2 Components
Service manual
25
ATXP20~3 FTXP20~7 ARXP20~3
RXP20~71L2V1B
Split Comfora R32
ESIE18-01 – 2019.02
a
b
c
a
Putty
b
Expansion valve pipe
c
Expansion valve body
a
b
a
Expansion valve pipe
b
Expansion valve body
INFORMATION
The expansion valve and motor can have a different
configuration / layout.
3
Cut the expansion valve pipes using a pipe cutter.
4
Remove the expansion valve body.
5
To install the expansion valve body, see
To install the expansion valve body
1
Install the expansion valve body in the correct location.
2
Wrap a wet rag around the expansion valve body and solder
the refrigerant pipes to the expansion valve body.
CAUTION
Overheating the valve will damage or destroy it.
a
b
c
a
Putty
b
Expansion valve pipe
c
Expansion valve body
a
b
a
Expansion valve pipe
b
Expansion valve body
INFORMATION
The expansion valve and motor can have a different
configuration / layout.
3
Reinstall the putty.
4
To install the expansion valve motor, see
.
5
Add refrigerant to the refrigerant circuit, see
.
About the installation of the expansion valve
motor
NOTICE
Select the correct type.
To install the expansion valve motor with clip
1
Install the expansion valve motor on the expansion valve body.
INFORMATION
The expansion valve motor is equipped with a pipe
retention clip. Install the pipe retention clip over the pipe to
lock the expansion valve motor.