Mapping Table
Index
S
ize Acronym
Data
Type
Min
Value
Max
Value R/W
Init
Value UoM Description
0
1
U001
BOOL
R/W FALSE
U001 - User pump 1 reset hour counters
1
1
U004
BOOL
R/W FALSE
U004 - User pump 2 reset hour counters
2
1
U010
BOOL
R/W FALSE
U010 - Enable set point compensation (0=Disabled, 1=Enabled)
3
1
U017
BOOL
R/W FALSE
U017 - Enable scheduler (0=Disabled, 1=Enabled)
4
1
U022
BOOL
R/W FALSE
U022 - Type of scheduling (0=Switch OFF, 1=Change set point)
5
1
U034
BOOL
R/W FALSE
U034 - Cool/heat changeover type (0=keypad, 1=DIn)
6
1
U036
BOOL
R/W FALSE
U036 - Startup control probe (0=Return, 1=Delivery)
7
1
U038
BOOL
R/W TRUE
U038 - Run control probe (0=Return, 1=Delivery)
8
1
U057
BOOL
R/W FALSE
U057 - Remote alarm input logic (0=N.C., 1=N.O.)
9
1
U058
BOOL
R/W TRUE
U058 - Cool/Heat input logic (0=N.O., 1=N.C.)
10
1
U059
BOOL
R/W TRUE
U059 - Remote unit ON/OFF input logic (0=N.O., 1=N.C.)
11
1
U060
BOOL
R/W FALSE
U060 - User pump fl ow input logic (0=N.C., 1=N.O.)
12
1
U061
BOOL
R/W FALSE
U061 - User pump overload input logic (0=N.C., 1=N.O.)
13
1
U062
BOOL
R/W TRUE
U062 - 2nd set point input logic (0=N.O., 1=N.C.)
14
1
U063
BOOL
R/W FALSE
U063 - User pump output logic (0=N.O., 1=N.C.)
15
1
U064
BOOL
R/W FALSE
U064 - Global alarm relay output logic (0=N.C., 1=N.O.)
16
1
U065
BOOL
R/W FALSE
U065 - Free-Cooling valve output logic (0=N.O., 1=N.C.)
17
1
U066
BOOL
R/W FALSE
U066 - Frost heater output logic (0=N.O., 1=N.C.)
18
1
U067
BOOL
R/W FALSE
U067 - Alarm relay confi guration (0=Control alarms, 1=All alarms)
19
1
U068
BOOL
R/W FALSE
U068 - Enable Free-Cooling (0=Disabled, 1=Enabled)
20
1
E000
BOOL
R/W FALSE
E000 - ExV circ.1 enable manual mode
21
1
E002
BOOL
R/W FALSE
E002 - ExV circ.2 enable manual mode
22
1
Hd06
BOOL
R/W FALSE
Hd06 - Enable capacity request from BMS (0=Disabled, 1=Enabled)
23
1
C001
BOOL
R/W FALSE
C001 - Comp.1 circ.1 reset hour counters
24
1
C004
BOOL
R/W FALSE
C004 - Comp.2 circ.1 reset hour counters
25
1
C007
BOOL
R/W FALSE
C007 - Comp.1 circ.2 reset hour counters
26
1
C010
BOOL
R/W FALSE
C010 - Comp.2 circ.2 reset hour counters
27
1
C034
BOOL
R/W FALSE
C034 - High press. switch input logic (0=N.C., 1=N.O.)
28
1
C035
BOOL
R/W FALSE
C035 - Comp. overload input logic (0=N.C., 1=N.O.)
29
1
C036
BOOL
R/W FALSE
C036 - Comp. output logic (0=N.O., 1=N.C.)
30
1
C044
BOOL
R/W FALSE
C044 - Enable circuit destabilisation (0=Disabled, 1=Enabled)
31
1
S001
BOOL
R/W FALSE
S001 - Source pump 1 reset hour counters
33
1
S009
BOOL
R/W FALSE
S009 - Source fan 1 circ.1 reset hour counters
34
1
S013
BOOL
R/W FALSE
S013 - Source fan 1 circ.2 reset hour counters
35
1
S020
BOOL
R/W FALSE
S020 - Enable low noise (0=Disabled, 1=Enabled)
37
1
S043
BOOL
R/W FALSE
S043 - Enable sliding defrost (0=Disabled, 1=Enabled)
38
1
S055
BOOL
R/W FALSE
S055 - Comp. behavior in post-defrost phase
(0=Comp. is OFF, 1=Comp. is switched ON)
39
1
S061
BOOL
R/W FALSE
S061 - Source fan output logic (0=N.O., 1=N.C.)
40
1
S062
BOOL
R/W FALSE
S062 - Source pump output logic (0=N.O., 1=N.C.)
41
1
S063
BOOL
R/W FALSE
S063 - Reverse valve output logic (0=N.O., 1=N.C.)
42
1
S064
BOOL
R/W FALSE
S064 - Source fl ow type (0=Independent, 1=Common)
44
1
S065
BOOL
R/W FALSE
S065 - Source fan type (0=Inverter, 1=ON/OFF)
45
1
rStr
BOOL
R/W FALSE
rStr - Restore application to Carel settings (0=Disabled, 1=Enabled)
46
1
S068
BOOL
R/W FALSE
S068 - Source type (0=Air, 1=Water)
47
1
UoM
BOOL
R/W FALSE
UoM - Unit of measure used for Display 2-Row and BMS,
not for Applica (0=°C/bar, 1=°F/PSI)
48
1
Hd07
BOOL
R/W FALSE
Hd07 - BMS port database type (0= 32bit, 1= 16bit)
49
1
F027
BOOL
R/W FALSE
F027 - Compressor with capacity control
50
1
Hc13
BOOL
R/W TRUE
Hc13 - Enable buzzer (0=Disabled, 1=Enabled)
52
1
Ha02
BOOL
R/W FALSE
Ha02 - Set controller internal clock (0=No set, 1=Set)
53
1
Hd03
BOOL
R/W TRUE
#N/D
54
1
UnSt
BOOL
R/W FALSE
UnSt - Unit ON/OFF command from keypad (0=OFF 1=ON)
55
1
ModE
BOOL
R/W FALSE
ModE - Cool/Heat mode from keypad (0=Cool, 1=Heat)
56
1
RES
BOOL
R/W FALSE
RES - Reset active alarms from BMS net (0=NO, 1=Reset)
57
1
DevRotReq_
Comp1Circ1
BOOL
R/W
Request comp.1 circ.1 by DeviceRotation
Coil Status