Daikin BRC7E61W Operation Manuals Download Page 23

OH08-1

Remote Controller (Wireless Type)

Control Systems

69

2

(Example)
If the time to clean air filter is set to “Filter Contamination-Heavy”, set Mode No. to “10”, FIRST CODE NO. 
to “0”, and SECOND CODE NO. to “02”.

NOTE

z

The SECOND CODE NO. is factory set to “01”. However, for the following cases it is set to “02”.

z

Air Flow Direction Range Setting

Do not use any settings not listed in the table.
For group control with a wireless remote controller, initial settings for all the indoor units of the group are 
equal. (For group control, refer to the installation manual attached to the indoor unit for group control.)

„

Test Operation

z

Perform test operation according to the instructions in the installation manual attached to the indoor 
unit.

z

After refrigerant piping, drain piping, and electric wiring, operate according to the table to protect the 
unit.

[PRECAUTIONS]

1. Refer to malfunction diagnosis in the installation manual attached to the indoor unit for split types.
2. Refer to malfunction diagnosis in the installation manual attached to the outdoor unit for VRV system 

types.

MODE 

NO.

FIRST 
CODE

NO.

DESCRIPTION OF SETTING

SECOND CODE NO.      NOTE)

01

02

03

10

0

Filter Contamination-
Heavy/Light (Setting for 
spacing time of display 
time to clean air filter) 
(Setting for when filter 
contamination is heavy, 
and spacing time of 
display time to clean air 
filter is to be halved)

Ultra-long-
life type

light

approx.

10,000 

hours

heavy

approx. 

5,000 hours

-

Long-life 
type

approx. 

2,500 hours

approx. 

1,250 hours

Standard 
type

approx. 

200 hours

approx. 

100 hours

1

Long-life filter type (Setting of filter 
sign indication time)
(Change setting when Ultra-long-life 
filter is installed)

Long-life filter

Ultra-long-life filter

-

3

Spacing time of display time to clean 
air filter count 
(Setting for when the filter sign is not 
to be displayed)

Display

Do not display

-

13

0

High ceiling setting (Setting for when 
installed in a ceiling higher than 2.7 m)

Normal

High Ceiling 1

High 

Ceiling 2

1

Selection of Air Flow Direction 
(Setting for when a blocking pad kit 
has been installed)

F

T

W

4

Air Flow Direction Range Setting

Upper

Normal

-

Order

Operation

(1)

Open gas side stop valve.

(2)

Open liquid side stop valve.

(3)

Electrify crank case heater for 6 hours. (Not necessary for cooling type units)

(4)

Set to cooling with the remote controller and push 

 button to start operation.

(5)

Push

button twice and operate in TEST OPERATION.

(6)

Push

button and confirm its operation.

(7)

Push

button and operate normally.

(8)

Confirm its function according to the operation manual.

ON/OFF

/TEST

SWING

/TEST

2

.3

  B

R

C

7

F

6

3

4

F

 / 

B

R

C

7

F

6

3

5

F

Summary of Contents for BRC7E61W

Page 1: ...low typ e is mou nted into th e ind oor u nit T h is u nit su p p orts th e th ree sp eed a irflow ra te c ontrol H H H L 2 3 2 F u n c tio n Sig na l rec eiv er u nit Insta lled typ e Sig na l rec e...

Page 2: ...D RAIN PIPING SID E RE CE IV E R INSTALLATION PROCE D U RE RE FRIG E RANT PIPING SID E RE CE IV E R D E TAIL W IRE LE SS RE MOTE CONTROLLE R K IT FOR E ACH D E CORATION PANE L RE MOTE CONTROLLE R D I...

Page 3: ...f th e Operating S ection 1 1 3 2 1 1 1 2 8 10 13 11 12 15 14 16 17 9 1 3 4 6 2 5 7 DOWN FAN UP ON OFF M H L C hr hr TEST MODE TIMER RESERVE CANCEL DOWN UP TEST SWING FAN TIME TEMP ON OFF M H L C hr h...

Page 4: ...AMMING TIMER BU TTON Use this button for programming START and or STOP time Operates with the front cover of the remote controller opened 12 TIMER MODE START STOP BU TTON Refer to page 57 13 TIMER RES...

Page 5: ...mote controller Direct the transmitting part of the remote controller to the receiv ing part of the air conditioner If something blocks the transmitting and receiving path of the indoor unit and the r...

Page 6: ...r normal use batteries last about a year However change them whenever the indoor unit doesn t respond or responds slowly to commands or if the display becomes dark CAUTIONS z Replace all batteries at...

Page 7: ...te in the following order z AUTOMATIC OPERATION can be selected only by Heat pump split system or Heat recovery VRV system z For cooling only type COOLING and FAN and DRY operation are able to select...

Page 8: ...mp lights up or goes off and the system starts or stops OPERATION z The fan may keep on running for about 1 minute after the heating operation stops for removing the heat in the indoor unit z The air...

Page 9: ...purchase 3 Adjustment For programming TEMPERATURE FAN SPEED and AIR FLOW DIRECTION follow the procedure shown below TEMPERATURE SETTING Press TEMPERATURE SETTING button and program the setting temper...

Page 10: ...facing downward air flow direction may change unexpectedly There is nothing wrong with the equipment This serves to prevent dew formed on parts in the air discharge outlet from dripping z Operation m...

Page 11: ...ocedure ends The display or changes from flashing light to a constant light TIMER CANCEL Press the TIMER OFF button to cancel programming The display vanishes For example When the timer is programmed...

Page 12: ...peration mode between FAN DRY and COOL When the indoor unit with master remote controller is set to HEAT you can switch over operation mode between FAN and HEAT When the indoor unit with master remote...

Page 13: ...rates with the previously set air flow direction STOP Press the EMERGENCY OPERATION switch again 7 Precautions for Group Control System or Two Remote Controller Control System This system provides two...

Page 14: ...tioner the communication between the units is cut off and the unit stops When the noise is gone the unit automatically restarts III NO CHANGEOVER IS AVAILABLE BETWEEN HEATING AND COOLING MODES z The i...

Page 15: ...until the indoor unit beeps and perform the following operation according to the number of beeps Number of beeps 3 short beeps Perform all steps from 3 to 6 1 short beep Perform 3 and 6 steps 1 long...

Page 16: ...of the same number Signal transmitted from a remote controller of a different number cannot be accepted If the number is not mentioned it is considered as 1 2 The system operates but it does not suff...

Page 17: ...the unit does not work at all Remedial action Check the malfunction code A1 UF on the remote control and contact the place of purchase See page 60 MODE TIMER RESERVE CANCEL DOWN UP TEST SWING FAN TIM...

Page 18: ...ther a source of light nor fluorescent lamp near the receiver Also ensure that the receiver is not exposed of direct sun light z Ensure that the operaiton display lamp and other indicators are easy to...

Page 19: ...roller by sliding it in the direction of the arrow 2 Insert the attached dry cell batteries Properly insert set the batteries by matching the and polarity marks as indicated Then close the cover as be...

Page 20: ...and make the multiple setting as shown below 3 Stick the Unit No label on the air outlet of the decoration panel and the back of the wireless remote controller PRECAUTIONS Set the Unit No of the rece...

Page 21: ...harnesses from the transmission using provided clamps Installation of the Decoration Panel Install the decoration panel as described in the Installation Manual supplied with the decoration panel NOTE...

Page 22: ...re 1 When in the normal mode press the button for a minimum of four seconds and the FIELD SET MODE is entered 2 Select the desired MODE NO with the button 3 Push the button and select the FIRST CODE N...

Page 23: ...tting for spacing time of display time to clean air filter Setting for when filter contamination is heavy and spacing time of display time to clean air filter is to be halved Ultra long life type ligh...

Reviews: