Unit installation
Installer and user reference guide
51
FXSN50~112A2VEB
CO₂ Conveni-Pack: indoor unit
4P602817-1A – 2020.05
▪
Suspension bolts.
Use M10 suspension bolts for installation. Attach the hanger
bracket to the suspension bolt. Fix it securely using a nut and washer from the
upper and lower sides of the hanger bracket.
e:
630
e: A
(mm)
a
b
b
d
c
4×
f
a
Nut (field supply)
b
Washer (accessories)
c
Hanger bracket
d
Double nut (field supply)
e
Suspension bolt spacing
f
Suspension bolt
15‒3 Suspension bolt spacing (A)
Class
A (mm)
50
738
71
1038
112
1438
▪
Level.
Make sure the unit is level at all four corners using a level or a water-filled
vinyl tube.
b
a
a
Water level
b
Vinyl tube
NOTICE
Do NOT install the unit tilted.
Possible consequence:
If the unit is tilted against the
direction of the condensate flow (the drain piping side is raised), the float switch
might malfunction and cause water to drip.