NSOR PB POWER DISTRIBUTION BLOCK PLF FEMALE PLUG CONNECTOR PLM MALE PLUG CONNECTOR TB TERMINAL BLOCK TR TRANSFORMER REPLACEMENT WIRE MUST BE SAME SIZE AND TYPE OF INSULATION AS ORIGINAL AT LEAST 105 C...

Page 50: ...E PU BR BK PU BR BK RD OR BK RD OR BK RD YL L2 208 230 460 575V 3PH 60Hz FB1 F1 F1 F1 5 BK PU BK PLF PLM CM BK BK RD OR POWER AND CONTROLS WIRING DIAGRAM DBC036 060 3 PHASE 1 SPD BELT DRIVE 2 1 2 1 GR...

Page 51: ...P FUSE BLOCKS 1 2 3 ARE OPTIONAL IF OPTIONAL SAFETY EQUIPMENT SUCH AS A PHASE MONITOR FLOAT SWITCH OR SMOKE DETECTOR IS INSTALLED UNPLUG JUMPER PLUG AND PLUG IN SAFETY DEVICE IF MULTIPLE SAFETIES ARE...

Page 52: ...52...

Page 53: ...53...

Page 54: ...2020 19001 Kermier Rd Waller TX 77484 www daikincomfort com CUSTOMER FEEDBACK Daikin is very interested in all product comments Please fill out the feedback form on the following link https daikincomf...

Reviews: