20
English
9. INITIAL SETTING
9-1
Settings in the field
Follow the instructions below to set the DIP switches as necessary.
WARNING
Electric shock hazard! Before performing work, be sure to disconnect any power source connected
to the unit.
Procedure
1. Disconnect the power source.
2. Set the DIP switches (DS1, DS2) for the corresponding branch ports based on the following table.
3. Once work is complete, be sure to close the cover on the control box.
ON
OFF
ON
OFF
1
A1P
A4P
2 3 4
1 2
DS1
DS2
3 4
A B C D
M N O P
..................
..........
.......... ..........
A
B
C
D
M
N
O
P
Piping branch port number
Terminal No. to which to
connect transmission
wiring
DIP switch
<Setting>
1. Setting for branch ports to which no indoor unit is connected
Setting
Setting for branch ports to which no indoor unit is connected
(Example 1)
(Example 1)
When not connecting the
indoor unit to the A and B
branch circuits
ON
OFF 1 2
DS1 (A1P)
3 4
DIP switch setting
ON (Not connected)
OFF (Factory default)
DIP switch No.
DS1
(A1P)
DS1
(A2P)
DS1
(A3P)
DS1
(A4P)
1
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4
BS4Q14AV1
Target branch port
Unit A
Unit B
Unit C
Unit D
BS6Q14AV1
Unit E
Unit F
BS8Q14AV1
Unit G
Unit H
BS10Q14AV1
Unit I
Unit J
BS12Q14AV1
Unit K
Unit L
BS16Q14AV1
Unit M
Unit N
Unit O
Unit P
01_EN_3P194121-8U.indd 20
2/21/2014 3:31:16 PM