15
|
Unit installation
Installer and user reference guide
44
FXSN50~112A2VEB
CO₂ Conveni-Pack: indoor unit
4P602817-1A – 2020.05
≥
500
c
A
(mm)
b
a
A
Minimum distance to the floor
2.7 m
to avoid accidental touching
2.5 m
in case the fan is covered (e.g. false ceiling, grille, …)
a
Ceiling
b
Floor surface
c
Maintenance space
Service space and ceiling opening size
Make sure ceiling opening is big enough to ensure a sufficient clearance for
maintenance and service.
800
800
(mm)
a
b:
≥
500
a
A
B
C
≥
500
A
Side view: refrigerant piping, drain piping, control box
B
Side view: air inlet
C
Top view
a
Ceiling opening
Class 50:
700 mm
Class 71:
1000 mm
Class 112:
1400 mm
b
Service space
Installation options
A
c
a
b
≥1100
(mm)
B
a
b
≥1100
(mm)
c
d
e
g
f