![Daikin Clima-Flex CLIC STAND ALONE Series Installation, Operation And Maintenance Manual Download Page 43](http://html1.mh-extra.com/html/daikin/clima-flex-clic-stand-alone-series/clima-flex-clic-stand-alone-series_installation-operation-and-maintenance-manual_3311908043.webp)
iom-clicsa-cf-eng
www.clima-flex.com
43
Index
S
ize Acronym
DataType Min
Value
Max
Value R/W InitValue UoM Description
128
1
RevVlv_Circ2
BOOL
R
FALSE
RevVlv_Circ2 - Reversing valve for refr. circ.2 (0=Cooling,
1=Heating)
129
1
OilEquVlv_Circ2
BOOL
R
FALSE
Oil equalisation solenoid valve circ.2
130
1
HeatCool
BOOL
R
TRUE
HeatCool - Unit in cooling mode (0=Heating, 1=Cooling)
131
1
DfrRun_Circ1
BOOL
R
FALSE
Defrost is running on circ.1
132
1
DfrRun_Circ2
BOOL
R
FALSE
Defrost is running on circ.2
133
1
DfrFrcCompDfrPwr_Circ1 BOOL
R
FALSE
Force circ.1 comp. to defrost capacity
134
1
UnitOn
BOOL
R
FALSE
Unit ON/OFF status (0=OFF, 1=ON)
140
1
EVD_CanGo
BOOL
R
FALSE
Enable EVD EVO driver to control superheat
141
1
ManPmpReqCirc1
BOOL
R
FALSE
Request user pump activation by manual-compressor
control in circ.1
142
1
CompsManCirc1
BOOL
R
FALSE
Manual status of comp. in circ.1
143
1
FrcOn_Comp1Circ1_Oil-
Migr
BOOL
R
FALSE
Force ON comp.1 circ.1 to avoid oil migration
144
1
FrcOn_Comp2Circ1_Oil-
Migr
BOOL
R
FALSE
Force ON comp.2 circ.1 to avoid oil migration
145
1
FrcOn_Comp1Circ2_Oil-
Migr
BOOL
R
FALSE
Force ON comp.1 circ.2 to avoid oil migration
146
1
FrcOn_Comp2Circ2_Oil-
Migr
BOOL
R
FALSE
Force ON comp.2 circ.1 to avoid oil migration
148
1
UsrFlw_Absent
BOOL
R
FALSE
UsrFlw_Absent - User pump fl ow absent (0=Flow OK,
1=Flow absent)
149
1
En_DscgPPrb_Circ1
BOOL
R
FALSE
En_DscgTempPrb_Circ1 - Connected discharge temp. probe
for circ.1
150
1
En_DscgTempPrb_Circ1
BOOL
R
FALSE
En_DscgTempPrb_Circ1 - Connected discharge temp. probe
for circ.1
151
1
En_OvldComp1Circ1_Din BOOL
R
FALSE
Enable comp.1 circ.1 overload input
152
1
UnitCh
BOOL
R
FALSE
Unit is chiller
153
1
UnitHp
BOOL
R
FALSE
Unit is heat pump
154
1
SrcFan1Circ1Status
BOOL
R
FALSE
Source fan circ.1 status (0=OFF, 1=ON)
155
1
SrcFan1Circ2Status
BOOL
R
FALSE
Source fan circ.2 status (0=OFF, 1=ON)
156
1
RegTypPrb
BOOL
R
FALSE
Control probe (0=Return; 1=Delivery)
157
1
En_SuctPPrb_Circ1
BOOL
R
FALSE
En_SuctPPrb_Circ1 - Connected suction press. probe for circ.1
159
1
ACU_PANEL
BOOL
R
FALSE
ACU panel
160
1
En_Circ2
BOOL
R
FALSE
Enable circ.2
161
1
En_Comp2Circ1
BOOL
R
FALSE
Enable compr.2 circ.1
162
1
En_Comp2Circ2
BOOL
R
FALSE
Enable compr.2 circ.2
163
1
En_CompsOnOff Circ1
BOOL
R
FALSE
Enable comp. ON/OFF for circ.1
164
1
En_CompsOnOff Circ2
BOOL
R
FALSE
Enable comp. ON/OFF for circ.2
165
1
En_CondTempPrb_Circ1
BOOL
R
FALSE
Connected cond. temp. probe for circ.1
166
1
En_SuctTempPrb_Circ1
BOOL
R
FALSE
En_SuctTempPrb_Circ1 - Connected suction temp. probe
for circ.1
167
1
UsrHeater2
BOOL
R
FALSE
UsrHeater2 - User heater 2 status
168
1
Al_RegulationAlrms
BOOL
R
FALSE
Al_RegulationAlrms - Control alarms
169
1
Al_MiscAlrms
BOOL
R
FALSE
Al_MiscAlrms - Miscellaneous alarms
170
1
Al_SrsCirc1
BOOL
R
FALSE
Al_SrsCirc1 - Serious alarm circ.1
171
1
Al_SrsCirc2
BOOL
R
FALSE
Al_SrsCirc2 - Serious alarm circ.2
172
1
Al_SrsCircs
BOOL
R
FALSE
Al_SrsCircs - Serious alarm circ.1 and circ.2
173
1
RemCmdComp1Circ1
BOOL
R
FALSE
RemCmdComp1Circ1 - Remote comand comp.1 circ.1
174
1
RemCmdComp2Circ1
BOOL
R
FALSE
RemCmdComp2Circ1 - Remote comand comp.2 circ.1
175
1
RemCmdComp1Circ2
BOOL
R
FALSE
RemCmdComp1Circ2 - Remote comand comp.1 circ.2
176
1
RemCmdComp2Circ2
BOOL
R
FALSE
RemCmdComp2Circ2 - Remote comand comp.2 circ.2
178
1
En_RemCmdComp-
1Circ1_Din
BOOL
R
FALSE
Enable remote command comp.1 circ.1 input
179
1
En_RemCmdComp-
2Circ1_Din
BOOL
R
FALSE
Enable remote command comp.2 circ.1 input
180
1
En_UsrRetWTempPrb
BOOL
R
FALSE
En_UsrRetWTempPrb - Connected user return water temper-
ature probe
181
1
En_UsrDlvWTempPrb
BOOL
R
FALSE
En_UsrDlvWTempPrb - Connected user delivery water
temperature probe
183
1
AFreezeHeatUsr_Circ2
BOOL
R
FALSE
Circuit 2 user frost heater status
190
1
Active2ndSetPDin
BOOL
R
FALSE
Second set point input
191
1
CoolHeatDin
BOOL
R
FALSE
Cool/Heat input status (0=Cooling, 1=Heating)
192
1
HiP_Pstat_Circ1
BOOL
R
FALSE
High pressure switch on circ.1
193
1
OvldComp1Circ1
BOOL
R
FALSE
Comp.1 circ.1 overload
194
1
OvldComp2Circ1
BOOL
R
FALSE
Comp.2 circ.1 overload
195
1
RemAlrmDin
BOOL
R
FALSE
Remote alarm
196
1
RemOnOff Din
BOOL
R
FALSE
Remote unit ON/OFF command from digital input
(0= OFF, 1=ON)
198
1
UsrPmp1Ovld
BOOL
R
FALSE
User pump 1 overload input logic
199
1
UsrPmp2Ovld
BOOL
R
FALSE
User pump 2 overload input logic
200
1
UnitChOnly
BOOL
R
FALSE
Unit is chiller only
197
1
UnitWW
BOOL
R
FALSE
Unit is WW - FALSE: Unit is not WW, TRUE: Unit is WW
201
1
UnitChHp
BOOL
R
FALSE
Unit is Chiller/Heat pump with reversal of refrigeration cycle
205
1
UnitHpOnly
BOOL
R
FALSE
Unit is heat pump only
202
1
UnitChHp_NotAA
BOOL
R
FALSE
Unit is reverse-cycle but not AA
203
1
UnitChHp_WR
BOOL
R
FALSE
UnitChHp_WR - WW Chiller/Heat pump with reversal on
water circuit
206
1
Rev4WayValve_Circ2_Out-
STATUS
BOOL
R
FALSE
4WayValve reverse output command for circ 2
204
1
En_AIN_PwrReqPrb_Circ1 BOOL
R
FALSE
Connected analogue capacity request probe on circuit 1
207
1
A88
BOOL
R
FALSE
Circuit 1 - Source fan/pump alarm
209
1
LP_Pstat_Circ1
BOOL
R
FALSE
Low pressure switch on circ.1
210
1
A90
BOOL
R
FALSE
Unit - Power failure
Mapping Table