![background image](http://html1.mh-extra.com/html/daikin/co2-conveni-pack/co2-conveni-pack_installer-and-user-reference-manual_3278134053.webp)
15
|
Unit installation
Installer and user reference guide
53
FXSN50~112A2VEB
CO₂ Conveni-Pack: indoor unit
4P602817-1A – 2020.05
▪
General guidelines
▪
Connecting the drain piping to the indoor unit
▪
Checking for water leaks
General guidelines
▪
Pipe length.
Keep drain piping as short as possible.
▪
Pipe size.
Keep the pipe size equal to or greater than that of the connecting pipe
(vinyl pipe of 25 mm nominal diameter and 32 mm outer diameter).
▪
Slope.
Make sure the drain piping slopes down (at least 1/100) to prevent air
from being trapped in the piping. Use hanging bars as shown.
1~1.5 m
a
a
Hanging bar
O
Allowed
X
Not allowed
▪
Rising piping
. If necessary to make the slope possible, you can install rising
piping.
-
Drain hose inclination: 0~75 mm to avoid stress on the piping and to avoid air
bubbles.
-
Rising piping: ≤300 mm from the unit, ≤625 mm perpendicular to the unit.
≤625
A
≤300
0~75
1000~1500
(mm)
b
a
b
a
d
d
c
A
In case of rear suction installation 231 mm
In case of installation with canvas duct (field supply) 350~530 mm
a
Metal clamp (accessory)
b
Drain hose (accessory)
c
Rising drain piping (vinyl pipe of 25 mm nominal diameter and 32 mm outer diameter) (field supply)
d
Hanging bars (field supply)
▪
Condensation.
Take measures against condensation. Insulate the complete drain
piping in the building.
▪
Combining drain pipes.
You can combine drain pipes. Make sure to use drain
pipes and T-joints with the correct gauge for the operating capacity of the units.
≥100
≤600
(mm)
a
a
T-joint