S
ize Acronym
DataType
Min
Value
Max
Value R/W
Init
Value UoM
Description
758
1
Hc43
USINT
R/W 0
Hc43 - Analogue input 3 confi g. on Secondary board (0= Not
used, 1= Source water delivery temp., 2= Outside temp., 3=
Discharge temp., 4= Condensing temp., 5= Suction temp., 6=
Evaporation temp., 7=Common delivery temp., 8= Delivery
water evap.2 temp.)
759
1
Hc44
USINT
R/W 0
Hc44 - Analogue input 4 confi g. on Secondary board (0= Not used,
1= Source water delivery temp., 2= Outside temp., 3= Discharge
temp., 4= Condensing. temp., 5= Suction temp., 6= Evaporation
temp., 7= Condensing press., 8= Evaporating press., 9= Common
delivery temp., 10= Delivery water evap.2 temp.)
760
1
Hc45
USINT
R/W 0
Hc45 - Analogue input 5 confi g. on Secondary board (0= Not used,
1= Source water delivery temp., 2= Outside temp., 3= Discharge
temp., 4= Condensing. temp., 5= Suction temp., 6= Evaporation
temp., 7= Condensing press., 8= Evaporating press., 9= Common
delivery temp., 10= Delivery water evap.2 temp.)
761
1
Hc47
USINT
R/W 0
Hc47 - Analogue input 7 confi g. on Secondary board (0= Not
used, 1= Source water delivery temp., 2= Outside temp., 3=
Discharge temp., 4= Condensing temp., 5= Suction temp., 6=
Evaporation temp., 7=Common delivery temp., 8= Delivery
water evap.2 temp.)
762
1
AI_CfgLim-
Max_Grp2_Slv
USINT
R/W 10
AI_CfgLimMax_Grp2 - Lim max probe group 2 secondary
763
1
AI_CfgLim-
Max_Grp1_Slv
USINT
R/W 8
AI_CfgLimMax_Grp1 - Lim max probe group 1 secondary
764
1
UnitTyp_Lim-
Max
USINT
R/W 4
UnitTyp_LimMax - Lim max unit type
765
2
U084
REAL
R/W 23
CELSIUS
U084 - Automatic changever threshold (type 1) (°C)
767
2
SEtU
REAL
R/W 23
CELSIUS
SEtU - Automatic changeover set point (type 2,3) (°C)
769
1
U088
USINT(0..2)
R/W 0
U088 - Frost heater position
770
2
F026
REAL
R/W -40
CELSIUS
F026 - Compressor cut-off by outside temperature
772
2
U085
REAL
R/W 2
DELTAKEL-
VIN
U085 - Automatic changeover deadband (°C)
774
2
U086
REAL
R/W 5
CELSIUS
U086 - Automatic changeover set point low limit (°C)
776
2
U087
REAL
R/W 20
CELSIUS
U087 - Automatic changeover set point high limit (°C)
818
2
U090
REAL
R/W 0
PERCENT
U090 - Analogue capacity request off set
820
2
U091
REAL
R/W 0
PERCENT
U091 - Analogue capacity request min value
822
2
U092
REAL
R/W 100
PERCENT
U092 - Analogue capacity request max value
817
1
U089
USINT(0..2)
R/W 0
U089 - Analogue capacity request input type (0=0-5V, 1=0-
10V, 2=4-20mA)
788
1
Hc90
USINT
0
8
R/W 0
HC90 - Display value selection - Large area
789
1
Hc91
USINT
0
8
R/W 0
Hc91 - Display value selection - Small area
Input Register
Index
S
ize Acronym
DataType
Min
Value
Max
Value R/W
Init
Value UoM
Description
0
2
HuP1
UDINT
R
0
HOUR
HuP1 - User pump 1 operating hours
2
2
HuP2
UDINT
R
0
HOUR
HuP2 - User pump 2 operating hours
4
2
H1C1
UDINT
R
0
HOUR
H1C1 - Comp.1 circ.1 operating hours
6
2
H1C2
UDINT
R
0
HOUR
H1C2 - Comp.2 circ.1 operating hours
8
2
H2C1
UDINT
R
0
HOUR
H2C1 - Comp.1 circ.2 operating hours
10
2
H2C2
UDINT
R
0
HOUR
H2C2 - Comp.2 circ.2 operating hours
12
2
dSt1
REAL
R
0
CELSIUS
dSt1 - Discharge temp. probe on circ.1
14
2
Sct1
REAL
R
0
CELSIUS
Sct1 - Suction temp. on circ.1
16
2
dSt2
REAL
R
0
CELSIUS
dSt2- Discharge temp. probe on circ.2
18
2
Sct2
REAL
R
0
CELSIUS
Sct2 - Suction temp. on circ.2
20
2
dSP1
REAL
R
0
BAR
dSP1 - Discharge press. probe on circ.1
22
2
ScP1
REAL
R
0
BAR
ScP1 - Suction press. on circ.1
24
2
Cnd1
REAL
R
0
CELSIUS
Cnd1 - Cond. temp. probe (or press. probe converted
value) on circ.1
26
2
EuP1
REAL
R
0
CELSIUS
EuP1 - Evap. temp. probe (or press. probe converted
value) on circ.1
28
2
dSP2
REAL
R
0
BAR
dSP2 - Discharge press. probe on circ.2
30
2
ScP2
REAL
R
0
BAR
ScP2 - Suction press. on circ.2
32
2
Cnd2
REAL
R
0
CELSIUS
Cnd2 - Cond. temp. probe (or press. probe converted
value) on circ.2
34
2
EuP2
REAL
R
0
CELSIUS
EuP2 - Evap. temp. probe (or press. probe converted
value) on circ.2
36
2
HSP1
UDINT
R
0
HOUR
HSP1 - Source pump 1 operating hours
38
1
C045
UINT
R
0
C045 - Refrigerant type (3=R407C, 4=R410a, 6=R290,
10=R744, 22=R32)
39
1
UnitCompTyp_Lim-
Max
USINT
R
0
UnitCompTyp_LimMax - Limit max of UnitCompTyp
variable
40
2
HFn1
UDINT
R
0
HOUR
HFn1 - Source fan 1 circ.1 operating hours
42
2
HFn2
UDINT
R
0
HOUR
HFn2 - Source fan 1 circ.2 operating hours
46
2
SEtA
REAL
R
0
CELSIUS
SEtA - Actual set point used by temp. control
48
2
SSH1
REAL
R
0
DELTAKELVIN SSH1 - Suction superheat on circ.1
50
1
Opn1
UINT
R
0
PERCENT
Opn1 - EEV position on circ.1
51
2
SSH2
REAL
R
0
DELTAKELVIN SSH2 - Suction superheat on circ.2
53
1
Opn2
UINT
R
0
PERCENT
Opn2 - EEV position on circ.2
54
2
rUSr
REAL
R
0
CELSIUS
rUSr - Return water temp. from user
56
2
dUSr
REAL
R
0
CELSIUS
dUSr - Delivery water temperature to user
Mapping Table