Mapping Table
Index
S
ize Acronym
DataType
Min
Value
Max
Value R/W
Init
Value UoM
Description
165
1
C015
UINT(5..999)
R/W 30
SECOND
C015 - Comp. load up time
166
1
C016
UINT(5..999)
R/W 10
SECOND
C016 - Comp. load down time
167
1
S021
UINT
R/W 0
HOUR
Time band hours
168
1
C020
UINT(5..999)
R/W 720
MINUTE
C020 - Circuit destabilisation max time with one or more
comp. OFF
169
1
C021
USINT(0..1)
R/W 0
C021 - Circuit capacity distribution (0=Equalised, 1=Grouped)
170
2
C022
REAL
R/W 0
DELTAKELVIN C022 - Discharge temp. probe off set for circ.1
172
2
C023
REAL
R/W 0
DELTAKELVIN C023 - Suction temp. probe off set for circ.1
174
2
C024
REAL
R/W 0
DELTAKELVIN C024 - Discharge temp. probe off set for circ.2
176
2
C025
REAL
R/W 0
DELTAKELVIN C025 - Suction temp. probe off set for circ.2
178
2
C026
REAL
R/W 0
BAR
C026 - Discharge press. probe off set for circ.1
180
2
C027
REAL
R/W 0
BAR
C027 - Suction press. probe off set for circ.1
182
2
C028
REAL
R/W 0
DELTAKELVIN C028 - Cond. temp. probe off set for circ.1
184
2
C029
REAL
R/W 0
DELTAKELVIN C029 - Evap. temp. probe off set for circ.1
186
2
C030
REAL
R/W 0
BAR
C030 - Discharge press. probe off set for circ.2
188
2
C031
REAL
R/W 0
BAR
C031 - Suction press. probe off set for circ.2
190
2
C032
REAL
R/W 0
DELTAKELVIN C032 - Cond. temp. probe off set for circ.2
192
2
C033
REAL
R/W 0
DELTAKELVIN C033 - Evap. temp. probe off set for circ.2
194
1
C037
USINT(0..1)
R/W 0
C037 - Suction press. probe type (0=0..5V, 1=4..20mA)
195
2
C038
REAL
R/W 0
BAR
C038 - Suction press. probe min value
197
2
C039
REAL
R/W 17.3
BAR
C039 - Suction press. probe max value
199
1
C040
USINT(0..1)
R/W 0
C040 - Discharge press. probe type (0=0..5V, 1=4..20mA)
200
2
C041
REAL
R/W 0
BAR
C041 - Discharge press. probe min value
202
2
C042
REAL
R/W 45
BAR
C042 - Discharge press. probe max value
204
1
C043
USINT(0..1)
R/W 1
C043 - Discharge temp. probe type (0=NTC, 1=NTC-HT)
206
1
C046
USINT(1..2)
R/W 1
C046 - Number of circuit in the unit
207
1
C047
USINT
2
3
R/W 2
C047 - Type of compressors used (0=1 ON/OFF, 1=2 ON/OFF,
2=BLDC, 3=BLDC + ON/OFF)
208
1
C048
USINT(1..2)
R/W 1
C048 - Compressor rotation type (1=FIFO, 2=TIME)
209
1
S000
UINT(0..999)
R/W 99
HOUR
S000 - Source pump 1 maintenance hour threshold (x100)
210
1
S002
UINT(0..2)
R/W 0
S002 - Source pump 1 manual mode (0=AUTO, 1=OFF, 2=ON)
212
1
S022
UINT
R/W 0
MINUTE
Time band minutes
213
1
S072
USINT(0..2)
R/W 0
S072 - Source pump activation (0=always on, 1=on with
compressor, 2=modulate on discharge)
214
1
S008
UINT(0..999)
R/W 99
HOUR
S008 - Source fan 1 circ.1 maintenance hour threshold (x100)
215
1
S010
USINT(0..2)
R/W 0
S010 - Source fan ON/OFFcirc.1 manual mode (0=AUTO,
1=OFF, 2=ON)
216
1
S011
USINT(0..101)
R/W 0
PERCENT
S011 - Source fan inverter circ.1 manual mode (0=AUTO,
1=0%, 2=1%, .. 101=100%)
217
1
S012
UINT(0..999)
R/W 0
HOUR
S012 - Source fan 1 circ.2 maintenance hour threshold (x100)
218
1
S014
USINT(0..2)
R/W 0
S014 - Source fan ON/OFF circ.2 manual mode (0=AUTO,
1=OFF, 2=ON)
219
1
S015
USINT(0..101)
R/W 0
PERCENT
S015 - Source fan inverter circ.2 manual mode (0=AUTO,
1=0%, 2=1%, .. 101=100%)
220
2
S016
REAL
R/W -5
CELSIUS
S016 - Source fan temp. threshold for cold climates
222
2
S017
REAL
R/W 10
PERCENT
S017 - Source fan min speed for cold climates
224
2
S018
REAL
R/W 50
PERCENT
S018 - Source fan speed up speed for cold climates
226
1
S019
UINT(0..300)
R/W 5
SECOND
S019 - Source fan speed up time for cold climates
229
2
Sprb
REAL
R
0
CELSIUS
SPrb - Source external air temperature
231
2
S025
REAL
R/W 45
CELSIUS
S025 - Low noise source fan set point in cooling
233
1
S026
UINT(0..999)
R/W 30
SECOND
S026 - Comp. ON delay after source pump ON
234
1
S027
UINT(0..999)
R/W 10
SECOND
S027 - Source pump delay OFF from comp. OFF
235
2
S028
REAL
R/W 30
CELSIUS
S028 - Source device cool set point
237
2
S029
REAL
R/W 10
CELSIUS
S029 - Source device heat set point
239
1
U081
USINT(0..7)
R/W 0
U081 - Pressure alarm reset confi guration
240
1
Hc71
USINT(0..3)
R/W 1
Hc71 - Analogue output 1 confi g. (0= Not used, 1=Source
pump - Source fan on/off , 2=Source fan mod, 3=Free cooling
valve)
241
2
S031
REAL
R/W 45
CELSIUS
S031 - Source fan cool set point at startup
243
1
S032
UINT(0..999)
R/W 240
SECOND
S032 - Source fan cool startup delay
244
1
Hc81
USINT(0..2)
R/W 1
Hc81 - Analogue output 1 secondary confi g. (0= Not used,
1=Source fan on/off , 2=Source fan mod)
245
1
Hc72
USINT(0..3)
R/W 1
Hc72 - Analogue output 2 confi g. (0= Not used, 1=Source pump -
Source fan on/off , 2=Source fan mod, 3=Free cooling valve)
246
2
S034
REAL
R/W 15
DELTAKELVIN S034 - Source device cool diff erential
248
2
S035
REAL
R/W 5
DELTAKELVIN S035 - Source device heat diff erential
250
2
S036
REAL
R/W 20
PERCENT
S036 - Source fan inverter min speed
252
2
S037
REAL
R/W 80
PERCENT
S037 - Source fan inverter max speed
254
2
S039
REAL
R/W -1
CELSIUS
S039 - Defrost start threshold
256
2
S040
REAL
R/W 1
CELSIUS
S040 - Defrost start threshold reset
258
1
S041
UINT(0..999)
R/W 30
MINUTE
S041 - Defrost start delay
259
2
S042
REAL
R/W 52
CELSIUS
S042 - Defrost end threshold
261
1
S044
UINT(0..999)
R/W 20
SECOND
S044 - Defrost begin delay before actuating the 4 way valve
262
1
S045
UINT(0..999)
R/W 30
SECOND
S045 - Defrost ending delay after actuating the 4 way valve
263
1
S046
UINT(0..99)
R/W 1
MINUTE
S046 - Defrost min duration
264
1
S047
UINT(0..99)
R/W 5
MINUTE
S047 - Defrost max duration
265
1
S048
UINT(0..999)
R/W 90
SECOND
S048 - Dripping duration
266
1
S049
UINT(0..999)
R/W 30
SECOND
S049 - Post dripping duration
267
1
S050
UINT(0..999)
R/W 20
MINUTE
S050 - Delay between defrosts
268
1
C049
UINT(0..999)
R/W 90
SECOND
C049 - Low pressure alarm start delay
269
1
C050
UINT(0..999)
R/W 15
SECOND
C050 - Low pressure alarm run delay
270
1
F024
USINT
R/W 0
F024 - Heater 1 manual mode (0=AUTO, 1=OFF, 2=ON)
271
1
F025
USINT
R/W 0
F025 - Heater 2 manual mode (0=AUTO, 1=OFF, 2=ON)
272
1
S053
USINT(0..2)
R/W 0
S053 - Defrost synchronisation type (0=Independent,
1=Separate, 2=Simultaneous)
274
2
S054
REAL
R/W 3
BAR
S054 - Delta press. to reverse the 4 way valve